HomeMy WebLinkAboutCD-106 Typical Driveway Detail
NOTES
LEGEND
* IF CURB AND GUTTER ARE POURED
SEPARATE OF APRON THEN DOWELS ARE
REQUIRED AT BACK OF CURB. 3" IN
CURB AND 9" IN CENTER OF APRON.
SEE DETAIL BELOW.
1. DRIVEWAY WIDTH SHALL BE 20' MAX. FOR
RESIDENTIAL AND 35' MAX. FOR COMMERCIAL.
2. WEAKENED PLANE JOINTS REQUIRED ON
CENTERLINE FOR DRIVEWAYS 10' TO 20' WIDE.
DRIVEWA YS 22' TO 35' WIDE SHALL HAVE TWO
WEAKENED PLANE JOINTS EVENLY SPACED AT
1/3 AND 2/3 POINTS.
3. ALL CONSTRUCTION AND MATERIALS IN
CONFORMANCE WITH CITY OF DUBLIN STANDARD
SPECIFICA TIONS.
4. THICKNESS OF APRONS SHALL BE 6" ON
RESIDENTIAL DRIVEWAYS AND 6" ON
COMMERCIAL DRIVEWAYS. ON COMMERCIAL
DRIVEWAYS, SIDEWALK SHALL BE REMOVED AND
REPLACED WITH 6" OF CONCRETE.
1"1:(;- ~~~~ _~~~ _~U_~T~~ _ ~~=-_3~0
#4x12" @ 24" OC (DOWELS)
GUTTER SEE CD-305 FOR DETAIL
EXPANSION
1" JOINT CD-306
WEAKENED PLANE JOINT
l' WIDE GROOVED BORDERS (CD-1 07)
MUST BE ON THE LEVEL SURFACE
AT THE TOP OF THE RAMPS
CURB AND GUTTER
REMOVE ENTIRE CURB AND GUTTER
POUR AS ONE UNIT *
.. (CURB AND GU~T~~_~~=-_3?0 12% MAX.
11:\-;-------~-2% MAX. I ~
- APRON""" T "
#4 @ 18" OC DRIVEWAY)
GUTTER BOTH WAYS
SECTION A-A
TYPICAL DRNEWAY DETAIL
SCALE: NOT TO SCALE
DATE: SEPTEMBER 13, 2006
DRA WN BY: LDH
V:\CAD\NEW STANDARDS
~.~
.h~
PUBLI WORKS DIRECTOR CD-I06