HomeMy WebLinkAboutItem 6.1 1994EdUniformBldgCd
"
CITY CLERK
File # [QJ~~[QJ-[2][QJ
..:.~
AGENDA STATEMENT
CITY COUNCIL MEETING DATE: December 12,1995
SUBJECT:
PUBLIC HEARING: ORDINANCE WHICH ADOPTS THE 1994 EDITIONS OF THE
UNIFORM BillLDING CODE; UNIFORM PLUMBING CODE;
UNIFORM MECHANICAL CODE; UNIFORM HOUSING CODE
AND THE 1993 EDITION OF THE NATIONAL ELECTRICAL
CODE.
~
EXIDBITS ATTACHED:
RECOMMENDATION:
~~
e.
FINANCIAL STATEMENT:
Report Prepared by: Kenneth C. Petersen, Building Official
1) / Draft Ordinance (red-lined version)
2) / Draft Ordinance
3) / Draft Resolution
1.
2.
3.
4.
5.
6.
Open Public Hearing
Receive Staff Report
Receive Public Testimony
Close Public Hearing
Deliberate
Waive Reading and adopt Ordinance which Adopts the 1994
Edition of the Uniform Building Code, 1994 Uniform
Plumbing Code, 1994 Uniform Mechanical Code, 1994
Uniform Housing Code and 1993 Edition of the National
Electrical Code, on an Urgency Basis.
Adopt Resolution relating to Findings of Necessity
7.
No measurable additional costs.
DESCRIPTION: The uniform model construction codes are adopted and published by
the California Building Standards Commission and by the California Department of Housing and ~,
Community Development on a three-year cycle. The provisions of this ordinance shall take effect on
January 1, 1996 pursuant to Government Code section 36937 as an urgency ordinance. The urgency is
based on the fact that the State published and adopted the 1994 editions of the model codes on July 1,
1995. A 4/5 vote is required to adopt the ordinance as an urgency ordinance.
The uniform codes must be adopted by the City as published unless the City Council adopts a resolution
finding that changes or modifications are necessary due to local climatic; geological or topographical
conditions. A number of such changes or modifications were made by the Council when it adopted the
1991 uniform codes.
..
- .
--------------------------------------------------------------------
COPIES TO:
a:agendaJubc1994.doc
ITEM NO.
~_/
The proposed ordinance adopting the 1994 model codes contains most of the same changes which were .
included in the City's adoption of the 1991 codes, except as noted in the following paragraphs. Some f
previous changes have been eliminated because the 1994 codes have incorporated these changes. For
example, current State law (1994 codes) now requires all new roofs, including re-roofmg, to be a
minimum Class C fire-retardant roof. Therefore, the City's prior change requiring Class C roofs is no
longer required.
I
e--
.0":
The proposed ordinance will streamline Chapters 7.28, 7.32, 7.40, 7.44 and 7.48 of the Dublin Municipal
Code which has many benefits for the City which include the following:
1. To ensure consistency with neighboring jurisdictions and the Bay Area.
2. To provide internally consistent, coherent and easier to use codes for City Staff.
3. To make it clearer for the public to review and to understand the uniform code
requirements.
The Rroposed ordinance does not adopt the Administration Chapters of the uniform codes which include
the permit fee tables, thus maintaining the City's current permit fees.
The provisions of the 1994 edition of the Uniform Building, Mechanical, Plumbing and Housing Code
have been reformatted into a "common code" format. The new format establishes a common format of
chapter designations for the three model codes published in the United States. A number of minor
changes to the Dublin Municipal Code are required as a result of the reformatting.
SUMMARY OF PROPOSED ORDINANCE:
1.
Therbe are 3f6thsecutio.~s of thBe .Mld~icCipadl Code that would be amended to refer to the new section e_-- __---.
num ers 0 e nl10rm Ul mg 0 e.
There are 2 sections of the Municipal Code that would be an referenced to an incorrect section of
the uniform code.
There are 12 sections of the Municipal Code that are in the new 1994 uniform code. These
Municipal Code sections are therefore no longer necessary.
There are 5 sections of the Municipal Code that would adopt the new uniform codes.
There is one section that coincides with State Law.
There are 13 new proposed changes to be added to the Dublin Municipal Code which are in
addition to changes carried over from 1991 (discussed in more detail below).
2.
3.
4.
5.
6.
SUMMARY OF PROPOSED CHANGES TO THE DUBLIN MUNICIPAL CODE:
1. Section 22 (Section 7.32.260 of the Dublin Municipal Code) is modified to require an automatic
fIre-extinguishing system when of Type V construction (which is construction consisting of the
lowest degree of fire resistance, in other words, buildings constructed of wood frame
construction). and when floor area exceeds 3,000 square feet in all occupancies except Group R,
Division 1 and 3 (which are single-family residences and multi-family residences).
The potential impact to buildings within the City of Dublin would total five (5) existing buildings.
The existing Dublin Municipal Code requires automatic fire-extinguishing systems in buildings
having areas in excess of 5,000 square feet. This requirement would only be triggered in existing e-.
buildings where square footage is added to the building. All proposed new buildings with areas
greater than 3,000 square feet would be required to have an automatic fire-extinguishing system.
e'" 3.
.:"7.
9.
2.
Section 23 (Section 7.32.260 of the Dublin Municipal Code) modifies the Uniform Building Code
to require an automatic fire-sprinkler system when any building except (private garages and utility
buildings) are located more than 1 'is miles from a fire station. This is an existing requirement of
the Dublin Municipal Code.
Section 25 (Section 7.32.270 of the Dublin Municipal Code) adds a requirement of a minimum of
one 1/2" diameter top and bottom reinforcement in all continuous foundations. This amendment is
necessary because the City of Dublin is within a very active seismic area (Seismic Zone 4) and
local soil conditions can be highly expansive clay soils. The Northridge earthquake provided
hundreds of examples of damage to plain concrete footings. This type of damage is extremely
expensive to repair, in contrast to the small expense of providing nominal footing reinforcement.
Footing reinforcement is also necessary to prevent damage due to pumping action caused by local
expansive soils which shrink and swell during seasonal drying and wetting conditions.
4.
Section 26 (Section 7.32.271 of the Dublin Municipal Code) modifies the Uniform Building Code
to require slab reinforcement. This modification is necessary due to the expansive soil conditions
and this is a typical minimum requirement by soil engineers in the City of Dublin in order to avoid
damage due to soil expansion and shrinkage.
..
5.
Section 27 (Section 7.32.272 of the Dublin Municipal Code) deletes the use of gypsum board for
lateral bracing. This deletion is necessary because the City of Dublin is located in Seismic Zone 4.
Gypsum wall~oard has performed poorly during recent California seismic events.
6.
Section 28 (Section 7.32.273 of the Dublin Municipal Code) limits the use of portland cement
plaster for lateral bracing to single story residential. This limitation is necessary because the City
of Dublin is located in Seismic Zone 4. Exterior portland cement plaster has performed poorly
during recent California seismic events.
Section 29 (Section 7.32.274 of the Dublin'Municipal Code) adds a new paragraph to require
upgrade of suspended ceiling systems for alteration and repair projects. This amendment is
necessary to mitigate a known seismic hazard in existing buildings due to the City of Dublin's
proximity to local active faults.
8.
Section 44 (Section 7.36.030 of the Dublin Municipal Code) limits the use ofNM and NMC
cables. The City of Dublin is located in the highly active seismic zone 4. Nonmetallic-sheathed
cable is not afforded the same protection from damage as wiring in a protective outer coating.
Damage to Nonmetallic-sheathed cable could occur in a seismic event which increases the
potential for a fire.
Section 50 (Section 7.40.105 of the Dublin Municipal Code) eliminates water piping in or under
concrete floor slabs within a building. This amendment is necessary for the following reasons:
1. Most of the surface soils in the City of Dublin are relatively young and unconsolidated
materials. The varying chemical composition, degree of weathering, and the relatively acid
environment have created soils of varying types, which are particularly corrosive in nature.
2. Much of the surface soil in the City of Dublin is highly expansive (i.e., shrink - swell behavior).
3. The local climate is characterized by markedly delineated rainy and dry seasons, which tend to
maximize the expansive characteristics of soil.
e' 4. Some parts of the City of Dublin have hard water, which is corrosive to ferrous pipe.
5. The groundwater table is unusually high in many places.
6. The City of Dublin is a highly active seismic area.
10.
Section 51 (Section 7.40.110 of the Dublin Municipal Code) requires backflow protection if
drainage piping serving fixtures is less than 12 inches above the next upstream manhole. This
requirements is necessary due to the fact that the City of Dublin topography includes mountainous
and foothill areas with intermittent steep slopes. Also, the City of Dublin is located'in a
seismically active area, which increases the likelihood of breakage of building sewers and laterals,
leading to an above average potential of sewage back-up into buildings without adequate
protection.
e"",
, '
11. Section 52 (Section 7.40.115 of the Dublin Municipal Code) adds a subsection regarding location
and termination of cleanouts. This subsection is necessary because the City of Dublin soils are
expansive in nature. These expansive soils create unstable conditions which increase the potential
_ of breaks in sewer laterals. To maintain health and sanitary services, it is necessary to gain access,
to periodically maintained public sanitary laterals. This is accomplished by the additional cleanout
as required above.
12. Section 53 (Section 7.40.120 of the Dublin Municipal Code) details cooling coil and comfort
cooling disposal and drain sizing. This amendment is required because the waste treatment
facilities serving the City of Dublin is operating at or near maximum capacity. The discharge of
treated waste water into San Francisco Bay is detrimental to its sensitive ecosystem.
Cooling coil and comfort cooling equipment condensate waste discharge does not contain
pollutants which require treatment before being discharged into storm sewers or the ground.
13.
Section 59 (Section 7.44.080 of the Dublin Municipal Code) amends the code to comply with
local sanitation district requirements regarding disposal for condensate for HV AC systems. The
waste water treatment facilities serving the City of Dublin is operating at or near maximum
capacity. The discharge of treated waste water into San Francisco Bay is detrimental to its
sensitive ecosystem.
e"':-
, ,
e:,;:
.
.'.:
."
.
ORDINANCE No. - 95
AN ORDINANCE OF THE CITY OF DUBLIN AMENDING CHAPTERS 7.28, 7.32,
7.40, 7.44, and 7.48 OF THE DUBLIN MUNICIPAL CODE AND ADOPTING BY
REFERENCE THE 1994 UNIFORM BillLDING CODE, UNIFORM PLUMBING CODE,
UNIFORM MECHANICAL CODE, UNIFORM HOUSING CODE AND THE
1993 NATIONAL ELECTRICAL CODE AND DECLARING THIS ORDINANCE
TO BE AN URGENCY ORDINANCE TO TAKE EFFECT JANUARY 1, 1996
The City Council of the City of Dublin does ordain as follows:
SECTION 1
Section 7.28.120 of the Dublin Municipal Code is amended to read:
- Section 7.28.120 Existing Buildings, Structures, or Installations.
A. Except as required by Section ~ 310.9.1 of the Building Code, and Sections 7.32.280 and
7.40.130, buildings or structures, electrical, plumbing or mechanical installations in existence at the time
of the adoption of this chapter may have their existing use or occupancy continued if such use or
occupancy was legal at the time of adoption of the ordinance codified in this chapter and provided such
continued use is not dangerous or substandard and does not menace health, life or property.
B. Electrical, plumbing and mechanical systems installed in apartments, hotels and dwelling and
in existence prior to January I, 1975, shall be deemed to have conformed to applicable law in effect at
the time of installation and to have been maintained in good condition of currently in good and safe
condition and working properly.
KEASON: Municipal Code has been reformatted to a new section number.
SECTION 2
Section 7.28.170 of the Dublin Municipal Code is amended to read:
Section 7.28.170 Appeals.
A. Any person aggrieved with any decision of the Building Official in connection with the
application or interpretation of the provisions of this chapter or in the approval of alternate materials or
methods of construction may appeal to the City Council. Such appeal shall be in writing and filed
within ten (10) days.
B. The City Council may after hearing, interpret any provision of this chapter.
C. The City Council may after hearing vary the application of this chapter in any specific case
when in its opinion the enforcement thereof would be contrary to the spirit and purpose of this chapter or
public interest. The City Council in granting a variance may impose requirements or conditions to
mitigate any adverse effects that may result from granting a variance.
D. In making any such interpretation or granting any variance the City Council shall make the
following findings:
1. That the interpretation or variance is consistent with the purpose of this chapter;
2. That the interpretation or variance will not lessen the protection to the people of the city and
the property situated therein.
1
i1<J.......ii~ Q~B' .IT 1
..... ,;.l ~l! e:
t...#~~ F[lt, _ ~
E. The City Council may approve alternate materials or methods of construction as set forth in
Section -H-:-W 7.28.140 by overruling the decision of the Building Official. In approval any alternate
materials or methods of construction the City Council shall make findings that the material, method or .. :',__'
work proposed is for the purpose intended, at least the equivalent of that prescribed by this chapter in
quality, strength, effectiveness, fire resistance, durability, dimensional stability and safety.
F. The City Council may appoint a Board of Appeals to hear any specific appeal. The Board of
Appeals shall consist of five (5) members qualified by training and experience to pass on matters
pertaining to the subject matter of the appeal and to serve until the disposition of the appeal. The Board
of Appeals shall have the same authority and duties as the City Council in interpreting this chapter,
granting variances, or approving alternate materials or methods of construction. The Building Official
shall be an ex officio member of the Board of Appeals and shall act as secretary to the board. The board
of appeals shall adopt reasonable rules and regulations for conducting its hearings and investigations.
The decision of the Board of Appeals shall be fmal.
RE~SON: This Municipal Code section was an incorrect reference.
SECTION 3
Section 7.28.290, of the Dublin Municipal Code is amended to read:
Section 7.28.290 Exceptions.
A. No permit shall be required for the following; however, permits shall be required for
electrical, plumbing and mechanical installations in any building or structure listed in subsections Al
through A18 of this section, and permits shall be required for all new construction and substantial
improvements that are located within an area of special flood hazard in which case a permit shall be
required as set forth in Chapter 7.24:
.,"
1. Open wire fences not more than sixteen (16) feet in height, masonry fences not more than six
(6) in height, and all other type fences not more than eight (8) feet in height;
2. Retaining walls which do not retain more than three (3) feet of earth when the earth retained is
level or where there is no surcharge load, and retaining walls which do not retain more than two
(2) feet of earth when the earth retained is sloping or which supports surcharge loads. See
Section 2516( c) 2317.11 of the Uniform Building Code for requirements for treatment of wood
used for retaining walls;
3. One-story detached accessory buildings used as tool and storage sheds, playhouses and
similar uses, provided the projected roof area does not exceed one hundred twenty (120) square
feet;
4. One-story buildings not more than four hundred (400) square feet in area used exclusively for
housing animals, poultry, livestock and similar animals and the storage of necessary food, hay or
grain for the animals housed therein;
5. ,Agricultural buildings as defined in Section ~ 202 of the Uniform Building Code on lots
exceeding twenty (20) acres in area which are located in an A zoning district and where the
principal use of the land is agriculture; ,
6. Lath houses and similar sun shade structure with roofs which do not shed water, which are not
more than ten (10) feet in height and one thousand (1,000) square feet in area;
7. Awnings over doors and windows of a Group R-3 or Group M!l:l Occupancy which are
entirely supported by the building and do not project more than fifty-four (54) inches;
e:
2
.'
. ,
e.'
"
e:
8. Temporary construction offices, and storage sheds which are used on a site where there is a
valid building permit, grading permit, or which are used in connection with a construction
project where no building permit or grading permit is required; however, this provision shall not
apply to such building remaining on the site 30 days after the completion of construction;
9. Temporary construction offices and storage sheds when stored in a contractor's equipment
yard; however, this provisions shall not apply if such buildings are used for any purpose
whatsoever;
10. Raised decks which are less than thirty (30) inches above the ground at any point;
11. Treehouses or other structures which are designed to be used by children for play;
12. Flag poles, radio or TV antennas and towers, less than thirty-five (35) feet in height when
not attached to a building and less than twenty (20) feet in height when attached to a building,
except permits are required for dish type antennas more than four (4) feet in diameter;
13. Swimming, bathing, and wading pools, and fish ponds not exceeding twenty-four (24)
inches in depth;
14. Prefabricated swimming pools, spas, or hot tubs not exceeding four (4) feet in depth if
resting on the surface of the ground or a concrete slab on the ground;
15. Painting, papering and similar finish work;
16. Moveable cases, counters, and partitions not over five (5) feet nine (9) inches high;
17. Water tanks supported directly upon grade if the capacity does not exceed five thousand
(5,000) gallons and the ratio of height to diameter or width does not exceed two to one;
18. Water storage tanks of any size ifresting on the surface of the ground or on a concrete slab
on the ground when used only for watering livestock or irrigation;
19. The replacement of lamps or the connection of portable electrical appliances to suitable
receptacles which have been permanently installed;
20. Nonelectrical, signs less than eight (8) feet in height, nonelectrical signs which do not
exceed three (3) pounds per square foot nor four (4) inches in thickness when fastened flat
against the wall of any building and provided further that the sign does not extend above the top
of the wall of the building.
21. Clearing stoppages or repairing leaks in pipes, valves, fittings or fixtures when such repairs
do not involve the replacement or rearrangement of pipes, valves, fittings or fixtures;
22. Buildings and structures owned by a sanitary district used exclusively for storage, collection,
conveying and treating sewage;
23. A permit shall not be required for demolition or exploration work that may be necessary in
order to determine conditions in connection with a proposed addition or alteration to an existing
building if an application for a permit is on file and prior approval for the demolition or
exploration work is obtained from the Building Official;
24. A permit shall not be required for small or unimportant work when approved by the Building
Official;
3
B. Exemption from the requirement of a permit shall not be deemed to be permissible to viol~te
any provision of this chapter or any other law, ordinance, rule or regulation.
C. Although permits are not required by this section, any person may obtain inspection services . '
by applying for a permit for such work and paying the applicable fee.
REASON: This Municipal Code section has been reformatted to new section numbers, also the
occupancy groups have been revised.
SECTION 4
Section 7.28.410 of the Dublin Municipal Code is amended to read:
Section 7.28.410 Building Official - Authority to Deny Permit.
The Building Official may refuse to issue any permit where it cannot be demonstrated that:
A. The hazards of land slippage, erosion or settlement will be eliminated;
2. The proposed work will not be located on a trace of an active fault;
3. The proposed work will conform to Chapters 7.20 and 7.24;
4. The placement of existing fills has not been subject to continuous inspection by a special
inspector as required by Section ~ 1701.5.13 of the Uniform Building Code;
5. The private water supply will conform to Section WQ..l...6..Q.L.Q of the Uniform Plumbing
Code.
6. The private sewage disposal system required by Section 713.0 of the Plumbing Code will
conform to Section 7.10.110 7.40.140;
7. Whenever a licensed contractor has failed to make corrections as specified in Section .. ':
7.28.540 through 7.28.580.
REASON: This Municipal Code section has been reformatted to new section numbers. The
referenced Municipal Code section was incorrectly referenced.
SECTION 5
Section 7.28.590 of the Dublin Municipal Code is amended to read:
Section 7.28.590 Special Inspections.
.^>.. In addition to the inspection required to be made pursuant to Sections 7.28.540 through
~2g.580, the owner shall employ a special inspector who shall be present at all times during
construction of the follo'.ving 'Node:
A. In addition to the inspections required by sections 7.28.540 through 7.28.580. Special
Inspections shall be provided in accordance with Chapter 17 of the Uniform Building Code.
1. Dur.ng the placing of reinforced concrete and taking of test specimens when the structural
desigR is based on a fe in excess oftvlO thousand fi'le hundred (2,500) pounds per square inch;
2. Ductile moment resisting concrete frame. .^>.s required by Section 26250) of the Uniform
Building Code;
3. Reinforcing steel and prestressing steel:
.
a. During all stressing and grouting of prestressed concrete,
4
.'
b. Checking reinforcing steel after it has been placed for all concrete required to ha~:e
special inspection by subsection Al of this section, .
c. Cheeking of tendons and prestressing steel after it has been placed for prestressed or
post tensioned concrete;
'1. 'Welding:
a. Ductile moment resisting steel frames. f...s required by Section 2722(F) of the
Uniform Building Code,
b. fJl structural welding, including '.velding of reinforcing steel. Exceptions:
i. V/hen v/elding is done in an approved fabricator's shop,
ii. \Vhen appro';ed by the Building Official, single pass fillet welds when stressed
to less than fifty percent (50%) of allo'.vable stresses;
5. High strength bolting: l\S required by U.B.c. Standard No. 27 7.
- Exception: The special inspector need not be present dur..ng the entire installation and tightening
operation, for shear/bear..ng type connections 'Nhen threads are not required by design to be
excluded from the shear plane, pro':ided that prior to the start of bolting, the surfaces and the bolt
size and typo are inspected for conformance to plans and specifications. f...dditionally, at the
completion of all bolting,. the inspector shall determine that the plies have been brought into
snug contact.
6. Structural masonry: during preparation of masonry wall prisms, sampling and placing of all
masonry units, placement of reinforcement, inspection of grout space, immediately prior to dosing of
deanouts and during all grouting operations,
Exception: special inspection will not be required for structures designed in accordance '.villi the
':alues in appropriate tables for noncontinuous inspection;
.",
7. Reinforced gypsum concrete: '.vhen cast in place Class B gypsum concrete is being mixed
and placed;
8. Insulating concrete fill: during the application of insulating concrete fill when used as part of
a structural system;
9. Applying spray on fire roofing;
10. Pile driving;
11. Shotcrete: during the taking of test specimens and placing of all shotcrete and as required by
Section 26210) and (k) of the Uniform Building Code.
Exception: shotcrete work fully supported on earth, minor repairs and when, in opinion of the
Building Official, on special hazard exists;
12. Preparation of the site for the placement of fills, and installation of subsurface drainage
facilities, and the placement offill as required by Section 2903 of the Uniform Building Code;
13. V/hen required by the Building Official for special construction or work im'olYing unusual
hazards, new construction methods, special testing, or \vhich requires constant inspection.
.' '. B. Prior to the issuance of a permit, the o','lner shall submit a complete description of the testing
, and inspection program for .:ipproyal by the Building Official. '
5
t
C. The special inspector shall be a qualified person who has demonstrated his competence to the
satisfaction of the Building Official f-or inspection of the particular type of construction or operation -
requiring spedal inspection. Documentary evidence of such competence shall be submitted to the .' ,
Building Official for approval.
D. Inspection and testing agencies perf-orming special inspection for concrete and steel 'Nork
shall conform to the requirements of ,^..STM E329 (Recommended Practice for Inspection and Testing
Agencies for Concrete and Steels as Used in Construction);
E. The special inspector shall file a report that from personallmov:ledge the work performed
dur..ng the period covered by the report has been performed and that the materials used and installed are
in accordance with the plans and specifications. The term "personal knowledge" means the actual
detailed knowledge acquired by the special inspector dur..ng Bis personal eontinumg observation of
construction work at the construction site in all states of progress.
F. Vlhene':er the special[ inspector is aware that work that does not comply v:ith this chapter is
proceeding, the inspector shall immediately notify the Building Official. The special inspector or testing
af;ency shall immediately notify the Building Official when materials tested do not meet the strength
specified.
REASON: The Special Inspections are incorporated in the Uniform Building Code.
SECTION 6
Section 7.32.030 oftlte Dublin Municipal Code is amended to read:
Section 7.32.030 Adoption.
Certain documents, a copy of which is on file in the office of the City Clerk, being marked as "Uniform
Building Code," 199M Edition, Volumes 1.2 and 3 including Appendix Chapters 11, 12, Division II and
Division 111,23 Division II and 111,32,35, 19 and 55, and "Uniform Building Code Standards," 1991
Edition, 3 Division II. 4 Division I. 12 Division II. 15. 18. 31 Division III and 33 published by the
International Conference of Building Officials is hereby adopted by reference as the building code of the
city pursuant to the provision of Section 50022.1 et seq. of the Government Code of the state of
California except as hereinafter modified in Section 7.32.110 through 7.32.420 this chapter.
REASON: This Municipal Code section adopts the 1994 edition of the Uniform Building Code.
.'
SECTION 7
Section 7.32.110 oftlte Dublin Municipal Code is amended to read:
Section 7.32.110 Chapter 1, ~, Administration - Deleted.
Part 1, including Chapters 1,2 and 3 are is deleted.
REASON: This Municipal Code Administration section addresses Chapter 1 of the 1994 Uniform
Building Code. '
SECTION 8
.
Section 7.32.120 of the Dublin Municipal Code is amended to read.
6
Section 7.32.120 Section 502, Chapter 5, Part III, 3405~ Chapter 34, Change in Use-
Deleted.
.. Section ~ 3405 is amended by deleting the third paragraph.
REASON: This Municipal Code section has been reformatted to reference a new section number
of uniform code.
SECTION 9
Section 7.32.130 of the Dublin Municipal Code is amended to read:
Section 7.32.130 Section ~ 504.6, Chapter 5, Part III, Area Separation Walls-
Amended.
Section ~ ~ is amended by adding a new item sub section 7504.6.7 to read:
+: 504.6.7 Area separation walls shall not be considered to create separate buildings for the purpose of
automatic fire-sprinkler system requirements as set forth in Chapter ~ 2..
Exception: Buildings separated by continuous area separation walls of four-hour fire-resistive
construction without openings. Buildings required to have automatic fire-sprinkler protection as set
forth in Section 13113 of the Health and Safety Code are prohibited from using area separation walls in
lieu of automatic fire-sprinkler protection.
REASON: This Municipal Code section has been reformatted to reference new section numbers
of uniform code.
.
SECTION 10
Section 7.32.140 of the Dublin Municipal Code is amended to read:
Section 7.32.140 Section~) 505.4, Chapter 5, Part III, fAllowable fArea Inereases
:\dded on Pages 37 and 38 ta read: Yard Restriction.
A new subsection fiB 505.4 is added to section
505.4 Yard Restriction. The increase in area permitted by Subsections W 505.1 and (b1505.2 of
this Section shall not be allowed unless or until the owner of the required yard shall file an agreement
binding such owner, his heirs, and assignees, to set aside the required yard as unobstructed space having
no improvements. Such agreement shall be recorded in the Alameda County Recorder's Office.
REASON: This Municipal Code section has been reformatted to reference new section numbers
of uniform code.
SECTION 11
Section 7.32.150 of the Dublin Municipal Code is deleted.
. f.". ction 1108 is ad~ed to read:
. , (a) ExtensioH Carage DaaF Springs. Evcry garage door spring installed in any garagc or
carport which is accessory to an apartment house,. hotel, motel or dwelling shall conform to the
following rcquircments:
7
1. Hard dra'.vn spring vMe shall conform to f~STM Designation .^~ 22 71, and shall be made by
the steel processes described therein, conforming to the chemical compositions requirements listed and
meeting the standards of steel heat as set forth by the Ladle i\nalysis. '''ire tensile strength and .:,~
dimension ':ariations shall meet the prescribed properties of established standards.
2. Oil tempered wire shall conform to :\STM Designation.\ 229 71, and shall be made by the
steel processes desoribed therein conforming to the chemical compositions requirements listed and
meeting the standards of steel heat as set forth by the Ladle Analysis. Wire tensile strength and
dimension variations shall meet the prescribed properties of established standards.
3. Extension springs sha:ll be fabricated from either hard dra'.vn spring '.'lire or oil tempered ';lire
as required n Subsections (a) 1 and (a) 2 abo'/e.
(b) Desigu Standards. :Minimum design standard shall be 9,000 oyeles. (One cyele is equal to
door opening plus door closing at maximum '.vorking load.)
- (0) Certifieation. 1. :Mill certification of'.vire physical tests and chemical properties shall be
kept on file by the spring manufaoturer. 2. Physical cycling tests shall be performed for each spring
design. and sha:ll be certified by an approved testing agency acceptable to the department and report kept
on file by the manufacturer. 3. Containment de'.1.ces shall be physically tested for each spring design by
installing the de'lice on the spring and by destroying the spring at mrodmum recommended stretch.
Containment tests shall be certified by an appro'led testing agency acceptable to the department and
reports kept on file by the manufacturer.
(d) Containment Deyiees. Each spring shall be equipped \'1ith an approved deyice capable of
restraining the spring or any part thereof in the event it brealcs.
(e) Identifieation. Springs shall be permanently identified as to manufacturer and also to .','
indioate maximum recommended stretch. Both springs and containment devices shall bear information
stating that they ha'le been manufactured in accordance with requirements of the California Department
of Housing and Community Development.
(t). Installation. Installation of springs, containment devices and hard'.vare shall be in
accordance '.'lith the manufacturer's installation instructions. Instructions shall be provided by the
manufacturer and shall specify the approved method of restraint and maximum recommended stretch.
Unless otherwise permitted by the manufacturer's installation instructions, the hardware and springs
shall be mounted to nominal 2 by 6 framing members which shall be of a species identified as Group I or
II in the Uniform Building Code Standards, Table No 25 17 J.
REASON: This Municipal Code section occurs in its entirety in the new uniform code.
SECTION 12
Section 7.32.155 of the Dublin Municipal Code is deleted.
Section 1201 is amended to read:
EJdts shall be provided as specified in Chapter 33. (See also Section 3317 for special requirements and
Section 3311 for mdt markings.)
f..ccess to, and egress from, buildings required to be accessible shall be proyided as specified in Chapter
:H-:
e::,
Basements in dwelling units and every sleeping room below the fourth story shall have at least one
operable window or door approved for emergency escape or rescue which sha:ll open directly into a
8
public street, public alley, yard or exit 0000. The units shall be operable from the inside to provide afull
clear opening without the use of separate tools.
.
All escape or rescue vnndows shall haye a minimum net clear openable area of 517 square feet. The
minimum net clear openable height dimension shall be 21 inches. The minimum net clear openable
width dimension shall be 20 inches. When vnndows are provided as a means of escape or rescue they
saall have a fmished sill height not more than 11 inches above the floor.
Bars, grilles, grates or similar devices may be installed on emergency escape or rescue vnndows or any
required exit door, proyided:
1. The devices are equipped \vith appro'led release mechanisms which are openable from the
inside vnthout the use of a key or special knowledge or effort; and
2. The building is equipped with smoke detectors installed in accordance '.vith Section 1210.
Such pars, grilles, grates or similar devices shall be equipped \vith an approyed release device for use by
the fire department only, on the exterior side for the purpose offire depar-..ment emergency access, when
required by the authority haYing jurisdiction.
REASON: This Municipal Code section occurs in its entirety in the new uniform code.
SECTION 13
Section 7.32.160 of the Dublin Municipal Code is amended to read:
Section 7.32.160 Section ~ 1617, Chapter ~ 16, Part VI, Wind Design - Amended
.' Kxposure Section 1617 is amended ta read:
Section ~ 1617 is amended to read:
Section 1617 Exposure.
All portions of the City of Dublin have a basic wind speed of 70 miles per hour.
All portions shall be exposure "B" except that all portions of the City of Dublin east of the
easterly city boundary as it existed on December 23, 1986 and all portions of the City of Dublin west of
the westerly city boundary as it existed on April 21, 1991 shall be exposure "C".
REASON: This Municipal Code section has been reformatted to reference a new section number
of the uniform code.
SECTION 14
Section 7.32.170 of the Dublin Municipal Code is amended to read:
Section 7.32.170 Table ~ 16-A, Chapter ~ 16, Part VI, Uniform and Concentrated
Loads - ,,'\mended. '
Table ~ 16-A is amended by adding a new footnote 9- 10 to read:
.' 9-: lQ. Bridges for vehicular traffic shall be designed for H20 loading as designated by the
, American Association of State Highway Officials.
REASON: This Uniform Code Table has been reformatted to a new chapter.
9
SECTION 15
Section 7.32.180 of the Dublin Municipal Code is deleted.
Roof Sheathing is amended by amending the fIrst paragraph to read:
Section 2517(h) 8 Roof Sheathing. Roof sheathing shall be in accordance 'l.ith Table 25 S 1 &
Table 25 S 2 for plyv/ood, or Table 25 S 3 f{)r particle board and Table 25 R 1 for diagona:1 sheathing
~
.'~'
REASON: The new uniform code addresses roof sheathing.
SECTION 16
Section 7.32.190 of the Dublin Municipal Code is deleted.
Section 2901 (a) is amended to read:
Section 2901 General. This chapter sets forth requirements goyerning grading drainage,
mitigation of geologic ha3ards, excavations and fills for any building or structure, and off{)undations
and retaining structures.
REASON: The new uniform code addresses this section.
SECTION 17
Section 7.32.200 of the Dublin Municipal Code is deleted.
Section 2903 is amended to read:
.",
Section 2903 Excavations and Fills.
(a) Ceneral. Excavations or fills f{)r any building or structure and excayations or fills accessory
thereto shall be so constructed or protected so that they do not endanger life or property.
(b) Crading Permits. Grading permits are required for excayations and fills as set forth in
Chapter 7.16.
(c) Exeayatians. ''.l/here exempt from grading permits, the slope of cut surfaces of permanent
excavations shall not be steeper than 2 horizontal to I verticaL Existing footings or foundations which
may be affected by any excayation shall be under pinned or othef'\l.ise protected against settlement and
sha:11 be protected against lateral movement.
(d) Fills. Where exempt from grading permits, slopes of permanent fills shall not be steeper
than 2 horizontal to I 'lertical. The ground surface shall be prepared to receiye fill by remoying
vegetation, topsoil and other unsuitable material and ',yhere slopes are 5 horizonta:1 to I yertical or steeper
by benching into sormd bedrock or other competent material.
(e) Existing Fill. .\ny fill which exceeds 5 feet in depth on slopes which elcceed ten (10)
percent and a:11 fills which v:ill be used to support the foundation of any building or structure v:hich
existed on :\ugust 1, 1971, and \vhieh 'NilS placed in conformanoe vlith the Alameda Cooo-ty Ordinanoe e' , ",
950 N.S. effccti'/e October 1, 1965, need not haye continuous inspection. .^..ll other fills which exceed 5
feet in depth on slopes which exceed ten (10) percent and all fills which ',viII be used to support the
foundation of any building or structure, which existed on August 1, 1971, shall be altered or completely
removed and replaced with continuous inspection by a special inspector. fJl:Y fill placed after f..ugust I,
10
.-
, ,
1971 'Nhich exceeds 5 feet in depth on slopes ',vhich exceed ten (10) percent or ,yhich will be used to
support the foundation of any building or structure 'Nithout continuous inspection by a special inspector,
shall be altered or completely remo'/ed and replaced with continuous inspection by a special inspector.
(f) Erosion Control. The faces of cut and fill slopes that are exempt from grading permits shall
be prepared and maintained to control against erosion. This control may consist of effective planting.
The protection of the slopes shall be installed as soon as practicable and prior to calling for fmal
inspection and approyal. V,lbere cut slopes are not subject to erosion due to the erosion resistant
character of the materials, such protection may be omitted.
(g) Protection of .^...djoining Property. The rights of coterminous O'.'lners shall be us set forth in
Section 832 of the Civil Code of the State ofCalif{)rnia.
REASON: The uniform code addresses this section.
_ SECTION 18
Section 7.32.210 of the Dublin Municipal Code is deleted.
Section 2905 is amended to read:
Section 2905 Soil and Geologic Investigation.
(a) '''heR Required. .^... soil and/or geologic inyestigation shall be required in the folloviing
circumstances:
.'
1. For all..^... 1,.^... 2, ..^... 2.1 and H Occupancies.
2. V,lben the allo'.voUe soil pressure used in the dcsign of the foundation exceeds 2,000 psf.
3. 'Alben the building is proposed to be supported in fill.
1. 'Alben the slope of the natural ground ,vithin 30 feet of any building or structure exceeds
twenty (20) percent and the slope is more than 10 feet in height.
5. "'hen a cut or a fill exceeding 5 feet in depth at any point either exists or is proposed and the
slope of the natural ground '.'lithin 30 feet of the building or the cut or fill exceeds ten (10) percent and
the slope is more than 10 feet in height.
6. 'Albere highly expansive or erodible soils are present unless it can be demonstrated to the
satisfaction of the Building Official that the structure will not bear on such soils, or that the
recommendations of a soils engineer are suitable.
7. In an subdivision into five or more parcels which hilS been recorded after September 17, 1965.
Where highly expansive soils or other soil conditions are present vlithin a subdivision, which if not
corrected would load to structural defects, a soil and/or geologic investigation report shall be required for
each lot in the subdivision.
8. On a building site trayersed or suspected to be traversed by a potentially active fault.
9. In areas ofknovr.n or suspected geological hazards, including landslide hazards and hazards
from earthquake caused ground shaking.
. 10. 'Alben otherwise requircd by the Building Official due to proposed design of the structure or
due to topographical or geological conditions on the building site.
11
(b) Prior Reports. l\Il soil and geologic reports prepared f-or a property, whether for the
proposed project or not, shall be submitted f-or a record of the conditions observed on the property at "
various times.
.-."
"
( c) Iavestigatien. Those portions of the investigation that are civil engineering as defIned by
Section 6731 of the Business and Prof-essions Code of the State ofCaJifomia shall be prepared by a soil
engineer who is a civil engineer registered by the State of CaJifornia. Those portions of the investigation
that involve the practiee of geology as defined by Section 7802 of the Business and Prof~ssions Code of
the State of California shall be prepared by an engineering geologist registered and certified by the State
of California.
The investigation shall be based on observation and tests of the materials disclosed by borings or
excavations made in appropriate locations. f...dditional studies may be necessary to evaluate soil
strength, the effect of moisture variation on soil, bearing capacity, compressibility and expansiveness.
(d) Reports. The soil and geologic in':estigation report shall contain all of the information
requirements set forth in Chapter 7.16 us they may be applicable to the particular site and any
recommendations contained therein shall be su-bj ect to the approval of the Building Official.
The site development and all buildings and structures shall be designed and constructed in accordance
with the recommendations contained in the soil and geologic investigation reports.
(e) Final Report. Upon completion of rough grading '.york and prior to the approval of the
foundation for any proposed building or structure, a final grading report as set forth in Chapter 7.16 and
as built grading plan prepared by a registered civil engineer including original ground surface elevatiofi5;
as graded ground surface elevations, lot drainage and location of all surface and subsurface drainage
facilities.
REASON: The requirements for foundation investigations are outlined in Section 1804 of the
new Uniform Building Code.
.:,
SECTION 19
Section 7.32.220 of the Dublin Municipal Code is deleted.
/\. nev,' Section 2911 is added to read:
Section 2911 Drainage. f...II portions of any building site including vent shafts, courts,
passageways, areav,'Q.Ys, and access drivev/ays shall be graded and drained so that '.vater \vill not pond or
occwnulate on the surface of any building site. f...Il portions of any building site shaJl be drained in such
a manner that it will not cau~e erosion or endanger the stability of any cut or fill slope or any building or
structure. When surfaoe drainage is discharged onto any adjoining property, it shall be discharged in
suoh a manner that it will not cause erosion or endanger any cut or fill slope or any building or structure.
REASON: The new Uniform Building Code Appendix Chapter 33 covers this section.
SECTION 20
Section 7.32.230 of the Dublin Municipal Code is amended to read:
Section 7.32.230 Section ~ 1503.1, Chapter ~ IS, Part VI, Special Requirements -
:\mended.
.
Section ~ 1503.1 is amended to read:
12
.'
.
.
Section 3209 1503.1 Special Requirements.
1. Map of Fire Safe Roof Areas. Figure ~ 15-1 * is a map of Fire Safe Roof areas. Said
map may be amended from time to time by including areas which are annexed to the City within one of
the two roofmg areas. Said amendments may be made by the Building Official after consultation, with
the Chief of the Dougherty Regional Fire Authority.
2. Roofing Area 1. Any new roof and any alteration, repair or replacement for buildings
housing R & M U-l occupancies in Roofmg Area 1 shall use roof covering material that conforms to
Class B or better when tested in accordance with UBC Standard ~ .li:2., or shall be made of concrete,
ferrous or copper metal, clay, slate or similar non-combustible material.
3. Roofing Area 2. f..ny new roof for buildings housing R or M oocupancies shall in Roofing
Area 2 use roof cO'/ering material that conforms to Class C or better when tested in accordance with
UEC Standard 32 7, or shall be made of concrete, ferrous or copper metal, clay, slate or similar non
combustible material.
lilly roof covering alteration including replacement or repair made '.vithin a 12 month period V/hich::
.^>.. Docs not exceed 25% of the projected area of the existing roof may use material similar to
the existing roof covering material.
E. Exceeds 25%, but does not eKceed 50% ofthe projected area of the existing roof coyering
materials as required for ne'.',' roofs.
3. Roofing Area 2. Any new roof for buildings using roof covering material that conforms to
Class C or better when tested in accordance with UBC Standard 15-2. or shall he made of concrete.
ferrous or copper metal. clav. slate or similar non-combustible material.
1. Roofing Area 3. .\n)' neVi roof for buildings housing R & M occupancies in Roofing .'\.rea 3
shall use roof covering material that conforms to Class C or better when tested in accordance with UBC
StJlldard 3207, or shall be made of concrete, ferrous or copper metal, clay, slate or other similar non
combustible material. fJlY .llterations, including replacement or repairs may be material similar to the
existing roof co';ering material, but may not use materials haying a lesser fire retardancy.
~. 1. Other Occupancies. Any new roof covering and any alterations, repairs or replacement of
roof covering material for buildings housing all other occupancies shall conform to the requirements a~
set forth in Roofing Area 1.
6. Other Provisions. Sk.)'lights shall be constructed as required in Chapter 31. Penthouses shall
be constructed as required in Chapter 36. For use of plastics in roofs, See Chapter 52. For solar energy
collectors located abo'/e or upon a roof See Section 1711
REASON: The State law now requires all new roofs to be a minimum Class "C" fire-retardant
roof. Therefore, the City's modification requiring Class "C" roofs is no longer required. Also, the
roof areas have been expanded to coincide with the city limits and future annexation.
SECTION 21
Section 7.32.250 oftlte Dublin Municipal Code is deleted.
Section 3703 (h) is amended to read:
(h) Spark fJTester. :-.11 chimneys attached to any appliance or fireplace that burns solid fuel shall
be equipped '.vith an appro';ed spark arrester. The net free area of the spark arrester shall be not less than
four times the net free area of the outlet ofthc chimney. The spark arrester screen shall have heat and
13
.
.~
.-'.i
-~
)
(....
. -
I
J
..
f,
. I
--1
'~f
,7
I
..(
)
::c
o
o
."
>-
;:::c
m
:>-
_.
",'
...
.;.
::!! I~
C) . ~::
c: '"
j ;:::c
m
j -
U"1
I
-
""--'
. .zc>-
i
! .
I--
I
t.
'---\
r---------"",
I' \
I i
I ~H~ I
I E~ ~
: ~~ :
-I n I
' "' I
I I
, I
I :
I :
>- ____..1 -r---___,
"..;.;J;;I : __',
m : ""
>- L-__, '__,-_
' "
' '-,-
' -,
: ", -"",
' ----
_.J
r-
,
I
.
I
,
I
I
,
I
,
,
I
I
I
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
\
· )-~~-1
ro
E~
-I",
"
~~
~~
'"
"
~
-I
5
:z
i'
::, I~
;'1
."
'::
:,:
'h .
fJ:r-: --
'" --------
I' ---
01,
'I'
:,1 .
I::: .
. :11
.11
."
'lI
:!i g
I It liD
II' r-
l;: z
'"
'II n
II' _
II: -4 .
I" -<
I',.
Ili'~ .
I" r
III _
III ""-4
Il' en
','
'"
'"
,"
I"
'Iil
II
It,
:::1-:'
'II
'" ",
,,,
I,'
: H
::1
H! .
:,:
,,'
"I
,,'
III, .
::iL'
",
II'
II:
'I,
:r:
Ii: ._
'jl
_c
(t)~
",:z
'. ~~
,,~
0",
~o
:z
"
c
::!
:;!.
r"
E~
~
"'"
"""
:0
:0'"
,.,1Il
III
,.,
~
~
6
z
,.
;:::c
o
o
...,.,
.....
I
I
I
!
lID
:~
n
o
c
:s
-<
J.ttcieru'o Dr:
~
Modiqon
Rd.
:\11
, <
(
!
i
"
r
"
1>
~
",,,,
"'"
"'Ill
0-1
Z
"..
r"
...
'"
)>
:0
"
/
/,
o
~
5'
l3~
-_3
-'D
~2.-
..
~
---,
I
,
To ES;;OrQ ~d.
.",
corrosion resistanee equi~lalent to 12 gauge wire, 10 gauge galvanized ~:lire or 21 gauge stainless steel.
Openings shall not permit the passage of spheres haying a diameter larger than 1/2 inch and shall not
block the passage of spheres having a diameter of less thafl 3/8 inch.
'When alterations, repair or additions requiring a permit and having a valuation in excess of$I,OOO.OO
occur in an existing building that has a chimney attached to any appliance, fireplace or incinerator that
bU:rIlS solid or liquid fuel and said chimney does not have a spark arrester, a spark arrester shall be
installed.
REASON: The new Uniform Building Code, Section 3102.3.8 addresses this section.
SECTION 22
Section 7.32.260 of the Dublin Municipal Code is amended to read:
. Section 7.32.260 Section ~ 904.2, Chapter ~ 2, Part VI, Automatic fire-extinguishing
systems - },.mended.
Section ~ 904.2. is amended to read:
Section 3802 904.2. Automatic Fire-Extinguishing Systems.
fa) 904.2.1 Where Required. An automatic fire-extinguishing system shall be installed in the
occupancies and locations as set forth in this section. For special provisions on special hazardous
chemicals and magnesium, and calcium carbide materials see the Fire Code.
.... W 904.2.2 All Occupancies Except Group R, Division 3 and Group M U Occupancies.
': Except for Group R, Division 3 and Group M 11 Occupancies, an automatic sprinkler system shall be
. . installed:
1. In every story or basement of all buildings when the floor area exceeds 1,500 square feet
(139.4m~) and there is not provided at least 20 square feet (1.86m~) of opening entirely above the
adjoining ground level in each 50 lineal (15 240m) or fraction thereof of exterior wall in the story or
basement on at least one side of the building. Openings shall have a minimum dimension of not less
than 30 inches (762mm). Such openings shall be accessible to the frre department from the exterior and
shall not be obstructed in a manner that firefighting or rescue cannot be accomplished from the exterior.
When openings in a story are provided on only one side and the opposite wall of such story is
more than 75 feet (22860mm) from such openings, the story shall be provided with an approved
automatic sprinkler system, or openings as specified above shall be provided on at least two sides of an
exterior wall of the story.
If any portion of a basement is located more than 75 feet (22 860mm) from openings required in
this section, the basement shall be provided with an approved automatic sprinkler system.
2. At the top of rubbish and linen chutes and in their terminal rooms. Chutes extending through
three or more floors shall have additional sprinkler heads installed within such chutes at alternate floors.
Sprinkler heads shall be accessible for servicing.
3. In rooms where nitrate film is stored or handled.
. 4. In protected combustible fiber storage vaults as defmed in the Fire Code.
. '.-~ 5. Throughout all buildings with a floor level with an occupant load of30 or more that is located
55 feet (16 764mm) or more above the lowest level of fire department vehicle access.
14
EXCEPTION: 1. AiI:port control towers.
2. Open parking structures.
3. Group F. Division 2 Occupancies.
W 904.2.3 Group A Occupancies. An automatic fire extinguishing system shall be installed in
all Group A Occupancies (except of Type V construction) where the floor area exceeds 5,000 square feet
and in all basements classified Group A Occupancy when the basement floor area exceeds 1,500 square
feet. Group A occupancies that are of Type V construction where the floor area exceeds 3.000 square
feet.
.
904.2.3.1 Drinking e~tablishments. An automatic sprinkler system shall be installed in rooms
used by the occupants for the consumption of alcoholic beverages and unseparated accessory uses where
the total area of such unseparated rooms and assembly uses exceeds 5.000 square feet (465 m.) (except
of Type V construction). For uses to be considered as separated. the separation shall not be less than as
required for a one-hour occupancy separation. The area of other uses shall be included unless separated
by at least a one-hour occupancy separation. Drinkin~ establishments that are of Type V construction
where the floor area exceeds 3.000 square feet (279 m )
" 904.2.3.2 Basements. An automatic sprinkler system shall be installed in basements classified as
a Group A Occupancy when the basement is larger than 1,500 square feet (139 m~) in floor area.
904.2.3.3 Exhibition and display rooms. An automatic sprinkler system shall be installed in
Group A Occupancies which have more than 12.000 square feet (112 m~) of floor area which can be
used for exhibition or display purposes.
904.2.3.4 Stairs. An automatic sprinkler system shall be installed in enclosed usable space below
or over a stairway in Group A. Divisions 2. 2.1. 3 and 4 Occupancies. See Section 1009.6.
904.2.3.5 Multitheater complexes. An automatic sprinkler system shall be installed in every
building containing a multi theater complex.
.:
904.2.3.6 Amusement buildings. An automatic sprinkler system shall be installed in all
amusement buildings. The main water-flow switch shall be electrically supervised. The sprinkler main
cutoff valve shall be supervised. When the amusement building is tempora:r:y. the sprinkler water-supply
system may be of an approved tempora:r:y type.
EXCEPTION: An automatic sprinkler system need not be provided when the floor area
of a tempora:r:y amusement building is less than 1,000 square feet (92.9 m~) and the exit travel
distance from any point is less than 50 feet (15 240 mm).
904.2.3.7 Stages. All stages shall be sprinklered. Such sprinklers shall be provided throughout
the stage and in dressing rooms. workshops. storerooms and other accessory spaces contiguous to such
stages.
EXCEPTIONS: 1. Sprinklers are not required for stages 1,000 square feet (92.9 m2) or
less in area and 50 feet (1542 rom) or less in height where curtains. scenery or other combustible
hangings are not retractable vertically. Combustible hangings shall be limited to a single main curtain.
borders. legs and a single backdrop.
2. Under stage areas less than 4 feet (1219 mm) in clear height used exclusively for chair
or table storage and lined on the inside with 5/8-inch (16rom) Type X gypsum wallboard or an approved
equal.
.'"
,.
15
.",
ftl1904.2.3.8 Group B Occupancies.
An automatic fire-extinguishing system shall be installed in Group B occupancies (except Type
V construction) where the floor area exceeds 5.000 square feet (465 m2). An automatic sprinkler system
shall b1 installed in Group B, of Type V construction where the floor area exceeds 3,000 square feet
(279 m ).
W 904.2.4.1 Group E Occupancies. An automatic frre-extinguishing shall be installed in all
Group E occupancies (except Type V construction) where the floor area exceeds 5,000 square feet. and
in all basements classified Group E occupancy where the basement floor area exceeds 1,500 square feet.
An automatic sprinkler system shall be installed in all Group E Occupancies of Type V construction
where the floor area exceeds 3,000 square feet.
904.2.4 Group E Occupancies.
. 904.2.4.1 General. An automatic fire sprinkle system shall be installed throu~hout all buildings
containing a Group E. Division 1 Occupancy.
EXCEPTION: 1. When each room used for instruction has at least one exit door directly to the
exterior at ground level and when rooms used for assembly purposes have at least one half of the
required exits directly to the exterior ~round level, a sprinkler system need not be provided.
2. When area separation walls. or occupancy separations having a fire-resistive rating of not less
than two hours subdivide the building into separate compartments such that each compartment
contains an aggregate floor area not greater than 20.000 square feet (1858 m~). an automatic
sprinkler system need not be provided.
e: An automatic fire:extinguishing system shall be in Group E. Division 2 and j occupancies .
, , (except Tvpe V constructIOn) where the floor area exceeds 5.000 square feet (465 m-). An automatIC
. sprinkler system shall be installed in Group E. Division 2 and 3 of Type V construction where the floor
area exceeds 3.000 square feet (279 m~1
904.2.4.2 Basements. An automatic sprinkler system shall be installed in basements classified as
Group Eo Division 1 Occupancies.
904.2.4.3 Stairs. An automatic fire sprinkler system shall be installed in enclosed usable space
below or over a stairway in Group E. Division 1 Occupancies. See Section 1009.6.
904.2.4.4 Group F Occupancies. An automatic fire sprinkler system shall be installed in all
Group F occupancies (except Type V construction) where the floor area exceeds 5.000 square feet (465
m~) an automatic sprinkler system shall be installed in all Group F occupancies of Type V construction
where the floor area exceeds 3.000 square feet (279 m~1
ff1904.2.5 Group H Occupancies. f..n automatic fire extinguishing system shall be installed in
Group H, Division 1, 2, and 3 Occupancies and in all Group H Di'lision 1 & 5 Occupancies when the
floor area exceeds 1,500 square feet.
904.2.5.1 General. An automatic fire-extinguishing system shall be installed in Group H.
Divisions 1. 2. 3 and 7 Occupancies.
904.2.5.2 Group H. Division 4 Occupancies. An automatic fire-extinguishing system shall be
installed in Group H. Division 4 Occupancies having a floor area of more than 3.000 square feet (279
,,)
..m z. [fT'\ 904253 G TT L: H D' .. 60 . g'" e An . fi
' \15J. .. roup ft--tt . IVISIOn ccupanCles. IYISIOn. automatIc lre-
extinguishing system shall be installed throughout buildings containing Group H, Division 6
16
occupancies. The design of the sprinkler system shall be not less than the required under U.B.C.
Standard No. ~ .2.:1 for the occupancy hazard classifications as follows:
Location
Occupancy Hazard Classification
.,'
Fabrication areas
Service corridors
Storage rooms without dispensing
Storage rooms with dispensing
F-xit corridors
Ordinary Hazard Group ~ 2
Ordinary Hazard Group ~ 2
Ordinary Hazard Group ~ 2
Extra Hazard Group 2 .I-
Ordinary Hazard Group; 21
Note: 1 When the design area of the sprinkler system consists of a corridor protected by one row of
sprinklers, the maximum number of sprinklers that need to calculated is 13.
W 904.2.6 Group I Occupancies. An automatic sprinkler system shall be installed in Group I
Occupancies.
EXCEPTION: Injails, prisons, and reformatories, the piping system may be dry, provided a
manually operated valve is installed in a continuously monitored location. Opening of the valve
will cause the piping system to be charged. Sprinkler heads in such systems shall be equipped
with fusible elements or the system shall be designed as required for deluge systems in U.BC.
Standard No. ~ .2.:1.
904.2.7 Group M. and S Occupancies. An automatic sprinkler system shall be installed in
Group M and S occupancies where the floor area exceeds 5.000 square feet (except Type V
construction). An automatic fire sprinkler system shall be installed in all retail sales rooms classed A
Group M and S occupancies of Type V cons~ction where the floor area exceeds 3.000 square feet.
fij 904.2.8 Group R, Division 1 Occupancies. An automatic sprinkler system shall be installed
throughout every apartment house three or more stories in height or containing 16 or more dwelling
units in congregate residences three or more stories in height and having an occupant load of 50 or more
and in hotels three or more stories in height or containing 20 or more guest rooms. Residential or quick
re$ponse standard sprinkler heads shall be used in the dwelling unit and guest room portions of the
building.
e'::"
..
904.2.8.1 Group R. Division I and 3 Occupancies. An automatic fire-extinguishing system
shall be installed where the total area exceeds 5.000 square feet (465m~1
FINDING: This section modifies the Uniform Building Code to require an automatic fire-
extinguishing system when of type V construction and the floor area exceeds 3,000 square feet in
all occupancies, except R. Division 1 and 3. This modification was necessary because the City of
Dublin has a dry period of at least five months each year. Additionally, the area is subject to
occasional drought. Because of dryness. a rapidly burning grass fire or exterior building fire can
quickly transfer to other buildings. These modifications are consistent with Dougherty Regional
Fire Authority requirements.
SECTION 23
Section 7.32.260 of the Dublin Municipal Code is amended to read:
tB 904.2.9 All Group A, B, E, H, I, & R-l & R-3 Occupancies. Automatic fire-extinguishing
systems shall be installed in all Groups A, B, E, H, I, & R-l & R-3 occupancies located more than 1 'is ..',',
miles from a fire station providing fire protection to that location. Said distance shall be measured in a
s~"aight line. For R-3 occupancies the sprinkler system may be a residential sprinkler system as set forth
in Item & of Section 3&.103 ~fUBC Standard 38 1. type NFPA 13.
17
Buildings containing portions which are required to have an automatic fIre extinguishing system
because of the number of stories shall have the automatic fIre extinguishing system installed throughout
.:, and area separation as set forth in Section 505(c).5.Qti shall not be considered as creating separate
,:.:.' buildings for the purpose of this section. '
When the specific use of a building is not known at the time of design and installation of the automatic
fIre-extinguishing system the design shall be based upon Ordinary Hazard Group ~2 as set forth in UBC
Standard ~ B.
Whenever an addition is made to an existing building automatic fire-extinguishing systems shall be
installed if the existing building plus the addition exceeds the area or height limitation set forth in this
section. Whenever the use of an existing building or portion thereof is changed in any manner so as to
require the installation of an automatic fIre-extinguishing system, said system shall be installed in that
portion of the building housing the new use.
FINDING: This modification was necessary because the City of Dublin has a dry period of at
least five months each year. Additionally. the area is subject to occasional drought. Because of
dryness, a rapidly burning grass fire or exterior building fire can quickly transfer to other
buildings. These modifications are consistent with Dougherty Regional Fire Authority
requirements.
SECTION 24
Section 7.32.270 of the Dublin Municipal Code is deleted.
."
Section 3803 is amended by adding a second exception to read:
Exception 2: Local alarms are acceptable for R 3 occupancies.
REASON: The change to the 1991 Uniform Building Code which was made by this section is no
longer necessary since it is now included in the 1994 Uniform Building Code Section
904.3.2
SECTION 25
Section 7.32.270 of the Dublin Municipal Code is added to read:
Section 7.32.270 Section 1806. Chapter 18. Footings.
7.32.270, Section 1806 is amended by adding the following at the end of the first paragraph:
A minimum of one top and one bottom continuous bars of 1/2" diameter reinforcing steel shall
L<; required in all continuous concrete or masom:y bearing foundations of Group R residential
occupancies.
FINDING: This section adds a requirement of a minimum of one 1/2" diameter top and bottom
reinforcement in all continuous foundations. This amendment is necessary because The City of
Dublin is within a very active seismic area (Seismic Zone 4) and local soil conditions can be highly
expansive (clay soil). The Northridge earthquake provided hundreds of examples of damage to
plain concrete footings. This type of damage is extremely expensive to repair, in contrast to the
. small expense of providing nominal footing reinforcement. Footing reinforcement is also
. ... necessary to prevent damage due to pumping action caused by local expansive soils which shrink
. and swell during seasonal drying and wetting conditions.
18
SECTION 26
Section 7.32.271 of the Dublin Municipal Code is added to read:
Section 7.32.271 Section 1924, Chapter 19, Minimum Slab Thickness.
Section 1924 is amended as follows:
e-
(a) General. The minimum thickness of concrete floor slabs supported directly on the ~ound
shall be not less than 3-1/2". The slab shall be reinforced with not less than six inches by six inches ten-
gauge wire mesh or an approved alternate installed at mid height of the slab.
FINDING: This section modifies the Uniform Building code to require slab reinforcement. This
modification is necessary due to the expansive soil conditions and this is a typical minimum
requirement by soil engineers in the City of Dublin in order to avoid damage due to soil expansion
and shrinkage.
SECTION 27
Section 7.32.272 of the Dublin Municipal Code is added to read:
Section 7.32.272 Section 2326.11.3, Chapter 23, Item 5 Deleted - Bracing.
Section 2326.11.3. Item 5 is deleted.
FINDING: This section deletes the use of gypsum board for lateral bracing. This deletion is
necessary because the City of Dublin is located in Seismic Zone 4. Gypsum wallboard has
performed poorly during recent California seismic events. The shear values for gypsum
wallboard contained in the code are based on mono-directional testing. It is appropriate to limit
the use of this product until cyclic loading testings are performed and evaluated.
e
SECTION 28
Section 7.32.273 of the Dublin Municipal Code is added to read:
Section 7.32.273 Section 2326.11.3. Chapter 23. Item 7, Amended Bracing.
Section 2326.11.3 Item 7 is amended as follows:
Portland cement plaster on studs spaced 16 inches on center installed in accordance with Table
No. 47-1. Limited to si~gle story R-3 and U-l occupancies.
FINDING: This section limits the use of portland cement plaster for lateral bracing to single
story residential. This limitation is necessary because the City of Dublin is located in Seismic Zone
4. Exterior portland cement plaster has performed poorly during recent California seismic events.
The shear values for portland cement stucco contained in the code are based on mono-directional
testing. It is appropriate to limit the use of this product until cyclic loading testings are performed
and evaluated.
SECTION 29
.,.
Section 7.32.274 of the Dublin Municipal Code is added to read:
Section 7.32.274 Section 3403.2. Chapter 34, Suspended Ceilings.
19
Section 3403.2 is amended by adding the following paragraph at the end ofthe Section folloWing
.- exceptions.
When a permit is issued for alterations or repairs. the existing sus.pended ceiling system within
the area of alteration or repair shall comply with the lateral design requirements ofUBC Standard 25-2
Part III.
FINDING: This section adds a new paragraph to require upgrade of suspended ceiling systems
for alteration and repair projects. This amendment is necessary to mitigate a known seismic
hazard in existing buildings due to the City of Dublin's proximity to local active faults.
SECTION 30
Section 7.32.280 of the Dublin Municipal Code is amended to read:
Section 7.32.280 Chapter 41, Part IV Section 1023, Appendix Chapter 10, Building
Security - Added.
Chapter ~ 1 Appendix 10 is amended to read:
Section 4Wl- 1023 Residential Security Requirements.
(a) Exterior doors. All exterior wood doors shall be of solid wood construction, no less than 1-
3/4 inches thick or hollow metal doors. Except for sliding glass doors, exterior doors hall not have
glazing larger than 2" unless glazing is 1/4" tempered glass.
.'-
<' (b) Locking devices. Exterior swinging doors shall have a lock on the latching device and an
auxiliary cylinder dead bolt. The dead bolt shall be hardened steel and have a I" throw. If the cylinder
of the lock protrudes from the face of the door it shall be fitted with a cylinder ring guard so it cannot De
gripped with pliers or other wrenching devices. Double doors shall have the inactive leaf secured with
flush bolts at top and bottom. The bolts shall be hardened steel 1/4" minimum in diameter and shall
engage a metal strike plate to a minimum depth of 3/8".
(c) Strike plates. Strike plates for wood jambs shall be the high security type and shall be
secured with a minimum of two wood screws 3" long which shall engage the door studs.
(d) Jambs. Inswinging doors with wood jambs shall have rabittedjambs. The jambs on the
strike side shall have continuous solid shims above and below the strike plates and the opposite jamb
shall have solid shims at the level of the strike plate. Both door studs shall be reinforced with horizontal
solid blocking at the approximate height of strike.
(e) Hinges. Exterior hinges and hinges of outswinging doors from the garage to the dwelling
shall have non-removable pins.
(f) Sliding glass doors. Sliding glass doors shall comply with Chapter M 24. Sliding glass
doors shall be fitted with a l"cking device that shall engage the strike sufficiently to prevent its being
disengaged by any possible movement of the door within the space or clearances provided for
installation and operation. The bolt and strike shall be reinforced by hardened material so as to prevent
their separation by pulling, prying or similar attack. An auxiliary locking device shall be installed on the
door which may be a pin, lock, or similar device of not less than 1/4 inch diameter. The pin shall be of a
hardened material and engage the metal portion of the sliding door. Doors with two sliding panels shall
be locked at the meeting rails and shall have an auxiliary locking device as described above.
.
(g) Entry vision. All main or front entry doors shall be fitted with a viewing device having a
field of view of not less than 180 degrees.
20
(h) Windows. All accessible dwelling windows shall be secure as follows:
1. Sliding glass windows shall be secured on the inside with a locking device capable of .',..
withstanding prying or wrenching. An auxiliary lock shall be installed on each sliding
window that prevents movement in the sliding track.
2. Louvered windows shall not be used within eight feet of ground level, adjacent
structures, or fire escapes.
3. Casement type windows shall be secured with a metal to metal locking device
contacting both frames of the window at the meeting edge. Auxiliary locks such as a pin
that penetrates both frame structures shall be installed on casement and double hung
windows.
4. Windows fitted with a crank type gear opening device shall be fitted with a positive
window lock that engages metal to metal.
Windows shall not be located within 40 inches of the locking device of any door unless
protected by a steel grill with 1/4" minimum diameter bars not more than 2" on center or
by a screen with 1/8" diameter wire mesh more than 2" on center mounted on the inside
or glazed with 1/4" tempered glass.
(i) Garage doors. Vehicle garage doors shall be secured with a metal to metal locking device
that prevents the door from being pulled or pried up from the outside. No electric garage door openers
shall be permitted that will automatically activate when the door is forced open. Garage doors fitted
with automatic openers shall be permitted with an alternative form of locking device activated from the
interior of the garage. Other garage doors shall comply with all of the provisions of this section.
G) Storage areas. Any exterior storage area attached to a dwelling, apartment or condominium
and enclosed by a door shall comply with this section or have a minimum 3/8" diameter hardened
padlock hasp.
Section ~ 1024 Non Residential Security Requirements
(a) Doors. Exterior doors which are located at the rear or side or away from the primary
entrance shall be solid doors with no glazing and shall be installed in metal frames. Exterior wood doors
shall be solid wood construction 1-3/4 inches thick or hollow metal doors.
. ,
.':
(b) Locking device. Exterior swinging doors which are exit doors as set forth in Chapter ~ 10
shall have cylinder dead-bolt locks which shall be openable without he use of key, special effort, or
knowledge. In Group B occupancies, a double cylinder dead-bolt lock may be used on the main exit
door if there is a readily visible, durable sign on, or adjacent, to the door stating, "this door to remain
unlocked during business hours." The sign shall be in letters not less than I inch high on contrasting
background. When unlocked the single door and both leaves of a pair of doors shall be free to swing
without operation of any latching device. Doors which are not exit doors shall have a double-keyed
cylinder dead-bolt. Double doors that are not exit doors shall have the inactive leaf secured with flush-
bolts at the top and bottoms. The bolts shall be hardened steel1/4" minimum diameter and shall engage
a metal strike plate to, a minimum depth of 3/8 inch.
The dead bolts shall be hardened steel and shall have a minimum of eRe 1-1/2 inch throw. If the
cylinder of the lock protrudes from the face of the door it shall be fitted with cylinder ring geared so that
it cannot be griped with pliers or other wrenching devices.
gVehicle doors, overhead doors, and sliding doors shall be secured with metal to metal locking devices
which prevent the door from opening.
(c) Strike plates. Strike plates for wood jambs shall be the high security type and shall be
secured with a minimum of two wood screws 3" long which shall engage the door studs.
.,,:
21
.'
(d) Jambs. Inswinging doors with wood jambs shall have rabittedjambs. The jambs on the
strike side shall have contin.lous solid shims above and below the strike plates and the opposite jamb
shall have solid shims at the level of the strike plate. Both door studs shall be reinforced with horizontal
solid blocking at the approximate height of strike.
(e) Hinges. Exterior doors shall have non-removable hinge pins.
e::
(f) Sliding glass doors. Sliding glass doors shall comply with Chapter M 24. Sliding glass
doors shall be fitted with a locking device that shall engage the strike sufficiently to prevent its being
disengaged by any possible movement of the door within the space or clearances provided for
installation and operation. The bolt and strike shall be reinforced by hardened material so as to prevent
their separation by pulling, prying or similar attack. An auxiliary locking device shall be installed on the
door which may be a pin, lock, or similar device of not less than 1/4 inch diameter. The pin shall be of
hardened material and engage the metal portion of the sliding door. The primary locking device shall be
operable by a keyed or code lock inside. Doors with two sliding panels shall be locked at the meeting
rails and shall have an auxiliary locking device as prescribed above.
(g) Windows. All accessible windows which are not located at the front or main entrance side
of a non-residential building shall be made secure as follows:
1. Sliding glass windows shall be secured on the inside with a locking device capable of
withstanding prying or wrenching. An auxiliary lock shall be installed on -each sliding
window that prevents movement in the sliding track.
2. Louvered windows shall not be used within eight feet of ground level, adjacent
structures, or fire escapes.
3. Casement type windows shall be secured with a metal to metal locking device
contacting both frames of the window at the meeting edge. Auxiliary locks such as a pin
that penetrates both frame structure shall be installed on casement and double hung
windows.
4. Windows shall not be located within 40" of the locking device of any door not located
on the main entrance side of the non-residential building unless the windows are glazed
with 1/4" tempered glass.
(h) Openable transoms. All exterior openable transoms exceeding 8" x 12" which are not
located on the front or main entrance side of a non-residential building shall be protected with a steel
grill with 1/4" minimum bars not more than 2" on center or by a screen with 1/8" diameter wire mesh
not more than 2" on center mounted on the inside.
(i) Roof openings. All skylights on the roof of a non-residential building shall be protected by:
1. Iron bars 1/2" minimum diameter not more than 8" on center or;
2. A screen with 1/8" diameter wire mesh not more than 2" on center. All roof access
hatches of a non-residential building shall be protected as follows:
(1). If the hatchway is of wooden material, it shall be covered on the inside with at
least 16 gauge steel or its equivalent attached with screws at 6";
(2). The hatchway shall be secured from the inside with a slide bar or slide bolts;
(3). Outside hinges on all hatchway openings shall be provided with non
removable pins when using pine-type hinges.
All air duct or air vent openings exceeding 8" x 12" on the roof or exterior walls of any
building or premise used for business purposes shall be secured by covering the same
with either of the following:
.'
1. Iron bars of at least 1/2" round or 1" x 1/4" flat steel material, spaced no more than 8"
apart and securely fastened.
G) Exterior ladders. Exterior ladders to the roof are not permitted.
22
REASON: This Municipal Code section has been reformatted to new sections. Also. this section is
now consistent with the City of Dublin Police Department.
SECTION 31
.
Section 7.32.290 Dublin Municipal Code is deleted.
Section 7.32.290, Seetien 4306(m), Chapter 43, Part VII, Fire resistive }",ssemblies fer
Protection of Openmgs Deleted.
REASON: This Municipal Code section is covered in the California Building Code.
SECTION 32
Section 7.32.300 of the Dublin Municipal Code is amended to read:
Section 7.32.300 Section 44Dl-ll!U, Chapter 44 .3.3., Part VIII Protection of Pedestrians
During Construction or Demolition - .\mended.
Section 44G+ 3303.1 is amended to read:
Section 44G+ 3303.1 General. No person shall place or store any material or equipment
necessary for the work authorized by any building permit on any street or alley or public sidewalk unless
an encroachment permit is provided by Chapter 7.04, Dublin Municipal Code, has been secured. No
person shall perform any work on any building or structure if by so doing it endangers pedestrians on the
street that abuts the property, unless the protection of pedestrians as specified in this code is provided.
No encroachment permit shall be required for the construction of any railing, fence, or canopy used for
the protection of pedestrians if there is a valid building permit in effect for such work and the railing,
fence or canopy does not extend beyond the curb or gutter if there is no curb.
T,-~ASON: This Municipal Code section has been reformatted to new section of uniform code.
."'.'
, ,.
. '
SECTION 33
Section 7.32.310 of the Dublin Municipal Code is amended to read:
Section 7.32.310 Section ~ 3303.2, Chapter 44.3.3., Temporary Use of Streets and Alleys
- Deleted.
Section 44Q2. 3303.2 on page 713 is deleted.
REASON: This Municipal Code section, chapter and page number have been reformatted.
SECTION 34
Section 7.32.320 of the Dublin Municipal Code is amended to read:
Section 7.32.32 Section 44()J 3303.3, Chapter 41, Part VIII.3.3., Storage on Public Property
- Deleted.
Section 4-4-(B 3303.3 on page 713 is deleted.
e','
.'
REASON: This Municipal Code section, chapter. and page number have been reformatted.
23
.
."
.
SECTION 35
Section 7.32.330 of the Dublin Municipal Code is amended to read:
Section 7.32.330 Section 4404 3303.4, Chapter 44 Part VIII 33" Mixing Mortar on Public
Property - Deleted.
Section 4494 3303.4 on page 713 is deleted.
REASON: This Municipal Code section, chapter, and page number have been reformatted.
SECTION 36
Section 7.32.340 of the Dublin Municipal Code is amended to read:
Section 7.32.340 Section 44()S 3303.5, Chapter 44 Part VIII 33" Protection of Utilities -
Deleted.
Section ~ 3303.5 on page 713 is deleted.
REASON: This Municipal Code section. chapter, and page number have been reformatted.
SECTION 37
Section 7.32.350 of the Dublin Municipal Code is amended to read:
Section 7.32.350 Section ~ 3201, Chapter 4$ 32, Part VIII General - _\meBded.
Section 4W+ 3201 is amended to read:
Section 4W+ 3201. No part of any structure or any appendage thereto shall project beyond the
property line of the building site except as specified in this chapter. Structures or appendages regulated
by this code shall be constructed of materials as specified in Section H-l-l- 705. The projection of any
structure or appendage shall be the distance measured horizontally from the property line to the
outermost point of the projection. No provision of this chapter shall be construed to permit the violation
of other laws or ordinances regulating the use and occupancy of public property.
REASON: This Municipal Code section, chapter. and page number have been reformatted.
SECTION 38
Section 7.32.360 of the Dublin Municipal Code is deleted.
Section 7.32.360 Section ~ 3202, Chapter 4$ 32, Part VIII Projection into Alleys -
Deleted.
Section ~ 3202 on page 717 is deleted.
REASON: This Municipal Code section. chapter, and page number have been reformatted.
SECTION 39 _
Section 7.32.370 of the Dublin Municipal Code is amended to read:
24
Section 7.32.370 Section ~ 3Z!l3., Chapter ~ 32., Part VIII Space Below Sidewalks-
Deleted.
Section #00- 3203 on page 717 is deleted.
REASON: This Municipal Code section. chapter, and page number have been reformatted.
.',.~"
"
SECTION 40
Section 7.32.380 of the Dublin Municipal Code is amended to read:
Section 7.32.380 Section 4$08 3Z.O.H, Chapter ~ 32, Part VIII Signs - Added.
A new Section 4W812Q.8. is amended added to read as f{)llows:
Section 4W812Q.8. Signs. Signs when placed flat against the wall of a building shall not project
beyond the front property line not more than 12 inches.
REASON: This Municipal Code section, chapter, and page number have been reformatted.
SECTION 41
Section 7.32.390 of the Dublin Municipal Code is amended to read:
Section 7.32.390 Section 4706(d) 2506.4, Chapter 47 25, Part VIII, Weather-resistive
Barriers - Amended.
Section 1706(d) 2506.4 is amended to read:
Section 1706 (d) 2506.4. Notwithstanding the provisions of +7G+ 1402.1 the weather-resistive
barrier for exterior stucco shall be either Type 15 felt or Grade D craft building paper having a 60-
lr~mute water-resistance when tested in accordance with UBC Standard 14-1. Two layers of the weather-
resistive barrier shall be appiied over wood sheathing.
.
REASON: This Municipal Code section. chapter, and page number have been reformatted.
SECTION 42
Section 7.32.400 of the Dublin Municipal Code is deleted.
Seetion 7.32.400 Seetion 1243(a) 1, Chapter 12, }....ppendix, Outdoor Swimming Pool
Deleted.
REASON: This Municipal Code section is addressed in the new Uniform Building Code
Appendix Chapter 4, Division I.
SECTION 43
Section 7.32.420 of the Dublin Municipal Code is deleted.
.'
Section 7.32.420, Section 3501(a), Chapter 35, }...ppendix, Sound Control Transmission
:r,*,~
25
REASON: This Municipal Code section is addressed in the new Uniform Building Code
Appendix Ch?JJter 12. Division II.
.-,
SECTION 44
Section 7.36.030 of the Dublin Municipal Code is amended to read:
Section 7.36.030 Adoption.
7.36.030 AdaptioB.
The "National Electrical Code.f-9.W .l.22.3.," published by the National Fire Protection
Association, a copy of which is filed in the office of the City Clerk, is adopted by reference as the
electrical code for the city pursuant to the provisions of Section 50022.1 et seq. of the Government Code
of the state of California, except as hereinafter modified in Sections 7.36.070 and 7.36.080 of this
chapter.
REASON: This Municipal Code section adopts the 1993 Edition of the National Electrical Code.
SECTION 45
.
Section 7.36.090 of the Dublin Municipal Code is added to read:
Section 7.36.090, Article 336-4 is amended by replacing it with the following:
(a) Type NM or NMC. Types NM and NMC cables shall not be used (1) in any dwelling or
structure exceeding three floors above grade: (2) as service-entrance cable: (3) embedded in poured
concrete: or (4) in any non-residential occupancy. For the purpose of this article. the first floor of a
building shall be that floor that has 50 percent or more of the exterior wall surface area level with or
above finished grade. One additional level that is the first level and not designed for human habitation
and used only for vehicle parking. storage. or similar use shall be permitted.
FINDING: This section limits the use ofNM and NMC cables. The City of Dublin is located in a
highly active Seismic Zone 4. Nonmetallic-sheathed cable is not afforded the same protection from
damage as wiring raceways. Damage to Nonmetallic-sheathed cable could occur in a seismic event
which increases the potential for a fire.
SECTION 46
Section 7.40.030 of the Dublin Municipal Code is amended to read:
Section 7.40.030 Adoption.
The "Uniform Plum1,ing Code".J.99.l. 1994 Edition, published by the International Association of
Plumbing and Mechanical Officials, including Appendix Chapters A, B, G;- D, E, H, and I, and all
installation standards, a copy of which is filed in the office of the City Clerk is adopted by reference as
the plumbing code for the city pursuant to the provision of Section 50022.1 et seq. of the Government
Code of the state of California except as hereinafter modified in Section 7.40.075 through 7.40.150 of
this chapter.
. REASON: This Municipal Code section adopts the 1994 Edition of the Uniform Plumbing Code.
26
SECTION 47
Section 7.40.075 of the Dublin Municipal Code is amended to read:
Section 7.40.075 Section ~ ill, Chapter 3 Prohibited Fittings and Practices - ...A...meBded.
Section ;H4lli is amended by adding a new subsection ffi 1lL2 to read:
ffi 1lL2 Plastic piping shall not be exposed as a portion of the interior room finish in a building
or structure if the piping has flame-spread rating exceeding 75 when tested in accordance with ASTM E
84-77a Test for Surface Burning Characteristics of Building Materials.
REASON: This Municipal Code section has been reformatted.
e::
..
SECTION 48
Section 7.40.090 of the Dublin Municipal Code is amended to read:
Section 7.40.090 Section 401(8) 401, Chapter 4, Materials- ...\meBded.
Section 101(u) 401 is amended by adding a new subsection 401.3 to read:
W 401.3. Drainage piping shall be cast iron, galvanized steel, galvanized wrought iron, lead,
copper, brass, Schedule 40 ABS DWV, Schedule 40 PVC DWV, extra-strength vitrified clay pipe, or
other approved materials having a smooth and uniform bore, except that:
(1) No galvanized wrought iron or galvanized steel pipe shall be used under ground and shall be e.,,,,,
kept at least six (6) inches (152.4 mm) above ground.
(2) ABS and PVC DWV piping installations shall be limited to structures not exceeding three
floors above grade. For the purpose of this subsection, the frrst floor of a building shall be that floor that
has fifty (50) percent or more of the exterior wall surface area level with or above fmished grade. One
additional level that is the first level and not designed for human habitation and used only for vehicle
parking, storage, or similar use shall be permitted.
(2.1) ABS and PVC installations are limited to residential construction not more than two (2)
stories in height and to reIocatable public school buildings.
(3) No vitrified clay pipe or fittings shall be used above ground or when pressurized by a pump
or ejector. They shall be kept at least twelve (12) inches (304.8mm) below ground.
REASON: This Municipal Code section has been reformatted.
SECTION 49
Section 7.40.100 of the Dublin Municipal Code is amended to read:
Section 7.40.100 Section 503(8) 503.0, Chapter 5, Materials.; ...A...meBded.
Section 503(u) 503 is amended by adding a new subsection 503.1 to read:
fa) SeetioB 501.1 Materials. Vent pipe shall be cast iron, galvanized steel, galvanized wrought e~
iron, lead, copper, brass, Schedule 40 ABS DWV, Schedule 40 PVC DWV, or other approved materials
having a smooth and uniform bore, except that:
27
.
.
.
(1) No galvanized wrought iron or galvanized steel pipe shall be used under-ground and shall be
kept at least six (6) inches above ground. '
(2) ABS and PVC DWV piping installations shall be limited to structures not exceeding three
floors above grade. For the purpose of this subsection, the first floor of a building shall be that floor that
has fifty percent or more of the exterior wall surface area level with or above fmished grade. One
additional level that is the fIrst level and not designed for human habitation and used only for vehicle
parking, storage, or similar use shall be permitted.
(2.1) ABS and PVC installations are limited to residential construction not more than two (2)
stories in height.
(b) Vent fittings shall be cast iron, galvanized malleable iron or galvanized steel, lead,
copper, brass, ABS, PVC, or other approved materials, except that no galvanized malleable iron
or galvanized steel fitting shall be used underground and shall be kept at least six (6) inches
(I 52.4mm) above ground.
(c) Changes in direction of vent piping shall be made by the appropriate use of approved
fittings and no such pipe shall be strained or bent. Burred ends shall be reamed to the full bore of
the pipe.
REASON: This Municipal Code section has been reformatted.
SECTION 50
Section 7.40.105 of the Dublin Municipal Code is added to read:
Section 7.40.105 Section 609.3, Chapter 6. Water Piping in Slab Floors.
Section 609.3. First paragraph. is amended by replacing it to read:
Section 609.3 Water piping shall not be installed in or under a concrete floor slab within a
building without prior approval of the Building Official. When approved. such piping shall be installed
in accordance with the following requirements:
FINDING: This section eliminates water piping in or under concrete floor slabs within a building.
This amendment is necessary for the following reasons:
1. Most ofthe surface soils in the City of Dublin are relatively young and unconsolidated
sedimentary materials formed from a wide variety of parent materials. The varying
chemical composition, degree of weathering and the relatively acid environment have
created soils of varying types, which are particularly corrosive in nature.
2. Much ofthe surface soil in the City of Dublin is highly expansive (i.e., shrink-swell
behavior) and have low bearing strength.
There are two types of expansive soils in the area:
a. the organic silty clays which are the recent bay muds; and
b. the plastic silty clays which weather from the shale found in the hills surrounding
the City of Dublin.
3. The local climate is characterized by markedly delineated rainy and dry seasons, which
tend to maximize the expansive characteristics of soil.
4. Some parts of the City of Dublin have hard water. which is corrosive to ferrous pipe.
28
5. The groundwater table is unusually high in many places.
6. The City of Dublin is a highly active seismic area.
.'
SECTION 51
Section 7.40.110 of the Dublin Municipal Code is added to read:
Section 7.40.110 Section 710.1, Chapter 7, Backwater Valves.
Section 710.1 is amended to read:
Section 710.1 Draina~e pipin~ servin~ fixtures which have flood level rims less than twelve (12)
inches (304.8mm) above the elevation of the next upstream manhole and/or flushin~ inlet cover at the
public or private sewer system servin~ such draina~e pipin~ shall be protected from backflow of sewa~e
by installin~ an approved type backwater valve. Fixtures above such elevation shall not dischar~e
throu~h the backwater valve. unless first approved by the Buildin~ Official.
FINDING: This section requires backflow protection if drainage piping serving fixtures is less
than 12 inches above the next upstream manhole. This requirement is necessary due to the fact
that the City of Dublin topography includes mountainous and foothill areas with intermittent
steep slopes. Also. the City of Dublin is located in a seismically active area, which increases the
likelihood of breakage of building sewers and laterals, leading to an above average potential of
sewage back-up into buildings without adequate protection.
SECTION 52
.-:.
Section 7.40.115 of the Dublin Municipal Code is added to read:
Section 7.40.115 Section 719.7. Chapter 7, Cleanouts.
Section 719.7 is amended by adding subsection 7 to read:
Section 719.7 Cleanouts shall be installed at the property line where the private sewer system
connects to the publicly-maintained sanitary sewer lateral. All such line cleanouts shall be extended to
grade with materials and accordin~ to specifications approved by the Buildin~ Official and terminate
within a concrete box.
FINDING: This section adds a subsection regarding location and termination of cleanouts. This
subsection is necessary because the City of Dublin soils are expansive in nature. These expansive
soils create unstable conditions which increase the potential of breaks in sewer laterals. To
maintain health and sanitary services, it is necessary to gain access, to periodically maintained
public sanitary laterals. This is accomplished by the additional clean out as required above.
SECTION 53
Section 7.40.120 of the Dublin Municipal Code is amended to read:
Section 7.40.120 Section 807.2, Chapter 8, Condensate Disposal.
Section 807.2 is amended by replacin~ it to read:
.,-
29
.
Section 807.2 Condensate from air-cooling coils and comfort cooling equipment not intended to
be used for the storage or holding of food or drinks shall be collected and discharged to a storm sewer or
other approved points of disposal acceptable to the Building Official.
Termination of such drains shall be made by an air break. Condensate drain lines in sizes 11/4" and
larger shall be assembled using approved drainage pipe and fittings. Condensate waste water shall not
drain over or upon a public way. sidewalk. pedestrian ramp or the like. Condensate drains within the
interior of a building shall not be connected to the building roof drain or overflow piping systems. The
waste pipe shall have a slope of not less than 1/8 inch per foot and shall be of approved corrosion-
resistant material not smaller than the outlet size as required below for air-cooling coils or condensing
fuel-burning appliances. respectfully.
Condensate wastes pipes from air-cooling coils shall be sized in accordance with equipment capacity as
follows:
Equipment Capacity
Up to 20 tons of refrigeration
21 to 40 tons of refrigeration
41 to 90 tons of refrigeration
91 to 125 tons of refrigeration
126 to 250 tons of refrigeration
Minimum
Condensate
Pipe Diameter
3/4 inch
1 inch
1 1/4 inch
1 1/2 inch
2 inch
The size of condensate waste pipes mav be for one unit or a combination of units, or as recommended by
the manufacturer. The capacity of waste pipes assumes a 1/8 inch-per-foot slope. with the pipe running
three-quarters full.
.
Condensate drain sizing for other slopes or other conditions shall be approved by the Building Official.
FINDING: This section details condensate disposal and drain sizing. This amendment is required
because the waste treatment facilities serving the City of Dublin is operating at or near maximum
capacity. The discharge of treated water into San Francisco Bay is detrimental to its sensitive
ecosystem.
C'ooling coil and comfort cooling equipment condensate waste discharge does not contain
pollutants which require treatment before being discharged into storm sewers or the ground.
SECTION 54
Section 7.40.130 of the Dublin Municipal Code is amended to read:
Section 7.40.130 Section 1005(g) 608.7, Chapter -l-O- Q, Water Pressure, Pressure Regulators
and Pressure Relief Valves - Added.
Section 1 005(~) 608.0 is amended by adding a new subsection W 608.7 to read:
tgj608.7 Each riser or branch shall be provided with an accessible sectionalizing valve in hot
and cold-water systems to permit servicing or replacement of piping or equipment. Stop valves shall be
provided at each fixture.
. REASON: This Municipal Code section and chapter has been reformatted.
30
SECTION 55
Section 7.40.140 of the Dublin Municipal Code is amended to read:
Section 7.40.140 Section ~ 713.0, Chapter 7, Sewer Required.
Section .f..l.(f.l.. 1.l.JJ! Sewer Required.
Every building in which plumbing fixtures are installed and every premises having drainage
piping thereon shall have a connection to a public sewer. Except that where there is no available public
sewer within 200 feet, measured along streets, alleys, or public right-of-way upon which a lot abuts, and
when the size of the property is in excess of 40,000 square feet, drainage piping from any building or
works may be connected to an approved private sewage disposal system. All such sewage disposal
systems shall be designed, constructed, operated, and maintained in compliance with the Health
Officer's regulations.
.'
Not withstanding the provisions of Section 320 and Section 11.8 of this Ordinance.
Whenever a public sewer is extended so as to become within 200 feet of any premises having a private
sewage disposal system, said private sewage disposal system shall be abandoned and the building sewer
shall be connect to the public sewer.
No permit shall be issued for the installation, alteration or repair of any private sewage disposal system
or part thereof of any premises for which a public sewer is within 200 feet.
On every lot or premises hereafter connected to a public sewer, all plumbing and drainage systems or
parts thereof on such lot or premises shall be connected to such public sewer.
REASON: This Municipal Code section and chapter has been reformatted.
.'
SECTION 56
Section 7.40.150 of the Dublin Municipal Code is amended to read:
Section 7.40.150 Section 1110(e) 308.3, Chapter 11 3, Location - Added.
Section +HQ ~ on page 88 is amended by adding a new subsection W 1Q.8.J. to read:
W 308.3 It shall be unlawful to sell, transfer, divide, or set off any portion of any lot which in
any way reduce the minimum areas set forth in Section.f..l.(f.l.. 713.0 or reduce the minimum distances set
forth in Table H 7-7.
E.$ASON: This Municipal Code section and chapter has been reformatted.
SECTION 57
Section 7.44.030 of the Dublin Municipal Code is amended to read:
Section 7.44.030 Adoption.
Section 7.11.030 i\doption.
.:.
The "Uniform Mechanical Code" +99+l2.2.1 Edition, published by the International Association
of Plumbing and Mechanical Officials and the International Conference of Building Officials, including
Appendix Chapters A, B, C and D, a copy of which is filed in the office of the City Clerk, is adopted by
31
,
reference as the mechanical code for the city pursuant to the provisions of Section 50022.1 et seq. of the
Government Code of the state of California except is hereinafter modified in Section 7.44.070.
REASON: This Municipal Code section adopts the 1994 Edition of the Uniform Mechanical
Code.
e:
SECTION 58
Section 7.44.070 of the Duhlin Municipal Code is amended to read:
Section 7.44.070 Chapter 1, Administration - Deleted.
Chapter 1, including Chapters 1, 2 and 3 Parts I, II, and III is deleted.
REASON: This Municipal Code section and chapter has been reformatted.
SECTION 59
eo,
Section 7.44.080 of the Duhlin Municipal Code is added to read:
Section 7.44.080 Section 301.1. Chapter 3, Condensate Disposal.
Section 310.1 is amended by replacing it to read:
Section 310.1 Condensate from air cooling coils and cQmfort cooling equipment not intended to
be used for the storage or holding of food or drinks shall be collected and discharged to a storm sewer or
other approved points of disposal acceptable to the Building Official.
Termination of such drains shall be made by an air break. Condensate drain lines in sizes 1 1/4" and
larger shall be assembled using approved drainage pipe and fittings. Condensate waste water shall not
drain over or upon a public v...ay. sidewalk. pedestrian ramp or the like. Condensate drains with
termination's within the interior of a building shall not be connected to the building roof drain or
overflow piping systems.
FINDING: This section amends the code to comply with local sanitation district requirements
regarding disposal for condensate for BY AC systems. The waste water treatment facilities serving
the City of Dublin is operating at or near maximum capacity. The discharge of treated waste
water into San Francisco Bay is detrimental to its sensitive ecosystem.
Cooling coil and comfort cooling equipment condensate waste discharge does not contain
pollutants which require treatment before being discharged into storm sewers or the ground.
SECTION 60
Section 7.48.030 of the Duhlin Municipal Code is amended to read:
.'
Section 7.48.030 Adoption.
Section 7.18.030 .^...doption.
The "Uniform Housing Code" .f.9.9..l-l22.1 Edition, published by the International Conference of
Building Officials, a copy of which is filed in the office of the City Clerk is adopted by reference as the
housing code for the city pursuant to the provisions of Section 50022.1 et. seq. of the Government Code
of the state of California except as hereinafter modified in Sections 7.48.050 through 7.48.140.
32
REASON: This Municipal Code section adopts the 1994 Edition of the Uniform Housing Code.
SECTION 61
."
Section 7.48.050 of the Dublin Municipal Code is amended to read:
Section 7.48.050 Chapter 1, Title and Scope - Deleted.
Chapter I on Page 91 is deleted.
REASON: This Municipal Code section and page has been reformatted.
SECTION 62
Section 7.48.060 of the Dublin Municipal Code is amended to read:
Section 7.48.060 Chapter 2, Enforcement - Deleted.
Chapter 2 on Pages -M 2 and -t+ 3. is deleted.
REASON: This Municipal Code section and page has been reformatted.
SECTION 63
Section 7.48.070 of the Dublin Municipal Code is amended to read:-
Section 7.48.070 Chapter 3, Permits and Inspections - Deleted.
Chapter 3 on Page -t+ 1 is deleted.
REASON: This Municipal Code section and page has been reformatted.
.:'"
SECTION 64
Section 7.48.080 oftlte Dublin Municipal Code is amended to read:
Section 7.48.080 Section 505 (h), (i), G), 505.8,505.9,505.10, Chapter 5, Sanitation- Added.
Section 505 on pages 16 and 17 page 8 is amended by adding new subsections (h), (i), and G)
505.8. 505.9, and 505.10 to read:
w ~ Garbage Receptacles. An adequate number of appropriate receptacles with close
fitting covers for garbage and rubbish as may be considered necessary by the enforcing agency shall be
provided for the occupant of every dwelling unit by the owner or operator of every apartment house,
hotel, or combination thereof. Each receptacle shall be kept in a clean condition and good repair.
fit ~ Bedding. In every apartment house or hotel every part of every bed, including the
mattress, sheets, blankets, and bedding shall be kept in a clean, dry and sanitary condition, free from
filth, urine, or other foul matter; and from infection of lice, bed-bugs, or other insects. The bed linen
shall be changed before a new guest occupies the dwelling unit.
ill 505.10 Caretaker. A manager, janitor, housekeeper, or other responsible person shall reside
upon the premises and shall have charge of every apartment house in which there are sixteen (16) or
33
.,'
.",
"
more apartments and of every hotel in which there are twelve (12) or more guest rooms, in the event that
the owner of any such apartment house or hotel does not reside upon said premises. If the owner does
not reside upon the premises of any apartment house in which there are more than four (4) but less than
sixteen (16) apartments, a notice stating his name and address, or name and address of his agent in
charge of the apartment house shall be posted in a conspicuous place on the premises.
REASON: This Municipal Code section and page has been reformatted.
SECTION 65
Section 7.48.090 of the Dublin Municipal Code is amended to read:
Section 7.48.090 Chapter 11, Notices and Orders of the Building Official- Deleted.
Chapter lIon Pages 25, 26, and 27 16. 17, and 18 is deleted.
REASON: This Municipal Code section and page has been reformatted.
SECTION 66
Section 7.48.100 of the Dublin Municipal Code is amended to read:
Section 7.48.100 Chapter 12, Appeal- Deleted.
Chapter 12 on Pages 28 and 29 Page 19 is deleted.
.' REASON: This Municipal Code section and page has been reformatted.
SECTION 67
Section 7.48.110 of the Dublin Municipal Code is amended to read:
Section 7.48.110 Chapter 13, Procedures for Conduct of Hearing Appeals - Deleted.
Chapter 13 on Pages 30, 31, 32 and 3320.21 and 22 is deleted.
REASON: This Municipal Code section and page has been reformatted.
SECTION 68
Section 7.48.120 of the Dublin Municipal Code is amended to read:
Section 7.48.120 Chapter 14, Enforcement of the Order of the Building Official or the
Board of Appeals - Deleted.
Chapter 14 on Pages 31 and 35 23 and 24 is deleted.
.'
REASON: This Municipal Code section and page has been reformatted.
34
SECTION 69
Section 7.48.130 of the Dublin Municipal Code is amended to read:
Section 7.48.130 Chapter 15, Performance of Work of Repair or Demolition - Deleted.
Chapter 15 on Page Je ~ is deleted.
REASON: This Municipal Code section and page has been reformatted.
e'
"
SECTION 70
Section 7.48.140 of the Dublin Municipal Code is amended to read:
Section 7.48.140 Chapter 16, Recovery of Cost of Repair or Demolition - Deleted.
Chapter 16 on Pages 37, 3g, and 39 26. 27. and 28 is deleted.
REASON: This Municipal Code section and page has been reformatted.
SECTION 71
The provisions of this ordinance shall take effect on January 1, 1996 pursuant to Government
Code section 36937 as an urgency ordinance. The urgency is based on the fact that the State published
and adopted the 1994 editions of the model codes on July 1, 1995. Local jurisdictions must then adopt..
these codes within 6 months, which is January 1, 1996. This City Clerk of the City of Dublin shall e',:",
cause this ordinance to be posted in at least three (3) public places in the City of Dublin in accordance
with Section 36933 of the Government Code of the State of California.
PASSED, AND ADOPTED BY the City Council of the City of Dublin, on this day of
1995, by the following votes:
AYES:
NOES:
ABSENT:
ABSTAIN:
Mayor
ATTEST:
City Clerk
e:
35
.
ORDINANCE No. - 95
AN ORDINANCE OF THE CITY OF DUBLIN AMENDING CHAPTERS 7.28, 7.32,
7.40, 7.44, and 7.48 OF THE DUBLIN MUNICIPAL CODE AND ADOPTING BY
REFERENCE THE 1994 UNIFORM BUILDING CODE, UNIFORM PLUMBING CODE,
UNIFORM MECHANICAL CODE, UNIFORM: HOUSING CODE AND THE
1993 NATIONAL ELECTRICAL CODE AND DECLARING TillS ORDINANCE
TO BE AN URGENCY ORDINANCE TO TAKE EFFECT JANUARY 1, 1996
The City Council of the City of Dublin does ordain as follows:
SECTION 1
Section 7.28.120 of the Dublin Municipal Code is amended to read:
Section 7.28.120 Existing Buildings, Structures, or Installations.
A. Except as required by Section 310.9.1 of the Building Code, and Sections 7.32.280 and
7.40.130, buildings or structures, electrical, plumbing or mechanical installations in existence at the time
of the adoption of this chapter may have their existing use or occupancy continued if such use or
occupancy was legal at the time of adoption of the ordinance codified in this chapter and provided such
continued use is not dangerous or substandard and does not menace health, life or property.
B. Electrical, plumbing and mechanical systems installed in apartments, hotels and dwelling and
in existence prior to January 1, 1975, shall be deemed to have conformed to applicable law in effect at
the time of installation and to have been maintained in good condition of currently in good and safe
.' condition and working properly.
.".
, ,
SECTION 2
Section 7.28.170 of the Dublin Municipal Code is amended to read:
Section 7.28.170 Appeals.
A. Any person aggrieved with any decision of the Building Official in connection with the
application or interpretation of the provisions of this chapter or in the approval of alternate materials or
methods of construction may appeal to the City Council. Such appeal shall be in writing and filed
within ten (10) days.
B. The City Council may after hearing, interpret any provision of this chapter.
C. The City Council may after hearing vary the application of this chapter in any specific case
when in its opinion the enforcement thereof would be contrary to the spirit and purpose of this chapter or
public interest. The City Council in granting a variance may impose requirements or conditions to
mitigate any adverse effects that may result from granting a variance.
D. In making any such interpretation or granting any variance the City Council shall make the
following findings: .
.'
1. That the interpretation or variance is consistent with the purpose of this chapter;
2. That the interpretation or variance will not lessen the protection to the people of the city and
the property situated therein. .
E. The City Council may approve alternate materials or methods of construction as set forth in
Section 7.28.140 by overruling the decision of the Building Official. In approval any alternate materials
1
Fv~~q~T ?
'..:Yt A,~, ;\i '- i1!'4 .. '-
or methods of construction the City Council shall make findings that the material, method or work
proposed is for the purpose intended, at least the equivalent of that prescribed by this chapter in quality,
strength, effectiveness, fire resistance, durability, dimensional stability and safety.
......,
, ,
F. The City Council may appoint a Board of Appeals to hear any specific appeal. The Board of
Appeals shall consist of five (5) members qualified by training and experience to pass on matters
pertaining to the subject matter of the appeal and to serve until the disposition of the appeal. The Board
of Appeals shall have the same autpority and duties as the City Council in interpreting this chapter,
granting variances, or appro"ing alte:nate materials or methods of construction. The Building Official
shall be an ex officio member of th~ Board of Appeals and shall act as secretary to the board. The board
of appeals shall adopt reasonable rules and regulations for conducting its hearings and investigations.
The decision of the Board of Appeals shall be final.
SECTION 3
Section 7.28.290, of the Dublin i'lfu11.icipal Code is amended to read:
Section 7.28.290 Except;ons.
A. No permit shall be required for the following; however, permits shall be required for
electrical, plumbing and mechanical installations in any building or structure listed in subsections Al
through A 18 of this section, and pennits shall be required for all new construction and substantial
improvements that are located within an area of special flood hazard in which case a permit shall be
required as set forth in Chapter 7.24:
1. Open wire fences not more than sixteen (16) feet in height, masonry fences not more than six
(6) in height, and all othe!' type fences not more than eight (8) feet in height;
2. Retaining walls which do not retain more than three (3) feet of earth when the earth retained is
level or where there is no surcharge load, and retaining walls which do not retain more than two
(2) feet of earth when the earth retained is sloping or which supports surcharge loads. See
Section 2317.11 of the Unifmm Building Code for requirements for treatment of wood used for
retaining walls;
.'
3. One-story detached accessory buildings used as tool and storage sheds, playhouses and
similar uses, provided the projected roof area does not exceed one hundred twenty (120) square
feet;
4. One-story buildings not r:lore than four hundred (400) square feet in area used exclusively for
housing animals, poultry, livestock and similar animals and the storage of necessary food, hay or
grain for the animals housed therein;
5. Agricultural buildings as defined in Section 202 of the Uniform Building Code on lots
exceeding twenty (20) acres in area which are located in an A zoning district and where the
principal use of the land is agriculture;
6. Lath houses and similar sun shade structure with roofs which do not shed water, which are not
more than ten (10) feet in height and one thousand (1,000) square feet in area;
7. Awnings ovei' doors c:nd windows of a Group R-3 or Group U-l Occupancy which are
entirely supported by the building and do not project more than fifty-four (54) inches;
8. Temporary construction offices, and storage sheds which are used on a site where there is a.":,
valid building permit, gradiag permit, or which are used in connection with a construction
project where no building p~rmit or grading permit is required; however, this provision shall not
apply to such building remaining on the site 30 days after the completion of construction;
2
.:~'.'
, ,
.'.
.
9. Temporary construction offices and storage sheds when stored in a contractor's equipment
yard; however, this provisions shall not apply if such buildings are used for any purpose
whatsoever;
10. Raised decks which are less than thirty (30) inches above the ground at any point;
11. Treehouses or other structures which are designed to be used by children for play;
12. Flag poles, radio or TV antennas and towers, less than thirty-five (35) feet in height when
not attached to a building and less than twenty (20) feet in height when attached to a building,
except permits are required for dish type antennas more than four (4) feet in diameter;
13. Swimming, bathing, and wading pools, and fish ponds not exceeding twenty-four (24)
inches in depth;
14. Prefabricated swimming pools, spas, or hot tubs not exceeding four (4) feet in depth if
resting on the surface of the ground or a concrete slab on the ground;
15. Painting, papering and similar finish work;
16. Moveable cases, counters, and partitions not over five (5) feet nine (9) inches high;
17. Water tanks supported directly upon grade if the capacity does not exceed five thousand
(5,000) gallons and the ratio of height to diameter or width does not exceed two to one;
18. Water storage tanks of any size if resting on the surface of the ground or on a concrete slab
on the ground when used only for watering livestock or irrigation;
19. The replacement of lamps or the connection of portable electrical appliances to suitable
receptacles which have been permanently installed;
20. Nonelectrical, signs less than eight (8) feet in height, nonelectrical signs which do not
exceed three (3) pO'..lnds per square foot nor four (4) inches in thickness when fastened flat
against the wall of any builGing and provided further that the sign does not extend above the top
of the wall of the building.
21. Clearing stoppages or repairing leaks in pipes, valves, fittings or fixtures when such repairs
do not involve the replacement or rearrangement of pipes, valves, fittings or fixtures;
22. Buildings and structures owned by a sanitary district used exclusively for storage, collection,
conveying and treating sewage;
23. A permit shall not be required for demolition or exploration work that may be necessary in
order to determine conditions in connection with a proposed addition or alteration to an existing
building if an application for a permit is on file and prior approval for the demolition or
exploration work is obtained from the Building Official;
24. A permit shall not be required for small or unimportant work when approved by the Building
Official; ,
B. Exemption from the requirement of a permit shall not be deemed to be permissible to
violate any provision of this Chapter or any other law, ordinance, rule or regulation.
C. Although permits are not required by this section, any person may obtain inspection
services by applying for a permit for such work and paying the applicable fee.
3
SECTION 4
Section 7.28.410 of the Dublin Municipal Code is amended to read:
Section 7.28.410 Building Official- Authority to Deny Permit.
The Building Official may refuse to issue any permit where it cannot be demonstrated that:
A. The hazards of land slippage, erosion or settlement will be eliminated;
2. The proposed work will not be located on a trace of an active fault;
3. The proposed work will conform to Chapters 7.20 and 7.24;
4. The placement of existing fills has not been subject to continuous inspection by a special
inspector as required by Section 1701.5.13 of the Uniform Building Code;
5. The private water supply will conform to Section 601.0 of the Uniform Plumbing
Code.
6. The private sewage disposal system required by Section 713.0 of the Plumbing Code will
conform to Section 7.40.140;
7. Whenever a licensed contractor has failed to make corrections as specified in Section
7.28.540 through 7.28.580.
.'"
SECTION 5
Section 7.28.590 of the Dublin Municipal Code is amended to read:
Section 7.28.590 Special Inspections.
A. In addition to the inspections required by sections 7.28.540 through 7.28.580, Special
Inspections shall be provided in accordance with Chapter 17 of the Uniform Building Code.
..".
, ,
SECTION 6
Section 7.32.030 of the Dublin Munidpal Code is amended to read:
Section 7.32.030 Adoption.
Certain documents, a copy of which is on file in the office of the City Clerk, being marked as "Uniform
Building Code," 1994 Edition, V clumes 1,2 and 3 including Appendix Chapters 3 Division II, 4
Division I, 12 Division II, 15, 18, 31 Division III and 33 published by the International Conference of
Building Officials is hereby adopted by reference as the building code of the city pursuant to the
provision of Section 50022.1 et seq. of the Government Code of the state of California except as
hereinafter modified in Section 7.32.110 through 7.32.420 this chapter.
SECTION 7
Section 7.32.110 of the Dublin Municipal Code is amended to read:
Section 7.32.110 Chapter 1, Administration - Deleted.
SECTION 8
.
Section 7.32.120 of the Dublin Municipal Code is amended to read.
Section 7.32.120 Section 3405, Chapter 34, Change in Use.
4
Section 3405 is amended by deletip-g the third paragraph.
.'
SECTION 9
Section 7.32.130 of the Dublin ldunicipal Code is amended to read:
Section 7.32.130 Section 504.6, Chapter 5, Area Separation Walls.
Section 504.6 is amended by adding a new item 504.6.7 to read:
504.6.7 Area separation walls shall not be considered to create separate buildings for the purpose of
automatic fIre-sprinkler system requirements as set forth in Chapter 9.:.
Exception: Buildings separated by continuous area separation walls of four-hour fire-resistive
construction without openings. Buildings required to have automatic fire-sprinkler protection as set
forth in Section 13113 of the Health and Safety Code are prohibited from using area separation walls in
lieu of automatic fire-sprinkler protection.
SECTION 10
Section 7.32.140 of the Dublin Municipal Code is amended to read:
Section 7.32.140 Section 505.4, Chapter 5, Yard Restriction.
A new subsection 505.4 is added to section
.',. 505.4 Yard Restriction. The increase in area permitted by Subsections 505.1 and 505.2 of this
Section shall not be ailowed unless or until the owner of the required yard shall file an agreement
binding such owner, his heirs, and assignees, to set aside the required yard as unobstructed space having
no improvements. Such agreement shall be recorded in the Alameda County Recorder's Office.
SECTION 11
Section 7.32.150 of the Dublin Mwlicipal Code is deleted.
SECTION 12
Section 7.32.155 of the Dublin Municipal Code is deleted.
SECTION 13
Section 7.32.160 of the Dublin MUilicipal Code is amended to read:
Section 7.32.160 Section 1617, Chapter 16, Part VI, Wind Design - Amended
Section 1617 is amended to read:
.
Section 1617 Exposure.
All portions of the City of Dublin have a basic wind speed of 70 miles per hour.
5
All portions shall be exposure "B" except that all portions of the City of Dublin east of the
easterly city boundar"'} as it existed on December 23, 1986 and all portions of the City of Dublin wesfof
the westerly city boundary as it existed on April 21, 1991 shall be exposure "C".
SECTION 14
.':'
Section 7.32.170 of the Dublin Municipal Code is amended to read:
Section 7.32.170 Table 16-A, Chapter 16, Part VI, Uniform and Concentrated Loads
Table 16-A is amended by adding a new footnote 10 to read:
10. Bridges for vehicular traffic shall be designed for H2O loading as designated by the
American Association of State Highway Officials.
SECTION 15
Section 7.32.180 of the Dublin Municipal Code is deleted.
SECTION 16
Section 7.32.190 of the Dublin Municipal Code is deleted.
SECTION 17
Section 7.32.200 of the Dublin Municipal Code is deleted.
.'
SECTION 18
Section 7.32.210 of the Dublin Municipal Code is deleted.
SECTION 19
Section 7.32.220 of the Dublin Municipal Code is deleted.
SECTION 20
Section 7.32.230 of the Dublin Municipal Code is amended to read:
Section 7.32.230 Section 1503.1, Chapter 15, Special Requirements.
Section 1503.1 is amended to read:
1503.1 Special Requirements.
1. Map of Fire Safe Roof Areas. Figure 15-1 * is a map of Fire Safe Roof areas. Said map may
be amended from time to time by induding areas which are annexed to the City within one of the two e" '.--,
roofing areas. Said amendments may be made by the Building Official after consultation, with the Chief
of the Dougherty Regional Fire Aut.hority.
6
(
.
~
( .
.
ROOF AREA 1
r------: .'. .
, ............'
. . ~
I .
(.
. I
~--~,
CoU",'ff ..~ ,,/ ~
~\.~tJ.tO, "
/
",/tI" ....
/
/'
(/
\
)
I
I
"
/
I
"
I
"
I
/
I
I
I
I
/
I
i r------'\ .-----....:-~.
, J - \
( r--------f--- .---------------....-- )\
! us, OEPT. ...
: OF JUSTICE 5
L_____________j ""~, ~ ''^"'~ h
I ____u.!~"..,._ ~
tAMP PARKS ROOF ArEA 1 k -j.~,~. -~
MIUTARY RESERVATION /-
I ~ I'
I ! .:
I
COS1 ~
cPlI'Il'1'
\.itJ.1't
~... '" 01~
_________ ~e>J
"l~ .
\ \
.~
CAIoIP PARKS
MILITARY RESERVATION
~
"~
'~
~'
l
,- :~.:: .:~
U.S. NAT. AE RON AUTI CS
(SPACE ADM.
- . -'
......:..;...
" .;.:.=..:-'
~.. '.7::~~~:; :":::-::'.::::":..."
',"'" ,,:::"!.. 7.:,:, "_""" ."...
;.'"
_L
...:,...
FIGURE 15-1
EAST BAY
REGONAL PARK
,;
a:
. Animal
Control
Sholl or
~
,.!.
'; .
,
I li
I
I 8
I "
I ."
I i
I . . L I
I '
":~,,,,L;0~"'~~~~~~'~~~;;;~~~;;''''=:''''''~,=,"=,,,,,=_,,~,,,,~~
{!
Dublrn Blvd.
r--
I
,
.'
2. Roofing Area 1. Any new roof and any alteration, repair or replacement for buildings
housing R & U-l occupancies in Roofing Area 1 shall use roof covering material that conforms to Class
B or better when tested in accordance with UBC Standard 15-2, or shall be made of concrete, ferrous or
copper metal, clay, slate or similar non-combustible material.
3. Roofing Area 2. Any new roof for buildings using roof covering material that conforms to
Class C or better when tested in acccrdance with UBC Standard 15-2, or shall he made of concrete,
ferrous or copper metal, clay, slate or similar non-combustible material.
4. Other Occupancies. Any new roof covering and any alterations, repairs or replacement of
roof covering material for buildings housing all other occupancies shall conform to the requirements as
set forth in Roofing Area I.
SECTION 21
Section 7.32.250 of the Dublin MUllic(val Code is deleted.
SECTION 22
,Section 7.32.260 of the Dublin Municipal Code is amended to read:
Section 7.32.260 Section 904.2, Chapter 9, Part VI, Automatic fire-extinguishing systems.
Section 904.2... is amended to read:
.'
904.2. Automatic Fire-Extinguishing Systems.
904.2.1 Where Required. An automatic fire-extinguishing system shall be installed in the
occupancies and locations as set forth in this section. For provisions on special hazardous materials see
the Fire Code. .
904.2.2 All Occupancies Except Group R, Division 3 and Group U Occupancies. Except for
Group R, Division 3 and Group U O.:cupancies, an automatic sprinkler system shall be installed:
1. In every story or basement of all buildings when the floor area exceeds 1,500 square feet
(139.4m2) and there is not provided at least 20 square feet (I.86m2) of opening entirely above the
adjoining ground level in each 50 lineal (15 240m) or fraction thereof of exterior wall in the story or
basement on at least one side of the building. Openings shall have a minimum dimension of not less
than 30 inches (762mm). Such openings shall be accessible to the fire department from the exterior and
shall not be obstructed in a manner that firefighting or rescue cannot be accomplished from the exterior.
When openings in a story are prcvided on only one side and the opposite wall of such story is
more than 75 feet (22 860m!:1) from such openings, the story shall be provided with an approved
automatic sprinkler system, or openings as specified above shall be provided on at least two sides of an
exterior wall of the stcry. .
If any portion of a basement is located more than 75 feet (22 860mm) from openings required in
this section, the basement shall be pr 0vided with an approved automatic 'sprinkler system.
2. At the top of rubbish and linen chutes and in their terminal rooms. Chutes extending through
.'.. thr~e or more floors shall have .additional spt1nkler heads installed within such chutes at alternate floors.
" Spnnkler heads shall be acceSSIble fer servIcmg.
3. In rooms where nitrate fihn is stored or handled.
7
4. In protected combustible fiber storage vaults as defined in the Fire Code.
5. Throughout all buildings with a floor level with an occupant load of30 or more that is located .....
55 feet (16 764mm) or more above the lowest level of fire department vehicle access.
EXCEPTION: 1. Airport control towers.
2. Open parking structures.
3. Group F, Division 2 Occupancies.
904.2.3 Group A Occupancies. An automatic fire extinguishing system shall be installed in all
Group A Occupancies (except of Type V construction) where the floor area exceeds 5,000 square feet
and in all basements classified Group A Occupancy when the basement floor area exceeds 1,500 square
feet. Group A occupancies that are of Type V construction where the floor area exceeds 3,000 square
feet.
904.2.3.1 Drinking establishments. An automatic sprinkler system shall be installed in rooms
used by the occupants for the consumption of alcoholic beverages and unseparated accessory uses where
the total area of such unseparated rooms and assembly uses exceeds 5,000 square feet (465 m2) (except
of Type V construction). For uses to be considered as separated, the separation shall not be less than as
required for a one-hour occupancy separation. The area of other uses shall be included unless separated
by at least a one-hour occupancy separation. Drinkin~ establishments that are of Type V construction
where the floor area exceeds 3,000 square feet (279 m )
904.2.3.2 Basements. An automatic sprinkler system shall be installed in basements classified as
a Group A Occupancy when the basement is larger than 1,500 square feet (139 m2) in floor area.
904.2.3.3 Exhibition and display rooms. An automatic sprinkler system shall be installed in
Group A Occupancies which have more than 12,000 square feet (112 m2) of floor area which can be
used for exhibition or display purposes.
904.2.3.4 Stairs. An automatic sprinkler system shall be installed in enclosed usable space below
or over a stairway in Group A, Divisions 2, 2.1,3 and 4 Occupancies. See Section 1009.6.
904.2.3.5 Multitheater complexes. An automatic sprinkler system shall be installed in every
building containing a multi theater complex.
.:-
904.2.3.6 Amusement buildings. An automatic sprinkler system shall be installed in all
amusement buildings. The main water-flow switch shall be electrically supervised. The sprinkler main
cutoff valve shall be supervised. When the amusement building is temporary, the sprinkler water-supply
system may be of an approved temporary type.
EXCEPTION: An automatic sprinkler system need not be provided when the floor area
of a temporary amusement building is less than 1,000 square feet (92.9 m2) and the exit travel
distance from any point is less than 50 feet (15240 mm).
904.2.3.7 Stages. All stages shall be sprinklered. Such sprinklers shall be provided throughout
the stage and in dressing rooms, workshops, storerooms and other accessory spaces contiguous to such
stages.
EXCEPTIONS: 1. Sprinklers are not required for stages'l,OOO square feet (92.9 m2) or
less in area and 50 feet (1542 mm) or less in height where curtains, scenery or other combustible
hangings are not retractable vertically. Combustible hangings shall be limited to a single main curtain,
borders, legs and a single backdrop.
2. Under stage areas less than 4 feet (1219 mm) in clear height used exclusively for chair
or table storage and lined on the inside with 5/8-inch (16mm) Type X gypsum wallboard or an approved
equal.
."
8
.
904.2.3.8 Group B Occupancies.
An automatic fire-extinguishing system shall be installed in Group B occupancies (except Type
V construction) where the floor area exceeds 5,000 square feet (465 m2). An automatic sprinkler system
shall be installed in Group B, of Type V construction where the floor area exceeds 3,000 square feet
(279 m2).
904.2.4.1 Group E Occupancies. An automatic fIre-extinguishing shall be installed in all
Group E occupancies (except Type V construction) where the floor area exceeds 5,000 square feet.. An
automatic sprinkler system shall be installed in all Group E Occupancies of Type V construction where
the floor area exceeds 3,000 square feet.
904.2.4 Group E Occupancies.
904.2.4.1 General. An automatic fire sprinkle system shall be installed throughout all buildings
containing a Group E, Division 1 Occupancy.
EXCEPTION: 1. When each room used for instruction has at least one exit door directly to the
exterior at ground level and when rooms used for assembly purposes have at least one half of the
required exits directly to the exterior ground level, a sprinkler system need not be provided.
.
2. When area separation walls, or occupancy separations having a fire-resistive rating of not less
than two hours subdivide the building into separate compartments such that each compartment
contains an aggregate floor area not greater than 20,000 square feet (1858 m2), an automatic
sprinkler system need not be provided.
An automatic fire-extinguishing system shall be in Group E, Division 2 and 3 occupancies
(except Type V construction) where the floor area exceeds 5,000 square feet (465 m2). An automatic
sprinkler system shall be installed in Group E, Division 2 and 3 of Type V construction where the floor
area exceeds 3,000 square feet (279 m2).
904.2.4.2 Basements. An automatic sprinkler system shall be installed in basements classified as
Group E, Division I Occupancies.
904.2.4.3 Stairs. An automatic fire sprinkler system shall be installed in enclosed usable space
below or over a stairway in Group E, Division 1 Occupancies. See Section 1009.6.
904.2.4.4 Group F Occupancies. An automatic fire sprinkler system shall be installed in all
G~oup F occupancies (except Type V construction) where the floor area exceeds 5,000 square feet (465
m ) an automatic sprinkler system shall be installed in all Group F occupancies of Type V construction
where the floor area exceeds 3,000 square feet (279 m2). '
904.2.5 Group H Occupancies.
904.2.5.1 General. An automatic fire-extinguishing system shall be installed in Group H,
Divisions 1, 2, 3 and 7 Occupancies.
904.2.5.2 Group H, Division 4 Occupancies. An automatic fire-extinguishing system shall be
in~talled in Group H, Division 4 Occupancies having a floor area of more than 3,000 square feet (219
m). '
904.2.5.3 Group H, Division 6 Occupancies. An automatic fire-extinguishing system shall be
.'. installed throughout buildings containing Group H, Division 6 occupancies. The design of the sprinkler
.,' system shall be not less than the required under U.B.C. Standard No. 9-1 for the occupancy hazard
classifications as follows:
9
Location
Occupancy Hazard Classification
Fabrication areas
Service corridors
Storage rooms without dispensing
Storage rooms with dispensing
Exit corridors
Ordinary Hazard Group 2
Ordinary Hazard Group 2
Ordinary Hazard Group 2
Extra Hazard Group 2
Ordinary Hazard Group 21
.
Note: 1 When the design area of the sprinkler system consists of a corridor protected by one row of
sprinklers, the maximum number of sprinklers that need to calculated is 13.
904.2.6 Group I Occupancies. An automatic sprinkler system shall be installed in Group I
Occupancies.
EXCEPTION: In jails, prisons, and reformatories, the piping system may be dry, provided a
manually operated valve is installed in a continuously monitored location. Opening of the valve
'will cause the piping system to be charged. Sprinkler heads in such systems shall be equipped
with fusible elements or the system shall be designed as required for deluge systems in U.BC.
Standard No. 9-1.
904.2.7 Group M, and S Occupancies. An automatic sprinkler system shall be installed in
Group M and S occupa.lcies where the floor area exceeds 5,000 square feet (except Type.V
construction). An automatic fire sprinkler system shall be installed in all retail sales rooms classed A
Group M and S occupancies of Type V construction where the floor area exceeds 3,000 square feet.
904.2.8 Group R, Division I Occupancies. An automatic sprinkler system shall be installed
throughout every apartment house three or more stories in height or containing 16 or more dwelling
units in congregate residences three or more stories in height and having an occupant load of 50 or more .":':,,' I
and in hotels three or more stories in height or containing 20 or more guest rooms. Residential or quick
response standard sprinkler heads shall be used in the dwelling unit and guest room portions of the
building.
904.2.8.1 Group R, Division I and 3 Occupancies. An automatic frre-extinguishing system
shall be installed where the total area exceeds 5,000 square feet (465m2).
SECTION 23
Section 7.32.260 of the Dublin Municipal Code is amended to read:
904.2.9 All Group A, B, E, H, I, & R-1 & R-3 Occupancies. Automatic fire-extinguishing
systems shall be installed in all Groups A, B, E, H, I, & R -1 & R - 3 occupancies located more than 1 'is
miles from a fire station providing fire protection to that location. Said distance shall be measured in a
straight line. For R-3 occupancies the sprinkler system may be a residential sprinkler system. type
NFPA 13.
Buildings con~aining portions which are required to have an automatic frre extinguishing system
because of the number of stories shall have the automatic fire extinguishing system installed throughout
and area separation as set forth in Section 504.6 shall not be considered as creating separate buildings for
the purpose of this section. '
When the specific use of a building is not known at the time of design and installation of the automatic
fire-extinguishing system the design shall be based upon Ordinary Hazard Group 2 as set forth in UBC
Standard 9-1. '
.'
.,
Whenever an addition is made to an existing building automatic fire-extinguishing systems shall be
installed if the existing building plus the addition exceeds the area or height limitation set forth in this
10
.':
section. Whenever the use of an existing building or portion thereof is changed in any manner so as to
require the installation of an automatic fire-extinguishing system, said system shall be installed in that
portion of the building housing the new use.
SECTION 24
Section 7.32.270 of the Dublin Municipal Code is deleted.
SECTION 25
Section 7.32.270 ofi'he Dublin Municipal Code is added to read:
Section 7.32.270 Section 1806, Chapter 18, Footings.
Section 1806 is amended by adding the following at the end of the first paragraph:
A minimum of one top and or.e bottom continuous bars of 1/2" diameter reinforcing steel shall
be requir~d in all conti~uous concrete or masonry bearing foundations of Group R residential
occupanCIes.
SECTION 26
Section 7.32.271 of the Dublin Municipal Code is added to read:
.
Section 7.32.171 Section 1924, Chapter 19, Minimum Slab Thickness.
Section 1924 is amended as follows:
(a) General. The minimum thickness of concrete floor slabs supported directly on the ground
shall be not less than 3-1/2". The slab shall be reinforced with not less than six inches by six inches ten-
gauge wire mesh or ar. approved alternate installed at mid height of the slab. -
SECTION 27
Section 7.32.272 of the Dublin Municipal Code is added to read:
Section 7.32.272 Section 2326.11.3, Chapter 23, Item 5 Deleted - Bracing.
Section 2326.11.3, Item 5 is deleted.
SECTION 28
Section 7.32.273 of the DuiJ;;n Municipal Code is added to read:
Section 7.32.273 Section 2326.11.3, Chapter 23, Item 7, Amended Bracing.
Section 2326.11.3 Item 7 is amended as follows:
. Portland cement plaster on studs spaced 16 inches on center installed in accordance with Table
No. 47-1. Limited to single story R-3 and U-1 occupancies.
11
SECTION 29
Section 7.32.274 oftlte Dublin Municipal Code is added to read:
Section 7.32.274 Section 3403.2, Chapter 34, Suspended Ceilings.
Section 3403.2 is amended by adding the following paragraph at the end of the Section following
exceptions.
.--"
When a permit is issued for alterations or repairs, the existing suspended ceiling system within
the area of alteration or repair shall comply with the lateral design requirements ofUBC Standard 25-2
Part III.
SECTION 3tl
Section 7.32.280 of Hie Dublin Municipal Code is amended to read:
Section 7.32.280 Section 1C23, Appendix Chapter 10, Building Security.
Appendix 10 is arnended to read:
Section 1023 Residential Security Requirements.
(a) Exterior doc:-s. All exterior wood doors shall be of solid wood construction, no less than 1-
3/4 inches thick or hollow metal doors. Except for sliding glass doors, exterior doors hall not have
glazing larger than 2" unless glazing is 1/4" tempered glass.
(b) Locking devices. Exterior swinging doors shall have a lock on the latching device and an
auxiliary cylinder dead bolt. The dead bolt shall be hardened steel and have a I" throw. If the cylinder
of the lock protrudes from the face of the door it shall be fitted with a cylinder ring guard so it cannot be
gripped with pliers or other wrenching devices. Double doors shall have the inactive leaf secured with
flush bolts at top and bottom. The belts shall be hardened steel 1/4" minimum in diameter and shall
engage a metal strike plate to a minimum depth of 3/8".
(c) Strike plates. Strike plates for wood jambs shall be the high security type and shall be
secured with a minimum oftwo wood screws 3" long which shall engage the door studs.
.~_.,
, ,
(d) Jambs. Ins'winging doors with wood jambs shall have rabittedjambs. The jambs on the
strike side shall have continuous solid shims above and below the strike plates and the opposite jamb
shall have solid shims at the level of the strike plate. Both door studs shall be reinforced with horizontal
solid blocking at the approximate height of strike.
(e) Hinges. Exterior hinges and hinges of outswinging doors from the garage to the dwelling
shall have non-removable pins.
(f) Sliding glass doors. Sliding glass doors shall comply with Chapter 24. Sliding glass doors
shall be fitted with a iocking device that shall engage the strike sufficiently to prevent its being
disengaged by any possible movement of the door within the space or clearances provided for
installation and operation. The bolt and strike shall be reinforced by hardened material so as to prevent
their separation by pulling, prying or similar attack. An auxiliary locking device shall be installed on the
door which may be a pin, lock, or similar device of not less than 1/4 inch diameter. The pin shall be of a
hardened material and engage the metal portion of the sliding door. Doors with two sliding panels shall .'.',,,,
be locked at the meeting rails and shall have an auxiliary locking device as described above.
(g) Entry vision. All main or fTont entry doors shall be fitted with a viewing device having a
field of view of not less than 180 degrees.
12
e
e'
(h) Windows. All accessible dwelling windows shall be secure as follows:
I. Sliding glass windcws shall be secured on the inside with a locking device capable of
withstanding prying Oi" wrenching. An auxiliary lock shall be installed on each sliding
window that prevents movement in the sliding track.
2. Louvered windows shall not be used within eight feet of ground level, adjacent
structures, or fire escapes.
3. Casement type windows shall be secured with a metal to metal locking device
contacting both frames of the window at the meeting edge. Auxiliary locks such as a pin
that penetrates both frame structures shall be installed on casement and double hung
windows.
4. Windows fitted with a crank type gear opening device shall be fitted with a positive
window lock that engages metal to metal.
Windows shall not be located within 40 inches of the locking device of any door unless
protected by a steel grill with 1/4" minimum diameter bars not more than 2" on center or
by a screen with 1/8" diameter wire mesh more than 2" on center mounted on the inside
or glazed with 1/4" tempered glass.
(i) Garage doors. Vehicle garage doors shall be secured with a metal to metal locking device
that prevents the door from being pulied or pried up from the outside. No electric garage door openers
shall be permitted that will automatically activate when the door is forced 'open. Garage doors fitted
with automatic openers shall be permitted with an alternative form oflocking device activated from the
interior of the garage. Other garage doors shall comply with all of the provisions of this section.
CD Storage areas. Any exterior storage area attached to a dwelling, apartment or condominium
and enclosed by a door shall comply v/ith this section or have a minimum 3/8" diameter hardened
padlock hasp.
Section 1024 Non Residential Security Requirements
(a) Doors. Exterior doors which are located at the rear or side or away from the primary
entrance shall be solid doors with no glazing and shall be installed in metal frames. Exterior wood doors
shall be solid wood construction 1-3/4 inches thick or hollow metal doors.
(b) Locking device. Exterior swinging doors which are exit doors as set forth in Chapter 10
shall have cylinder dead-bolt locks which shall be openable without he use of key, special effort, or
knowledge. In Group B occupancies, a double cylinder dead-bolt lock may be used on the main exit
door if there is a readily visible, durable sign on, or adjacent, to the door stating, "this door to remain
unlocked during business hours." The sign shall be in letters not less than I inch high on contrasting
background. When unlocked the single door and both leaves of a pair of doors shall be free to swing
without operation of any latching deVIce. Doors which are not exit doors shall have a double-keyed
cylinder dead-bolt. Double doors that are not exit doors shall have the inactive leaf secured with flush-
bolts at the top and bottoms. The bolts shall be hardened steel 1/4" minimum diameter and shall engage
a metal strike plate to, a minimum depth of 3/8 inch.
The dead bolts shall be hardened steel and shall have a minimum of 1 'is inch throw. If the cylinder of
the lock protrudes from the face of the door it shall be fitted with cylinder ring geared so that it cannot
be griped with pliers or othe~ wrenching devices.
Vehicle doors, overhead doors, and sliding doors shall be secured with metal to metal locking devices
which prevent the door from opening.
e'. (c) Strike pJ~tes. Strike plates for wood jambs shall be the high security type and shall be
secured with a minimum of two wood screws 3" long which shall engage the door studs.
13
(d) Jambs. Inswinging doors with wood jambs shall have rabittedjambs. The jambs on the
strike side shall have continuous solid shims above and below the strike plates and the opposite jamb
shall have solid shims at the level of the strike plate. Both door studs shall be reinforced with horizontal e"', '
solid blocking at the approximate height of strike.
(e) Hinges. Exterior doors shall have non-removable hinge pins.
(t) Sliding glass doors. Sliding glass doors shall comply with Chapter 24. Sliding glass doors
shall be fitted with a locking device that shall engage the strike sufficiently to prevent its being
disengaged by any possible movement of the door within the space or clearances provided for
installation and operation. The bolt and strike shall be reinforced by hardened material so as to prevent
their separation by pulling, prying or similar attack. An auxiliary locking device shall be installed on the
door which may be a pin, lock, or similar device of not less than 1/4 inch diameter. The pin shall be of
hardened material and engage the metal portion of the sliding door. The primary locking device shall be
operable by a keyed or code lock inside. Doors with two sliding panels shall be locked at the meeting
rails and shall have an auxiliary locking device as prescribed above.
(g) Windows. All accessible windows which are not located at the front or main entrance side
of a non-residential building shall be made secure as follows:
1. Sliding glass windows shall be secured on the inside with a locking device capable of
withstanding prying or wrenching. An auxiliary lock shall be installed on each sliding
window that prevents movement in the sliding track.
2. Louvered windows shall not be used within eight feet of grmmd level, adjacent
structures, or fire escapes.
3. Casement type windows shall be secured with a metal to metal locking device
contacting both frames of the window at the meeting edge. Auxiliary locks such as a pin
that penetrates both frame structure shall be installed on casement and double hung e'.. "
windows.
4. Windows shall not be located within 40" of the locking device of any door not located
on the main entrance side of the non-residential building unless the windows are glazed
with 1/4" tempered glass.
(h) Openable transoms. All exterior openable transoms exceeding 8" x 12" which are not
located on the front or main entrance side of a non-residential building shall be protected with a steel
grill with 1/4" minimum bars not more than 2" on center or by a screen with 1/8" diameter wire mesh
not more than 2" on center mounted on the inside.
(i) Roof openings. All skylights on the roof of a non-residential building shall be protected by:
1. Iron bars 1/2" minimum diameter not more than 8" on center or;
2. A screen with 1/8" diameter wire mesh not more than 2" on center. All roof access
hatches of a non-residential building shall be protected as follows:
(I). If the hatchway is of wooden material, it shall be covered on the inside with at
least 16 gauge steel or its equivalent attached with screws at 6";
(2). The hatchway shall be secured from the inside with a slide bar or slide bolts;
(3). Outside hinges on all hatchway openings shall be provided with non
removable pins when using pine-type hinges.
All air duct or air vent openings exceeding 8" x 12" on the roof or exterior walls of any
building or premise used for business purposes shall be secured by covering the same
with either of the following:
1. Iron bars of at least 1/2" round or 1" x 1/4" flat steel material, spaced no more than 8"
apart and securely fastened. .
G) Exterior ladders. Exterior ladders to the roof are not permitted.
14
SECTION 31
___ S:!ction 7.32.290 Dublin Municipal Code is deleted.
e'
..
SECTION 32
Section 7.32.300 of the Dublin Municipal Code is amended to read:
Section 7.32.300 Section 3333, Chapter 33, Protection of Pedestrians During Construction
or Demolition..
Section 3303.1 is amended to read:
Section 3303.1 General. No person shall place or store any material or equipment necessary for
the work authorized by any building permit on any street or alley or public sidewalk unless an
encroachment permit is provided by Chapter 7.04, Dublin Municipal Code, has been secured. No person
shall perform any work on any building or structure if by so doing it endangers pedestrians on the street
that abuts the property, unless the protection of pedestrians as specified in this code is provided. No
encroachment permit shall be required for the construction of any railing, fence, or canopy used for the
protection of pedestrians if there is a valid building permit in effect for such work and the railing, fence
or canopy does not extend beyond the curb or gutter if there is no curb.
SECTION 33
Section 7.32.310 of the Duclin Munidpal Code is amended to read:
Section 7.32.310 Section 3333.2, Chapter 33, Temporary Use of Streets and Alleys.
Section 3303.2 is deleted.
SECTION 34
Section 7.32.320 of the Dublin Municipal Code is amended to read:
Section 7.32.32 Section 3303.3, Chapter 33, Storage on Public Property.
Section 3303.3 is deleted.
SECTION 35
Section 7.32.330 of the Dublin Municipal Code is amended to read:
Section 7.32.330 Section 3303.4, Chapter 33, Mixing Mortar on Public Property.
Section 3303.4 is deleted.
SECTION 36
e Section 7.32.340 of the Dublin Municipal Code is amended to read:
Section 7.32.340 Section 33&3.5, Chapter 33, Protection of Utilities.
15
Section 3303.5 is deleted.
SECTION 37
.'
Section 7.32.350 of the Dublin Municipal Code is amended to read:
Section 7.32.350 Section 3201, Chapter 32, General.
Section 3201 is amended to read:
Section 3201. No part of any structure or any appendage thereto shall project beyond the
property line of the building site except as specified in this chapter. Structures or appendages regulated
by this code shall be constructed of materials as specified in Section 705. The projection of any
structure or appendage shall be the distance measured horizontally from the property line to the
outermost point of the projection. No provision of this chapter shall be construed to permit the violation
of other laws or ordinances regulating the use and occupancy of public property.
SECTION 38
Section 7.32.360 of the Dublin Municipal Code is deleted.
Section 7.32.360 Section 3202, Chapter 32, Projection into Alleys.
Section 3202 is deleted.
SECTION 39
."
Section 7.32.370 of the Dublin Municipal Code is amended to read:
Section 7.32.370 Section 3203, Chapter 32, Space Below Sidewalks.
Section 3203 is deleted.
SECTION 40
Section 7.32.380 of the Dublin Municipal Code is amended to read:
Section 7.32.380 Section 3208, Chapter 32, Signs.
A new Section 3208 is added to read:
Section 3208 Signs. Signs when placed flat against the wall of a building shall not project
beyond the front property line not more than 12 inches.
SECTION 41
Section 7.32.390 of the Dublin Municipal Code is amended to read:
Section 7.32.390 Section 2506.4, Chapter 25, Weather-resistive Barriers.
Section 2506.4 is amended to read:
.'
16
.
.'..
.
Section 2506.4. Notwithstanding the provisions of 1402.1 the weather-resistive barrier for
exterior stucco shall be either Type 15 felt or Grade D craft building paper having a 60-minute water-
resistance when tested in accordance with UBC Standard 14-1. Two layers of the weather-resistive
barrier shall be applied over wood sheathing.
SECTION 42
Section 7.32.400 of the Dublin Municipal Code is deleted.
SECTION 43
Section 7.32.420 of the Dublin Municipal Code is deleted.
SECTION 44
Section 7.36.030 of the Dublin Munic~?al Code is amended to read:
Section 7.36.030 Adoption.
The "National Electrical Code 1993," published by the National Fire Protection Association, a
copy of which is filed in the office of ~he City Clerk, is adopted by reference as the electrical code for
the city pursuant to th~ provisions of Section 50022.1 et seq. of the Government Code of the state of
California, except as hereinafter modified in Sections 7.36.070 and 7.36.080 of this chapter.
SECTION 45
Section 7.36.090 of the Dublin Municipal Code is added to read:
Section 7.36.090, Article 336-4 is amended by replacing it with the following:
(a) Type NM or NMC. Types NM and NMC cables shall not be used (1) in any dwelling or
structure exceeding three floors above grade; (2) as service-entrance cable; (3) embedded in poured
concrete; or (4) in any non-residential occupancy. For the purpose of this article, the first floor of a
building shall be that floor that has 50 percent or more of the exterior wall surface area level with or
above finished grade, One additional level that is the first level and not designed for human habitation
and used only for vehicle parking, storage, or similar use shall be permitted.
SECTION 46
Section 7.40.030 of the Dublin Municipal Code is amended to read:
Section 7.4(L030 Adoption.
The "Uniform Plumbing Code" 1994 Edition, published by the International Association of
Plumbing and Mechanical Officials, including Appendix Chapters A, B;D, E, H, and I, and all
installation standards, a copv of which is filed in the office of the City Clerk is adopted by reference as
the plumbing code for the Cl~Y pursuant to the provision of Section 50022.1 et seq. of the Government
Code of the state cfCalifornia except as hereinafter modified in Section 7.40.075 through 7.40.150 of
this chapter.
17
SECTION 47
Section 7.40.075 o/tlte Dublin Municipal Code is amended to read:
Section 7.40.075 Section 311, Chapter 3 Prohibited Fittings and Practices.
Section 311 is amended by adding a new subsection 311.9 to read:
311.9 Plastic piping shall not be exposed as a portion of the interior room finish in a building or
structure if the piping has flame-spread rating exceeding 75 when tested in accordance with ASTM E
84-77a Test for Surface Burning Characteristics of Building Materials.
.
SECTION 48
Section 7.40.090 o/tlte Dublin Municipal Code is amended to read:
Section 7.40.090 Section 401, Chapter 4, Materials.
Section 401 is amended by adding a new subsection 401.3 to read:
401.3. Drainage piping shall be cast iron, galvanized steel, galvanized wrought iron, lead,
copper, brass, Schedule 40 ABS DWV, Schedule 40 PVC DWV, extra-strength vitrified clay pipe, or
other approved materials having a smooth and uniform bore, except that:
(1) No galvanized wrought iron or galvanized steel pipe shall be used under ground and shall be
kept at least six (6) inches (152.4 mm) above ground.
(2) ABS and PVC DWV piping installations shall be limited to structures not exceeding three .::
floors above grade. For the purpose of this subsection, the first floor of a building shall be that floor that
has fifty (50) percent or more of the exterior wall surface area level with or above finished grade. One
additional level that is the first level and not designed for human habitation and used only for vehicle
parking, storage, or similar use shall be permitted.
(2.1) ABS and PVC installations are limited to residential construction not more than two (2)
stories in height and to relocatable public school buildings.
(3) No vitrified clay pipe or fittings shall be used above ground or when pressurized by a pump
or ejector. They shall be kept at least twelve (12) inches (304.8mm) below ground.
SECTION 49
Section 7.40.100 o/tlte Dublin Municipal Code is amended to read:
Section 7.40.100 Section 503.0, Chapter 5, Materials.
Section 503 is amended by adding a new subsection 503.1 to read:
501.1 Materials. Vent pipe shall be cast iron, galvanized steel, galvanized wrought iron, lead,
copper, brass, Schedule 40 ABS DWV, Schedule 40 PVC DWV, or other approved materials having a
smooth and uniform bore, except that:
(1) No galvanized wrought iron or galvanized steel pipe shall be used under-ground and shall be .' , ,':
kept at least six (6) inches above ground.
18
..
(2) ABS and PVC DWV piping installatio!ls shall be limited to structures not exceeding three
floors above grade. For the purpose of this subsection, the first floor of a building shall be that floor that
has fifty percent or more of the exterior wall surface area level with or above finished grade. One
additional level that is the first level and not designed for human habitation and used only for vehicle
parking, storage, or similar use shall be permitted.
(2.1) ABS and PVC installations are limited to residential construction not more than two (2)
stories in height.
(b) Vent fittings shall be cast iron, galvanized malleable iron or galvanized steel, lead,
copper, brass, ABS, PVC, or other approved materials, except that no galvanized malleable iron
or galvanized steel fitting shall be used underground and shall be kept at least six (6) inches
(152.4mm) above ground.
(c) Changes in direction of vent piping shall be made by the appropriate use of approved
fittings and no such pipe shall be strained or bent. Burred ends shall be reamed to the full bore of
the pipe.
SECTION 50
Section 7.40.105 of the Dublin Municipal Code is added to read:
Section 7.40.105 Sectioli 609.3, Chapter 6, Water Piping in Slab Floors.
.
Section 609.3, First paragraph, is amended by replacing it to read:
Section 609.3 Water piping shall not be installed in or under a concrete floor slab within a
heilding without prior approval of the Building Official. When approved, such piping shall be installed
in accordance with the folIo v;,ing requirements:
SECTION 51
Section 7.40.110 of the Dublin Muriidpal Code is added to read:
Section 7.40.110 Section 7141.1, Chapter 7, Backwater Valves.
Section 710.1 is amended to read:
Section 710.1 Drainage piping serving fixtures which have flood level rims less than twelve (12)
inches (304.8mm) above the elevati.:m of the next upstream manhole and/or flushing inlet cover at the
public or private sewer system serving such drainage piping shall be protected from backflow of sewage
by installing an approved type backwater valve. Fixtures above such elevation shall not discharge
through the backwater valve, unless fi~st approved by the Building Official.
SECTION 52
Section 7.40.115 of the Dublin Municipal Code is added to read:
Section 7.40.115 Sedioc 719.7, Chapter 7, Cleanouts.
.' Section 719.7 is amended by adding subsection 7 to read:
Section 719.7 Cleanouts shall be installed at the property line where the private sewer system
connects to the publicly-maintained sanitary sewer lateral. All such line cleanouts shall be extended to
19
grade with materials and according to specifications approved by the Building Official and terminate.
within a concrete box. .
SECTION 53
.~
Section 7.40.120 of the Dublin Municipal Code is amended to read:
Section 7.40.120 Section 807.2, Chapter 8, Condensate Disposal.
Section 807.2 is amended by replacing it to read:
Section 807.2 Condensate from air-cooling coils and comfort cooling equipment not intended to
be used for the storage or holding of food or drinks shall be collected and discharged to a storm sewer or
other approved points of disposal acceptable to the Building Official.
Termination of such drains shall be made by an air break. Condensate drain lines in sizes 11/4" and
larger shall be assembled using approved drainage pipe and fittings. Condensate waste water shall not
drain over or upon a public way, sidewalk, pedestrian ramp or the like. Condensate drains within the
interior of a building shall not be connected to the building roof drain or overflow piping systems. The
waste pipe shall have a slope of not less than 1/8 inch per foot and shall be of approved corrosion-
resistant material not smaller than the outlet size as required below for air-cooling coils or condensing
fuel-burning appliances, respectfully.
Condensate wastes pipes from air-cooling coils shall be sized in accordance with equipment capacity as
follows:
Equipment Capacity
Up to 20 tons of refrigeration
21 to 40 tons of refrigeration
41 to 90 tons of refrigeration
91 to 125 tons of refrigeration
126 to 250 tons of refrigeration
Minimum
Condensate
Pipe Diameter
."~:
--
3/4 inch
1 inch
1 1/4 inch
1 1/2 inch
2 inch
The size of condensate waste pipes may be for one unit or a combination of units, or as recommended by
the manufacturer. The capacity of waste pipes assumes a 1/8 inch-per-foot slope, with the pipe running
three-quarters full.
Condensate drain sizing for other slopes or other conditions shall be approved by the Building Official.
SECTION 54
Section 7.40.130 of the Dublin MUl!icipal Code is amended to read:
Section 7.40.130 Section 608.7, Chapter 6, Water Pressure, Pressure Regulators and
Pressure Relief Valves - Added. '
Section 608.0 is amended by adding a new subsection 608.7 to read:
608.7 Each riser or branch shall be provided with an accessible sectionalizing valve in hot and
cold-water systems to permit servicing or replacement of piping or equipment. Stop valves shall be
provided at each fixture.
,.,:
20
.
.
.
SECTION 55
Section 7.40.140 of the Dublin Municipal Code is amended to read:
Section 7.40.140 Section 713.0, Chapter 7, Sewer Required.
Section 713.0 Sewer Required.
Every building in which plumbing fixtures are installed and every premises having drainage
piping thereon shall have a connection to a public sewer. Except that where there is no available public
sewer within 200 feet, measured along streets, alleys, or public right-of-way upon which a lot abuts, and
when the size of the property is in excess of 40,000 square feet, drainage piping from any building or
works may be connected to an approved private sewage disposal system. All such sewage disposal
systems shall be designed, constructed, operated, and maintained in compliance with the Health
Officer's regulations.
Not withstanding the provisions of Section 320 and Section 11.8 of this Ordinance.
Whenever a public sewer is extended so as to become within 200 feet of any premises having a private
sewage disposal system, said private sewage disposal system shall be abandoned and the building sewer
shall be connect to the public sewer.
No permit shall be issued for the installation, alteration or repair of any private sewage disposal system
or part thereof of any premises for which a public sewer is within 200 feet.
On every lot or premises hereafter connected to a public sewer, all plumbing and drainage systems or
parts thereof on such lot or premises shall be connected to such public sewer.
SECTION 56
Section 7.40.150 of the Dublin Municipal Code is amended to read:
Section 7.40.150 Section 398.3, Ch2pter 11 3, Location.
Section 308.3 is a.'llended by adding a new subsection 308.3 to read:
308.3 It shall be unlawful to sell, transfer, divide, or set off any portion of any lot which in any
way reduce the minimum areas set forth in Section 713.0 or reduce the minimum distances set forth in
Table 7-7.
SECTION 57
Section 7.44.030 of the Dublin Municipal Code is amended to read:
Section 7.44.030 Adoption.
The "Uniform Mechanical Code" 1994 Edition, published by the International Association of
Plumbing and Mechanical Officials and the International Conference of Building Officials, including
Appendix Chapters A, B, C and D, a copy of which is filed in the office of the City Clerk, is adopted by
reference as the mechanical ~ode for the city pursuant to the provisions of Section 50022.1 et seq. of the
Government Code of the state of California except is hereinafter modified in Section 7.44.070.
SECTION 58
21
Section 7.44.070 of the Dublin Municipal Code is amended to read:
Section 7.44.070 Chapter 1, Administration - Deleted.
Chapter 1, including Parts I, II, and III is deleted.
e::
SECTION 59
Section 7.44.080 of the Dublin Municipal Code is added to read:
Section 7.44.080 Section 301.1, Chapter 3, Condensate Disposal.
Section 310.1 is amended by replacing it to read:
Section 310.1 Condensate from air cooling coils and comfort cooling equipment not intended to
be used for the storage or holding of food or cLrinks shall be collected and discharged to a storm sewer or
other approved points of disposal acceptable to the Building Official.
Termination of such drains shall be made by an air break. Condensate drain lines in sizes 1 1/4" and
larger shall be assembled using approved drainage pipe and fittings. Condensate waste water shall not
drain over or upon a public way, sidewalk, pedestrian ramp or the like. Condensate drains with
termination's within the interior of a building shall not be connected to the building roof drain or
overflow piping systems.
SECTION 60
Section 7.48.030 of the Dublin Municipal Code is amended to read:
.',:
"
Section 7.48.030 Adoption.
The "Uniform Housing Code" 1994 Edition, published by the International Conference of
Building Officials, a copy of which is filed in the office of the City Clerk is adopted by reference as the
housing code for the city pursuant to the provisions of Section 50022.1 et. seq. of the Government Code
of the state of California except as hereinafter modified in Sections 7.48.050 through 7.48.140.
SECTION 61
Section 7.48.050 of the Dublin Municipal Code is amended to read:
Section 7.48.050 Chapter 1, Title and Scope - Deleted.
Chapter 1 on Page 1 is deleted.
SECTION 62
Section 7.48.060 of the Dublin Municipal Code is amended to read:
Section 7.48.060 Chapter 2, Enforcement - Deleted.
Chapter 2 on Pages 2 and 3 is deleted.
e~
22
SECTION 63
.' Section 7.48.070 of the Dublin Municipal Code is amended to read:
Section 7.48.070 Chapter 3, Permits and Inspections - Deleted.
Chapter 3 on Page 4 is deleted.
SECTION 64
Section 7.48.080 of the Dublin Municipal Code is amended to read:
Section 7.48.080 Section 505.8, 505.9, 505.10~ Chapter 5, Sanitation- Added.
Section 505 on page 8 is amended by adding new subsections 505.8, 505.9, and 505.10 to read:
505.8 Garbage Receptacles. An adequate number of appropriate receptacles with close fitting
covers for garbage and rubbish as may be considered necessary by the enforcing agency shall be
provided for the occupant of every dwelling unit by the owner or operator of every apartment house,
hotel, or combination thereof. Each receptacle shall be kept in a clean condition and good repair.
505.9 Bedding. In every apartment house or hotel every part of every bed, including the
mattress, sheets, blankets, and bedding shall be kept in a clean, dry and sanitary condition, free from
filth, urine, or other foul matter; and from infection of lice, bed-bugs, or other insects. The bed linen
shall be changed before a new guest occupies the dwelling unit.
.
505.10 Caretaker. ..... manager, janitor, housekeeper, or other responsible person shall reside
upon the premises and shall have charge of every apartment house in which there are sixteen (16) or
more apartments and of every hotel in which there are twelve (12) or more guest rooms, in the event that
the owner of any such apartment house or hotel does not reside upon said premises. If the owner does
not reside upon L.1e premises of any apartment house in which there are more than four (4) but less than
sixteen (16) apartments, a notice stating his name and address, or name and address of his agent in
charge of the apartment house snaIl be posted in a conspicuous place on the premises.
SECTION 65
Section 7.48.090 oftlte Dublin Municipal Code is amended to read:
Section 7.48.090 Chapter 11, Notices and Orders of the Building Official- Deleted.
Chapter lIon Pages 16, 17, and 18 is deleted.
SECTION 66
Section 7.48.100 of the Dublin Municipal Code is amended to read:
Section 7.48.100 Chapter 12, Appeal- Deleted.
Chapter 12 on Page 19 is deleted.
.
SECTION 67
Section 7.48.110 of the Dublin Municipal Code is amended to read:
23
Section 7.48.110 Chapter 13, Procedures for Conduct of Hearing Appeals - Deleted.
Chapter 13 on Pages 20, 21 and 22 is deleted.
.'..
, ,
SECTION 68
Section 7.48.120 of the Dublin Municipal Code is amended to read:
Section 7.48.120 Chapter 14, Enforcement of the Order of the Building Official or the
Board of Appeals - Deleted.
Chapter 14 on Pages 23 and 24 is deleted.
SECTION 69
Section 7.48.130 of the Dublin Municipal Code is amended to read:
Section 7.48.130 Chapter 15, Performance of Work of Repair or Demolition - Deleted.
Chapter 15 on Page 25 is deleted.
SECTION 70
Section 7.48.140 of the Dublin llfunicipal Code is amended to read:
Section 7.48.140 Chapter 16, Reco....ery of Cost of Repair or Demolition - Deleted.
e"".
--
Chapter 16 on Pages 26, 27, and 28 is deleted.
SECTION 71
The provisions of this ordinance shall take effect on January 1, 1996 pursuant to Government
Code section 36937 as an urgency ordinance. The urgency is based on the fact that the State published
and adopted the 1994 editions of the model codes on July 1, 1995. Local jurisdictions must then adopt
these codes within 6 months, which is January 1, 1996. This City Clerk of the City of Dublin shall
cause this ordinance to be posted in at least three (3) public places in the City of Dublin in accordance
with Section 36933 of the Government Code of the State of California.
PASSED, AND ADOPTED BY the City Council of the City of Dublin, on this day of
1995, by the following votes:
AYES:
NOES:
ABSENT:
ABSTAIN:
e:
Mayor
24
.
.'
.
ATTEST:
City Clerk
25
#
..,""
.'
RESOLUTION NO. - 95
A RESOLUTION OF THE CITY COUNCIL
OF THE CITY OF DUBLIN
*********
FINDINGS AS TO WHY AMENDMENTS TO THE UNIFORM CODES ARE NECESSARY
WHEREAS, Section 17958.7 and 18941.5 of the Health and Safety Code of the State of California
requires cities to adopt ordinances which impose the same restrictions as contained in the California
Building Standards Code; and
WHEREAS, the 1994 Edition of the Uniform Building Code, 1994 Edition of the Uniform
Plumbing Code, the 1994 Edition of the Uniform Mechanical Code, the 1994 Edition of the Uniform
Housing Code and the 1993 Edition of the National Electrical Code have been adopted in the California
Building Standards Code; and
WHEREAS, this City Council having before it an ordinance adopting those codes set forth herein
above with changes; and
WHEREAS, Section 17958.7 and 18941.5 of the Health and Safety Code of the State of California
authorizes cities to make changes or modifications to the provisions of the California Building Standards
Code as the City determines are reasonably necessary because of local climatic, geological or
t<.;pographical conditions; and
WHEREAS, this City Council has reviewed the reasons for the changes and modifications as set
forth in Exhibit "A".
.'
NOW, THEREFORE, BE IT RESOLVED that the Dublin City Council does hereby declare and
find that said changes or modifications to the provisions of the State Building Standards Code are
reasonably necessary because of local climatic, geologic or topographical conditions as set forth in
Exhibit "A".
BE IT FURTHER RESOLVED that a copy of this resolution be forwarded to the California
Department of Housing and Community Development for filing as required by Section 17958.7 of the
Health and Safety Code of the State of California.
PASSED, APPROVED AND ADOPTED this
AYES:
NOES:
ABSENT:
ABSTAIN:
day of
, 1995.
. Mayor
ATTEST:
.'
City Clerk
~XL~i~;{!'!' 3
~ r- ,. " ~-,,:t l
EXHIBIT" A" TO RESOLUTION -95
LIST OF CHANGES AND MODIFICATIONS TO THE 1994 EDITION OF THE
UNIFORM BillLDING CODE, THE 1994 EDITION OF THE UNIFORM PLUMBING CODE,
THE 1994 EDITION OF THE UNIFORM MECHANICAL CODE, THE 1994 EDITION OF
THE UNIFORM HOUSING CODE AND THE
1993 EDITION OF THE NATIONAL ELECTRICAL CODE
.""
"
The sections listed below are sections of Ordinance -95
Sections 1.3.4.7,8.9.10. 13. 14,32.33.34.35,36.37.38.39.40.41.47.48,49.54.55.56.58.61.62,
63. 64. 65. 66. 67. 68. 69 and 70 have been reformatted to new section numbers.
Sections 2. 11 referenced incorrect reference.
Sections 5. 12. 15, 16. 17. 18. 19.21.24. 31.42 and 43 are in the new 1994 uniform codes.
Sections 6. 44. 46. 57 and 60 adopts the uniform codes.
Section 20 coincides with State law.
Section 22 modifies the Uniform Building Code to require an automatic fire-extinguishing system when
. of type V construction and the floor area exceeds 3,000 square feet in all occupancies, except R,
Division 1 and 3.
Section 23 modifies the Uniform Building Code to require an automatic fire-sprinkler system when Group
A, B, E, H, I and R-l and R-3 occupancies are located more than 1 'is miles from a fire station.
Section 24, adds a' requirement of a minimum of one 1/2" diameter top and bottom reinforcement in all .'~
continuous foundations. This amendment is necessary because the City of Dublin is within a very
active seismic area (Seismic Zone 4) and local soil conditions can be highly expansive clay soils.
The Northridge earthquake provided hundreds of examples of damage to plain concrete footings.
This type of damage is extremely expensive to repair, in contrast to the small expense of providing
nominal footing reinforcement. Footing reinforcement is also necessary to prevent damage due to
pumping action caused by local expansive soils which shrink and swell during seasonal drying and
wetting conditions.
Section 25, modifies the Uniform Building Code to require slab reinforcement. This modification is
necessary due to the expansive soil conditions and this is a typical minimum requirement by soil
engineers in the City of Dublin in order to avoid damage due to soil expansion and shrinkage.
Section 26, deletes the use of gypsum board for lateral bracing. This deletion is necessary because the
City of Dublin is located in Seismic Zone 4. Gypsum wallboard has performed poorly during
recent California seismic events. The shear values for gypsum wallboard contained in the code are
based on mono-directional testing. It is appropriate to limit the use of this product until cyclic
loading testing are performed and evaluated.
Section 27, limits the use of portland cement plaster for lateral bracing to single story residential. This
limitation is necessary because the City of Dublin is located in Seismic Zone 4. Exterior portland
cement plaster has performed poorly during recent California seismic events. The shear values for
portland cement stucco contained in the code are based on mono-directional testing. It is
appropriate to limit the use of this product until cyclic loading testing are performed and
evaluated.
Section 28, adds a new paragraph to require upgrade of suspended ceiling systems for alteration and repair
projects. This amendment is necessary to mitigate a known seismic hazard in existing buildings
due to the City of Dublin's proximity to local active faults.
2
.'
, t
Section 44, limits the use ofNM and NMC cables. The City of Dublin is located in the highly active
seismic zone 4. Nonmetallic-sheathed cable is not afforded the same protection from damage as
wiring in raceways. Damage to Nonmetallic-sheathed cable could occur in a seismic event which
increases the potential for a frre.
.'
Section 49, eliminates water piping in or under concrete floor slabs within a building. This amendment is
necessary for the following reasons:
1. Most of the surface soils in the City of Dublin are relatively young and unconsolidated
sedimentary materials formed from a wide variety of parent materials. The varying chemical
composition, degree of weathering, and the relatively acid environment have created soils of
varying types, which are particularly corrosive in nature.
2. Much of the surface soil in the City of Dublin is highly expansive (i.e., shrink - swell behavior)
and have low bearing strength.
There are two types of expansive soils in the area:
a. the organic silty clays which are the recent bay muds; and
b. the plastic silty clays which weather from the shale found in the hills surrounding the
City of Dublin.
3. The local climate is characterized by markedly delineated rainy and dry seasons, which tend to
maximize the expansive characteristics of soil.
.",.
"
4. Some parts of the City of Dublin have hard water, which is corrosive to ferrous pipe.
5. The groundwater table is unusually high in many places.
6. The City of Dublin is a highly active seismic area.
Section 50, requires backflow protection if drainage piping serving fixtures is less than 12 inches above
the next upstream manhole. This requirements is necessary due to the fact that the City of Dublin
topography includes mountainous and foothill areas with intermittent steep slopes. Also, the City of
Dublin is located in a seismically active area, which increases the likelihood of breakage of building
sewers and laterals, leading to an above average potential of sewage back-up into buildings without
adequate protection.
Section 51, adds a subsection regarding location and termination of cleanouts. This subsection is
necessary because the City of Dublin soils are expansive in nature. These expansive soils create unstable
conditions which increase the potential of breaks in sewer laterals. To maintain health and sanitary
services, it is necessary to gain access, to periodically maintained public sanitary laterals. This is
accomplished by the additional cleanout as required above.
Section 52, details condensate disposal and drain sizing. This amendment is required because the waste
treatment facilities serving the City of Dublin is operating at or near maximum capacity. The discharge of
treated waste water into San Francisco Bay is detrimental to its sensitive ecosystem.
Cooling coil and comfort cooling equipment condensate waste discharge does not contain pollutants
which require treatment before being discharged into storm sewers or the ground.
.' Section 58, amends the code to comply with local sanitation district requirements regarding disposal for
.' ':.condensate for HV AC systems. The waste water treatment facilities serving the City of Dublin is
, operating at or near maximum capacity. The discharge of treated waste water into San Francisco Bay is
detrimental to its sensitive ecosystem.
3
Cooling coil and comfort cooling equipment condensate waste discharge does not contain pollutants
which require treatment before being discharged into storm sewers or the ground.
4
. ,0
e,--.:,
, ,
e"