HomeMy WebLinkAbout8.3 Shannon Center Building Improvement Plan CITY OF DUBLIN
2, ) o -3o
AGENDA STATEMENT
CITY COUNCIL MEETING DATE: January 12 , 1987
SUBJECT Shannon Center Building Improvement Plan
EXHIBITS ATTACHED A. Building Improvement Plan Report
B. Memo from V. Taugher, Head Building
Official
RECOMMENDATION 1) Receive presentation from John
I',' Nelson of Hansen/Murakami/Eshima,_
Inc.
2 ) Consider Proposed Recommendations
3 ) Direct staff to develop a
recommended timeline as well as
sources of funding as part of the
Proposed 1987-88 Capital
Improvement Program.
FINANCIAL STATEMENT See attached report for Construction
Cost Analysis
DESCRIPTION At the February 24 , 1986 meeting of the
Dublin City Council, the Council retained the services of
Hansen/Murakami/Eshima, Inc. , to develop a Building Improvement
Plan for the Shannon Community Center. The main objectives of
the Building Improvement Plan were to:
1. Assess the overall condition of the building and
identify deficiencies in building design
2 . Make recommendations as to needed building improvements
3 . Prepare a preliminary improvement plan and cost
estimate
The study done by Hansen/Murakami/Eshima, Inc. , comprised four
main areas of concern. These areas are: ( 1) Life Safety, (2 )
Handicapped Accessibility, (3 ) = Function, as it relates to
architecture, structure, heating, ventilation, air conditioning,
plumbing and electrical systems, and (4 ) Maintenance.
The Building Improvement Plan Report shown in Exhibit A is meant
to focus attention on the modifications necessary to correct
building deficiencies to accommodate present and future users of
the Shannon Community Center. The report contains an analysis of
existing conditions, recommendations for improvements and a
construction cost analysis.
The Head Building Official, Vic Taugher, has reviewed the report
and his comments are summarized in Exhibit B. He is in agreement
with the architects recommendations in all areas except
handicapped accessibility. It is his recommendation that all
doors and clearance in the hallways be accessible to handicapped.
In discussing this matter with the architects, they have
indicated that it is their intent to widen all doorways, but that
there are two areas in the main hallway that are impossible to
obtain the required clearance without destroying the columns that
support the ceiling beams. This would be extremely costly and
would alter the appearance of the hall so that it would not be in-
conformance with architecture found throughout the remainder of
the building. It is their recommendation that we seek a waiver...
from the Building Official.
------------.------------------------_ -----------------------------
ITEM NO. '
AGENDA STATEMENT - Shannon Center Building Improvement Plan
January 12 , 1987
Page Two
Mr. Taugher also clarifies Title 24 requirements with regards to
the necessity of an elevator. If restrooms are added to the
lower level and if the lower level is accessible to the
handicapped, then an elevator is not required. However, if a
program was conducted downstairs and a participant was required
to go upstairs, then an elevator would be required.
It is the recommendation of . staff that the City Council :
1) Receive presentation from John Nelson of
Hansen/Murakami/Eshima, Inc.
2 ) Consider proposed recommendations
As the Building Improvement Plan Report was not complete at the
time that the Five Year Capital Improvement Program was. prepared,
funds were not budgeted for improvements at Shannon Center.
Therefore, it is necessary for the Council to determine what
improvements, if any, are to be made, in order that staff can
develop a timeline for implementation, and funding sources to pay
for those improvements .
EXHIBIT A
THE SHANNON COMMUNITY CENTER
BUILDING IMPROVEMENT PLAN
HANSEN/MURAKAMI/ESHIMA, INC
ARCHITECTS & PLANNERS
424 SECOND STREET
OAKLAND, CALIFORNIA 94607
I. Introduction
Purpose of Study
Project Description
Procedure
II. Analysis of Existing Conditions
General
Life Safety
Handicapped Accessibility
Function
Architectural
Structural
Mechanical
Electrical
Maintenance
III.Recommendations
Life Safety
Handicapped Accessibility
Function
Architectural
Structural
Mechanical
Electrical
Maintenance
IV. Construction Cost Analysis
V. Summary
VI. Appendix
Geotechnical Consultant Report
Structural Consultant Report
Mechanical Consultant Report
Electrical Consultant Report
VII.BibliographV
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
1
t
I. Introduction
Purpose of Study
This report presents a building improvement plan and preliminary
construction cost estimate for modifying the deficiencies at the Shannon
Community Center. The main objectives of the study were:
1. Assess the overall condition of the building and identify
deficiencies in building design.
2. Make recommendations as to needed building improvements.
3. Prepare a preliminary improvement plan and cost estimate.
Project Description
The Shannon Community Center is located amidst a pastoral setting in the
north-east corner of Shannon Park in Dublin, California. It was
constructed in 1973 from plans developed by the office of Walter Thomas
Brooks Architect.
The Community Center is managed by the City of Dublin Recreation
Department. It is used daily for community programs including meetings,
receptions, dining, offices, jazzercise, dancing, child care, recreations
programs and classes.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
Procedure
The study comprised four main areas of concern. These areas are (1) Life
Safety, (2) Handicapped Accessibility, (3) Function, as it relates to -
architecture, structure, heating, ventilation, air conditioning, plumbing
and electrical systems, and (4) Maintenance.
Current codes, regulations and building standards were used to assess the
condition of the building.
_ The following study is meant to focus attention on the modifications
necessary to correct building deficiencies to accommodate present and
future users of the Shannon Community Center.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
• 3
II. Analysis of Existing Conditions
General
The Shannon Community Center is an aesthetically pleasing building with
tiled, gable roofs and deep overhangs. The primary entrance is from the
south by way of a wooden bridge which spans a creek channel. The main
floor has approximately 8,500 square feet with an additional 5,000 square
_ feet exterior wood deck. The lower floor provides an additional 3,500
._ square feet.
The building is a wood framed, sprinklered structure of Uniform Building
Code classification type V, no hour construction. Its use for assembly
purposes classifies it as a Group A, Division 3 Occupancy.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
4
Life Safety
The Uniform Building Code sets standards regulating issues which affect the
life, safety and welfare of a buildings occupants. These issues range from
the type and method of a building's construction to the exiting of its
occupants. The following items are not in compliance with current code
regulations.
1. Required exiting from most occupied spaces is achieved by direct
access to the exterior, thereby minimizing the amount of corridor
space. An exception to this occurs at the required 2nd exit from the
East Meeting Room (refer to page 7). This exit path, which is
undersized, passes the public telephone, stairs and discharges out the
side door. Another exception occurs at the corridor from the lower
level Pre-school Room (refer to page 8).
2. The hardware on most doors which are required for exiting is improper,
missing or needs replacement or adjustment. Typically, only one leaf
of many double doors throughout the building is required for exiting
by the code and has exit hardware. However, in the case of an
emergency it is probable that both leaves of a double door will be
used.
3. Doors to the exterior from the Kitchen, Social Hall and East Room have
a 5" step at the threshold down to a concrete pad. A landing may not
be more than 1/2" lower than the threshold of the doorway. Also a
landing must be provided on both sides of a door.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
5
4. The doors from the Social Hall and offices through the entrance lobby
to the exterior, are not required exits by code but they would likely
be used as exits in an emergency.
5. Safety glazing material is required in hazardous locations. Locations
adjacent to and in the same plane as a door are considered hazardous
locations. Only some of these areas have safety glazing.
_ 6. The primary path of travel from the main parking area to the lower
_ level is through the main floor and down the stairs. These stairs
serve an occupant load greater than 50 and should be not less than
3'-8" in width. The stairs measure V-5 1/2" wide.
7. The handrails at the above stairs are not continuous their full length
and do not have proper extensions beyond the top and bottom risers as
required by code.
8. The exterior stairs from the deck to the path on the east side of the
building and from the lower level corridor up to the same path have
similar deficient handrail configurations.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
6
I
9Ecp down
concre Fe pad ^'--'1�- ----'-- .-_- --'
5 ste p own d to i.----G---- - --�- ------�•� -_� _- -{--. ��
r ------- -.--- ---- ---- -- --L. -- �_ ill
con.rc tc pod Kf
Fchen -
r --- ---= --- -- —1fj FXIk
c j fbor hunhts should 6c '
I 11=xit� T 'ilic Sam c an 6et1h,yldcs - ------------ .
I❑; —J Li L ❑I II I• f�ndrails
--- �-• •..� �re rs a 5° Step to. __... - d no
I � �G Cor7crGte dd�.
❑ Sim I
ilar at W�51 Room (❑ ❑ _ mccE code
Ino on West Room -rd kitchen �I
P Social Ha II Eaat Room
doors ❑� ❑• - _� r�
Ex i
I I.
YxIE Q
Entr Q- ' ri
----- -- -----------f-.-- °FI'cc I q \\Z2- door I
• t Gam• �; '^ i�—= lfff}re rcyuire� wrdkh
Io >`his cxil- door
- ❑ _ �� r
r 3
5omc windows adjacent__.__ fhesa doors arc not his does not meet \H.,Arail5 arc not
to doors do MOE have rc9ulrcd e-X& doore. the minimum re9ulred conEfnuous and do not
safety glazing as rejuircd. It Is pro6a61e that corridor'wtdth of 3'g" have Proper extens(ons•
they Would 6c used
�s cA5 in an
•Door hardware Is IncompleEe, emergency.
inoperative or needs- _ -----_�__. -
�diusEmenE --
locationa
i
• I
I I I
MAIN:.LEVEL
0-4 S 16 tEl � EXISTING
LIFE SAFETY
. ._._.._._._._._......_._.
I
i R ndrai
,....... ...... ..... .. mee� code
- Courl:Yard
._.... f...:....__. .._.. _.. _ ..._.. .._..: 17:7 _�._..
1
5ce main level F-xtl
_ plan for {airs R�-c-school Room
and hariJral 1 I
i ``
:..-.. -�
Fx1�
I
I �
i
mccLnj Room f
- 1� n�rails do
Ex1� r ttoi mcr-L
:
co�e.
i
---; In{ermediafe
rcgui re,
�.
LOWER LEVEL
04. 8 16 ® � EXISTING
LIFE SAFETY
Handicapped Accessibility
Handicapped accessibility has become a major issue in the design of all
buildings. It is regulated by the California Administrative Code, Title
24. The following items do not comply with current regulations.
1. The primary entrance to the Shannon Community Center is from the main
parking area on the south side of the building. Handicapped parking is
isolated on the north .side with no accessible route to the primary
entrance.
2. A secondary entrance from the handicapped parking area provides access
to the north side of the building. Circulation from the north entry to
other areas of the building is through the East Meeting Room. This is
the most direct route for non-handicapped persons. However, this path
of travel does not meet minimum requirements for handicapped persons.
Door widths, locations and hardware are all obstacles in providing an
accessible path of travel.
3. Architectural features which generally comply with handicapped
regulations are floor surfaces and thresholds. However, the number of
features which do not comply outnumber those which do. The lower
level, restrooms, telephones, and drinking fountains are inaccessible
to handicapped persons. Also door widths are inadequate, hardware is
inappropriate or lacking, and opening and closing door pressure is
excessive.
Shannon Community Center
Hansen/Murakami/Eshima, Inc. .
a
-- Tom harid icap parking
r
l
I I �
r---
i eleadrario/ Ii
_ I
II
' sEcP _ � re9uirc I.
- ---------- ❑-- �-------- -I-- �a �� � III � Pair o� Z=3"
„
——------
�r mimum door
G widFh is 3'-0:.
Nob acces5i6le q p __� II hardware
Z'0" I-L •�, clots nob
doors
I II
wrbE Room jI Social Hall I East Room c II
clear space �-r ❑' i i ir
re
requlrcd on Pullside I •
of door ❑ i--! L Ll l II I I i I.
I�
F.. I
floor. L 1
----I - - - --- ----- -� —`� I I , I ❑
_i 9 Hatdralls
c car re ulre d do
I!I 1 0 no[ have
3'-6" corridor j raPPcr
•i i ❑- ❑.. ..G- _�❑•' - Cr..pt I 'p i-y widEh I c�P nslon5
I
I -- I
-1 co4nLCr 6e1 ghE= 3'-3" clear L- L -` ._Doorwl[j .,.clearantes- _ -Telepho_nc Mounhny Handrails are noE
too. high corridor w&h. -:- toilet shalls, and ::: helghl and
- ------
on boih Sides' .e
3'•8' is minimum - _... 114ure heights. -, .. clearances 'do noE: . _ : stairs and do not
required - . ....are-nob a4cessl6le. -__ meeb re9ulremenF5- have e-xkeneions
i a� rcquirc
I .
Drinking j(ount3i.n
.. does no Rave -•�I�_,
re9uirad mounting
hefIhl- or
clearances
i I I I
I I •
MAIN LEVEL I I >°rimarrl FnErance
II r_; I [rem main parking U
0 4 8 16 I I I EXISTING.
--- HANDICAPPED ACCESSIBILITY
10
�1
L ,
._... _ ........
- HariAwls do noL
-3 doors double door
rc9uire meths
iirc 6lock--d off
' . I ,
' 18" clear
nd ra i Is
o j® spa�c rc�uir�d
regurred
F� ........_
Handrails wish
I
ax ctlsiotis are
re uirecl on 6A
si es o� all .stairs
LOWER LEVEL
0 4 8 16 EXISTING
HANDICAPPED ACCESSIBILITY
Function - Architectural
Several architectural deficiencies prevent the Shannon Community Center
from operating efficiently. Some of these have resulted in additional
monthly operating costs or limited rental usage.
1. Circulation from the Main Entry to the North Entry and parking area is
through the East Meeting Room. Access to the Kitchen or West Meeting
Room is from the exterior or through the Social Hall. This arrangement
prevents usage of all three meeting rooms concurrently.
2. Acoustic problems occur throughout the community center. Sound
reverberation is the main cause of the poor speech quality in the Social
Hall. There is a lack of sound isolating materials in the walls, and
the large amount of glazing in the Main Entry permits airborne noises to
travel from room to room.
3. The configuration and location of the raised platform in the Social Hall
is awkward. The depth of the platform does not permit users to be a
part of the room and cuts off viewing angles from the room. Circulation
from the entry to the Kitchen bisects the hall and increases the
distance between the platform and the first row of seating.
4. Storage space on the main level is inadequate for major items including
chairs, tables and a piano.
5. The Kitchen is of residential quality. The plastic laminate counter
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
12
tops and wood cabinetry show wear. Most users hire caterers because
there are no cooking facilities such as a stove or microwave oven.
6. At present there are three semi-private offices of which two are
usable. An additional three semi-private offices are needed.
7. A portion of the lower level was designed for use as an arts and crafts
room. It is now used as a pre-school room. Counters are 3 feet high
and the concrete floor where children spend their time is covered with
.. various area rugs.
8. The courtyard contains two small trees and a play structure for
pre-schoolers. Because of the high concrete walls surrounding the area
there is no air movement or visual relief. Heat build-up is increased
with the reflectance off the light colored walls.
9. There are no restrooms on the lower level.
10. The new Master Plan of Shannon Park does not include restrooms for park
users. A restroom with exterior access is needed.
11. Darkness and dampness limits the use of the lower level meeting room.
There is not enough natural lighting in this room.
12. The ten feet six inch tall glass doors at the Social Hall and West
Meeting Room are extremely flexible. The amount of glass in proportion
to the wood stile and rail does not provide enough rigidity for a large
door. When the doors are held open with a stop on the floor the closer
at the top of the door bends the door nearly six inches.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
13
13. There are no gutters at the perimeter of the roof. Persons entering or
leaving the building during a mild rain shower must cross beneath a
sheet of water.
14. The exterior concrete slab at the entry to the lower level meeting room
does not slope to the drain. Ponding during and after rains causes
this entry to be unusable and promotes decay of the wood sill and
mullions.
15. Energy Conservation within the building is almost non-existent by
today's standards. . Drawings indicate insulation values of R-2.08 and
R-7 at the roof and lower level ceiling. A minumum of R19 is used
today. Wall and floor insulation, double glazing and weatherstripping
are not apparent. This has resulted in large heating costs in winter
and the need for air conditioning during summer months.
16. The new Master Plan for Shannon Park includes the retention of the
children's play area south-west of the community center. It is
important for parents at the Center to be able to monitor their
children. This play area is not visible from the building because of
the solid railings along the perimeter of the exterior deck.
17. The approach to the community center from the parking area is not
highly visible. Persons going to the center are not directed towards
it.
•
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
14
Rcsl�en�ial klEehen r--- --= 5eaon�ar4 end Handicap
--- ----w/ minimal apTlianccs4 -- rii
PEI
i I rage . `Noriaa`En!n I.
SeaEin9 begins here I space � ------------
Gp Lp foo far from
o
----- L.• .. T --
r /
Vcst Room Social Hall EasE Room
�� inoperable doors - -• Q � _
t large la3s Acoustical . Pro61em 1- I i AcousEical Pr ms r1 -T
r--I r-- o c
I" n ❑ __.areas .abo.va_- 1 Q 61
F �I large 91ass I 1 "
I
f ,• .- areas above
Y"
`---------' --I ---/— --- -- �`a\��`l 3 aFFices ❑ ...
L
EnEr
tl
i I!
SccuriEy
r, Pro6lerns
Fl
I
1- 1 L
..Soli) rallinq �64&rWc�s-view .. RainwaEcr lows over - Dark room rinishe,s
_o{ ahilArcn-5 pla4: : area {hc roof, ej4e, above Wood surfaces In EailcE A.Alls. I..
--"- Jo noh mec� health requirem=nrs
No door a� .t-od.L- 3Eall
MoSE room (iniShes
-- -::Hre Eoo d2Y .
_-Mininvl.use of Ehcrmal insulakian
- C
r r
I I Primar - EnEran« From I
MAIN LEVEL I I Main Parking LoE ....._.
0p4 816 i r_I j EXISTING
FUNCTION ARCHITECTURE
15
Hi h re lcc�smcc
�of �i9h� col one
_ walls__.. __--
_... .......-..... ........
�
Cour�Yarc1
Hot ! No air movcmen} 2_ —....
concrcE= {loo ( I
. I
Prc-school Room - -
3
( ' Mectin Room
concrcve oor �
(Dark 4 amp)
d with cracks I foil 6t- croJ,-J swag
P
�rcm ;the wall
he 9u+-�c r for
\thy deck above
I I is In rrt icla i r
No rco� rooms
Pondin9 Solid woccl
Doors wikh
e.ra4 ks
LOWER LEVEL
® q EXISTING,
FUNCTION ARCHITECTURE
Function - Structural / Mechanical / Electrical
1. The roof girders have severely split and twisted such that in some
cases the supporting connections may be damaged. _
2. Significant portions of the plywood nailing at shear walls in the
basement did not engage the stud. In addition, the nailing of some
plywood shear walls was less than indicated in the original plans.
3. Poor initial compaction of the soil at the perimeter of the building
has resulted in settlement of the soil. The conrete gutter for.
drainage of the exterior deck was intended to sit on top of the
perimeter soil which has now sunken as much as 18". This gutter is now
only attached to the side of the concrete retaining wall but not
supported from below.
4. The steel girders at the north end of the bridge are supported on a
neoprene bearing pad and bolted to the concrete piers. Slotted bolt
holes were provided to allow for thermal expansion and contraction of
the bridge girders, but the bolts are tight up against one side of the
slotted hole. The bolts could eventually shear off.
5. The suspended light fixtures and large wooden chandeliers do not comply
with current seismic code requirements. They must be able to swing to
a 45 degree angle without striking anything, or they must be fixed.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
1 7
6. Contrary to Mechanical Code requirements the Men's and Women's Toilets
have no ventilation. The original ventilation louvers have been
removed and sealed off.
7. The only air conditioning in the building is provided by a window unit
in the office space. Office users have complained that this cooling
system is inefficient.
8. The building's heating system is composed of eight gas fired furnaces
and three electric wall heaters. The gas furnaces supply the air into
each room within a few feet of the grille which returns air into the
furnace. This has resulted in poor air circulation and heating.
9. The heating system must be turned on before occupants leave for the
building to be warm the following morning. This has contributed to the
high energy costs.
10. The electric heaters in the Social Hall are not working well. When
working properly they are still a high energy consumer.
11. General lighting is incandescent, with a row of very inefficient
recessed fluorescent fixtures at the perimeter of the long walls of
each room. The incandescent lighting system is very inefficient,
providing low lighting levels in most areas.
12. The available power in the existing electrical service switchboard is
only sufficient to handle minor additional loads.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
18
Elcclrie- wall I--- — --—... ------ --- � »?� --- �
- heaters _
r------- — --- --------- ---' ---` v�--� CSC'.\ i
existing .furnaces axls ing furnace 1
6
fG^r r ❑
--- i!ow light level rC�
l _
9
Wc,gf Rool}( Social Hall i East R-om
Ej t. ,
•, r-�±. ' L- - 1 �- T - -T�4��.., _I_ -I__T �.-�I�� I i I
.; I. i•i Twisting roof - -C�� 'L-� G ya ct c� cc. Gr `'•I- `l 4--t
1
L ' beams above I ..
4P
suPPIY air•re9ister9 wall mounted low light levels
air condihonin9 unit''" no ventilation
• I
Mootly incandescent li9htim'
low light levels
High enerq� corisumPtion
Minimal air/heat eirculation
-Air conditioning unit in office only ii -- I
1 jjTl I^^I I
MAIN LEVEL
}j– r-
0 4 8. 16 (T[-� I ! i EXISTING
-� F UIN C T 10 N STRUCT./MECH./ELECT. e
J-1 ....._....—- -
i
Cow l Yard i
exiAin9 {t{rMaccs
!
Prc school Room '
' ...( _._
i , M�o�in� Room
r
i
j.._. ..... ._ .. ... .... ... _. .: _....._
•I i�klc air/h�af circulation
•IoW liq k L lcVGIS
LOWER LEVEL
0 4 8 16 EXISTING
LAEA I= U N C T I O N STRUCTJMECHJELECT•
Maintenance
General maintenance items which are presently in need of repair or
replacement and will require periodic inspections are as follows.
1. Floor surfaces: Carpeting in the West Room needs replacing. Sheet
vinyl and vinyl tile flooring in most areas is worn or has raised edges
and needs replacing. The concrete floor slab on the lower level has
cracks which have been patched. Periodic inspections should be made
for any cracks which may develop.
2. Oak thresholds at exterior doorways are worn or show evidence of
dryrot. This condition in conjunction with the inappropriate hardware
and oversized flexible doors at the Social Hall and west meeting room
has proven to be a security problem.
3. There is evidence the roof has leaked. Waterspots are visible on the
underside of the wood ceiling in the office space. It is possible the
membrane beneath the wood deck has failed in areas which are not easily
accessible to inspections.
4. There are many knot holes in the wood decking which have been patched
with sheet metal. Drainage from the roof spills onto certain areas of
the deck and collects between spaced boards along with trash and
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
21
leaves. In many areas the decking boards have little or no gap between
which would allow for air circulation and drying out of the wood or
proper drainage of water. Wet debris could eventually lead to decay of
the wood deck as well as deterioration of the roofing membrane.
5. The wood decking at the bridge is not draining properly. The gaps
between the individual wood boards which were intended for drainage are
too narrow and have been filled with dirt and leaves.
6. There is no gutter at the perimeter of the roof. Rain water flows
freely off the eaves and the ends of the roof girders. The ends of
many of the girders show evidence of decay in addition to the growth of
lichen. Many of the girders have "heart centers" and are severely
split and twisted.
7. Electrical receptacles and light switches are showing signs of age.
Many of the light fixtures are damaged, plastic lenses and door frames
are missing and bulbs or fluorescent strips are exposed.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
22
dccaH and lichens ca61nekrN nccds r___ �___ j
on roof 9Irders a6ove refinishm9 —_----- I --i ----_ —
I
k(itchan �Fil I
wo rn floorin9
II
❑' ❑; Inoperable wall fan r j I
C, D Gh D 611-,, wafer marks G
-- .1 disiol red 1 on floor
Gi wall finish r
I I
k'/c.5 Room -5o6ial Nall Fait Roojn
I ❑ worn ❑ ~.
worn earpck carPe� �kep. t' D ❑ I r--
r-H.
Q-1 El
❑ F, -- ----
-
i
I ,
Ln:Lr-
imopara6le 'of{Ice - I
worn.floorin9 Wood deckin
holes in re wood .-deck. . ..
-worn%dry rokl:cd.thresholds - — build up of debris below
broken rcceptaAl s, light swikches, dcckin9, inaccessible
clif users ponding of waEcr to cicanin9
wa r marks on underside o{ wood 'cailin9 ..._. on wooden 6rld9c
• I I I'
.MAIN LEVLL
0 4 8 16 I ' EXISTING,
r-Lr--,
MAINTENANCE
23
i
i I
i
Cour}hard
wa}er marks
above
i
Pre Scllool Room
�l
j
l
Mcc�in9 Room `--
i
walcr marks }
a 6ove
{l
cracks in `
woocl Joor-s
• cracks in concrcte floor
• worn / JrH rotTCq +l res6lcls
• broken rcccptacic.s, li# .sWLHcs, dif iuscrs
LOWER LEVEL
0 4 8 16 EXISTING
MAINTENANCE z4
III Recommendations
Life Safety
Hansen/Murakami/Eshima places a high priority on life safety issues. The
extent to which an existing building must comply with current life safety
regulations, however, is determined by local building officials. There may
be items which local officials consider as hardships and would not require
compliance.
We recommend that the intent of the life safety regulations be satisfied.
The modifications required are as follows:
1. Door hardware should be installed or adjusted at all exit doors to
satisfy exiting requirements.
2. Install exit hardware on both leaves of double doors even if only one
leaf may be the required exit.
3. Provide an exterior landing within 1/2 inch of the threshold height on
both sides of doors used for exiting.
4. Install or modify exit hardware on doors from the entrance lobby to the
social hall, offices and exterior.
5. Glazing in hazardous locations as defined by the code should be of a
tempered or safety glass.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
25
Please note that there are large panels of glass which because of their
unusual locations are not covered by the regulations. The glass above
doorways in areas used as exits could shatter during a fire or
earthquake. We recommend replacing this glazing with safety glass or
at minimum applying a four millimeter clear film (which is available as
a security device) to the existing glazing.
6. Replace or modify handrails to satisfy code requirements at interior
and exterior stairs.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
26
cxtcrior
—
dt cxiE doom 7 — -. --- --- - ---- -_ -- _
{rpical I I~
i Kitchen Repla-c under-
r -------- -----i T .I L I I ',Patr o f
❑ ❑ I 3 O' wide
I. l xl �------- - -- doors.
--- ❑ ❑I❑I 0 A i p II
LU
I
i
West Room Social Nall EasE Roorn Ncw Exit
i. ❑' ❑ --X'[-Iy film .used d5 ❑ - .' �.. .❑�,�
j� - __-on ..91aZi\ -� .. exiE ••.. _ L,I r---�. i--
,
I
I u ❑- -- ' - ❑_ - ❑ ❑ E11 --- -
r. _
L
! t— G
n
7
tr N install 3=0" mode f y
E — III —
IIII tf I `1 door cxis�inqq
Modi f Y doors/hardware j--4
to make IE 'o'era6lc
JmLa I .exit Raloc c -[Ciephor1c RepLce handrails
hardware .. to provide a
minimum corridor
= width of 3 8"
Note: All exit doors t
should ha✓c exit
ha rd wa re
IF ff i i 1E i
MAIN LEVEL
0 4 8 16. RECOMMENDED
LIFE SAFETY
27
_............._._.....
I
_ Courlr yard
is
r
°ai Y
5 main level Exii - handrails to
Pre-,56hool Room
----- Vii._ .... .....
Meciins Room ' Ins}all
�'� I in}ermediaEc
o � I handrail
_ I
LOWER LEVEL
0 '4 8 16 RECOMMENDED
LIFE SAFETY
Handicapped Accessibility
Handicapped accessibility is a major concern in public buildings. Many of
the community programs held at the Shannon Community Center are geared
towards senior citizens who comprise a large portion of the handicapped
population. It is our recommendation to make all major areas of the
Shannon Community Center accessible to handicapped persons.
Entry to the center from the handicapped parking area is through the North
Entry. A path of travel from this area throughout the building should be
established. Modifications include:
1. Provide a corridor from the North Entry to the Main Entry and Social
Hall with a minimum width of 3 feet 8 inches.
2. Widen doors to 3'-0" wherever possible.
3. Provide 18 inches of wall space adjacent to and on the pull side of
interior doors and 24 inches at exterior doors.
4. Modify all doors to include lever handle hardware, kickplates and
closers with a maximum closing pressure of 8 1/2 lbs. at exterior or 5
lbs. at interior doors.
5. Modify restrooms to include a handicapped toilet stall with grab bars.
All toilet accessories are to be within 40 inches of the floor.
Adequate knee space should be provided beneath the counters.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
29
6. Replace existing and provide additional handrails with extensions
beyond the top and bottom risers.
7. Install an elevator to provide access to the lower level.
8. Provide an accessible drinking fountain and public telephone which have
proper clearances and heights above the floor.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
30
False- landing Rclocat� doors i'�_ -To-handicap Parking -- - -
�o floor hei917 t- r-- -- -- -------- - -_-...--- --
ilaisc landing I I I
I{ any addiElon or
1.0 floor he19h6 t---- --- - ------ - --- - ----❑ —� c\ti ❑ I I altcraFlon b madc to
---
! •, ,- I I the
lower
to�er level
E mus 6e occc s3lble
-- by an elcvabor III I
I .
II
I �
LXiend aeecssi6lc /- .. 'r• ' ---- -------r II
-- -� ❑ Z ` F' I\
r I_ IIIr� r k of travel from
rf h cnb2rFo 5xia l
Hall 13oom5
�
I i
1 Inshall S-0, Social Nall Instill 3=0"
minimum doors Telephone c East Rmom
[� �minimum doors
oa M.—
1 i I
! Drinking �ountalnJ` I, A ❑ ❑ r--! J---j
�1i I i
Lit
Raise larldin9 lower -i - !I Remove
- -- ---------- t -= •• -' Relocate door,
make it 5-0".
i' �� cncioSUra I
r---r
Rrovidc handrails II
wiFh exFcnsions II
r r-
-L L i
- Mol Men•s Restcroom Modiry Women's Restroom
to 1 Irldi4,ap tonal, - Fo 1 handicap d• 2 rc9ular
Not-,: boor hardware 1 re� . toilet.-d 1 urinal toilets:
to all occupied spaces Provide 29".clear .. Provide 29' clear
should be made ae-essi6le 6clow lavatory 6elow' lavaFor4
�I -.fill accesorles-_.arc .
to be with .40•.:-
I I� of the `leor
- r r
I I I i
MAIN LEVEL
0 4 8 16 i t I RECOMMENDED•
- HANDI,CAPPED ACCESSIBILITY 31
Provides cicvaEor and
corridor it anti Jdihorl
or ol�craPiom IS madc �o
�hc lower Icvcl
--1---rte._.. ._... ._. ._.. __. ._.
i I1
�.._......_............
_�
_.... I i
--.. ........ _..Courkyard 1
j,
� 1!{
relocate Jaor ,.:__..... I ..._.._.. ....�
...... .......
- Rc lace it h
Provul c
w r handrail
50" door and pre-sohocl Room
- 5ideli9h� ±j - with cxlcnsions
...
7.
Jr_._.... ........
L i
Rcvnrsc
door -swine
RampP with
Mcc�in9 Room j Ivndrails
Provides handrailsi i
w&h eAcnsions -
LOWER LEVEL
0 4 8 16 RECOMMENDED
HANDICAPPED ACCESIEILIT�
Function
The Shannon Community Center was constructed in 1973 to serve the needs of
the community at that time. Present uses and needs have changed. As a
result, the center should reflect these changes to function efficiently.
Function - Architectural
Modifications to several architectural features would be conducive to
efficient usage of the Shannon Community Center. The following are our
recommendations. (Refer to pages 36, 37, 41, and 42 for additional
information).
1. Circulation would be improved with a corridor from the North Entry
through the East Meeting Room to the Main Entry and Social Hall. This
would isolate the rooms and encourage their independent use.
2. The acoustic problem in the Social Hall could be reduced with the
installation of sound absorbing panels on the walls and/or ceilings.
(Refer to reports generated by Charles McMillan of the Lawrence
Livermore National Laboratory Volunteer Program). We do not recommend
the use of carpeting because of the large dance groups which use the
_ room.
3. The raised platform should be removed and the rear wall moved forward.
This would create some much needed storage space. A new movable
platform could be located at either end of the Social Hall.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
VA
4. The kitchen should be finished with more durable surfaces and should
have a range and microwave oven to accommodate different caterers,
non-catered affairs and possible cooking classes.
5. Three additional semi-private offices should be created within the
general office space.
6. The pre-school room on the lower floor should be adapted to the
children with use of lower counter heights and carpeting.
_ 7. Softening the courtyard with the use of planting, trellises, a fountain
or pond would make it a more pleasant space and expand the
possibilities as to its use.
8. Provide additional restrooms on the lower level which are accessible to
the handicapped, children, and the exterior. The location of these
restrooms improves the proportions of the meeting room while
eliminating the dark area of the room. This would make the room more
enjoyable and therefore more usable.
9. The ten feet six inch door heights should be lowered to eight feet or
seven feet to achieve the rigidity needed. This in combination with
the installation of hardware on both leaves of double doors and
replacement of worn or dry rotted thresholds would secure the exterior
doors.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
34
10. Gutters and downspouts would be difficult and expensive to install at
the roof perimeter. We recommend installing rain diverters at
entryways.
11. Replace the concrete slab at lower level meeting room entry with a slab
sloped to the existing drain.
12. The priority for providing thermal insulation is first the roof, second
the walls, and third the floors and windows. We recommend that at
least roof insulation be installed to the underside of the wood ceiling
in the Social Hall meeting rooms and office areas. Weatherstripping
- should be installed at all doors and operable windows in conjunction
with other door and window modifications.
13. The solid guardrails at the perimeter of the deck could be replaced at
portions with wood pickets to provide visibility from the building to
the children's play area.
-- 14. The approach to the Community Center would greatly improve with the
incorporation of the plans for the fountain at the end of the bridge as
recommended in the New Master Plan for Shannon Park. This fountain
area would serve as a focal point for directing people from the parking
area to the Center.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
35
U grad° --.a in. q. Provide
dlverEers on a dlElonal
roof a6ovc
c
K
IEhcn I !
❑ ❑ ❑' ❑
......--------- �1-----i-�._ .i I� NorEh EnEry
--- 1 Ly T
i J (N w walls; �- E -- M err �- I- --- --Elevator (or ad�lihon,al
` 1 ❑ _ I s1'ora9e below -
j----'� � - L.,•.- ; Porkable Pla��orm i.i f I ❑ ❑ � i---- j
n ❑i 1 may be located --
r—C i ' opposite end o{ 1.1211 P ifo u C
\A/e:5t Room __ Social Hall " �� —
< I )as Room
—' r'PPIy -safety film ---II hE colored ._. --lurid As-r61n usEora e I S°Nnd absorbing r -
❑ on lazin above 9 3a et dm q 19 ❑ I Inishes an walls �}-'LLI '
cxitg g floorin9 y finishes on walls ! I L_ !I
i
❑ I
=
G L
w
t --, ---- -- -----i— — �I lowal EnEr .._ .. ,
I of f IGG3 '�
Modify doors/hardware', C'i i ❑ .. — -- --e—o— __ .�..�. `-�.—.G ❑ �. .
to make °Pcra6lc '-
I
a y
Re-pIace/rnodifY Install diverEcrs on roofs Provide corridor
hardware 1:, aE enErywiys, Frpical circulahon
improves securil: '
Provide openings
in .solid railings
Eo provide v1si6ilikq.
1 I I I
I I
.MAIN.LEVEL.
0 4 8 16 I ^ r l RECOMMENDED
F U N C T I'O N. -ARCHITECTURE
' I
InS�all �r�llis exisl-in9
pla►� sCru��'urc
bo,
f--1 I :
1 1
_ � �� Cour�tlarcl
l:or2q �
I
plart}-in (vines) i:. ::......:::...J.._
elcv i _...� ........ on wal
carp�r►n9
lower co�in{cr
Pre-xhool Room Hi-�- for
- cki� rem
ILLam r' : +
IL-J11-i Q
ErT ' r McGtfn9 FZoomn I _
light colored Wome '
I carpc�in9 � ��
New 91ass cnErj doors I i°
i ..._........ . ® _. _.....................
Inst-all resiroom ;acilihcs
5lopc new eoncrrJc wil7h exterior 'access.
awa4 front crtkr4 (Minimum 2 toilc}s 12 lavaEorics
io area drain cacti Sex)
. LOWER LEVEL
0 •4 8 16 � RECOMMENDED
FUNCTION ARCHITECTURE
Function - Structural / Mechanical / Electrical
Modifications to these major subsystems are necessary for this building to
operate most efficiently. The following are our recommendations.
1. It is not possible to repair the twisted roof girders other than to
replace the existing members with new members. This is an aesthetic
decision. The possible damage at the supports of the girders caused by
the twisting is unknown. All of the connections should be inspected so
the degree and extent of the damage is known, and the damaged
_ connections repaired.
2. Additional railing should be applied to the existing plywood shear
walls.
3. The perimeter soil at the foundation walls has settled due to poor
initial compaction. Additional soil needs to be added to support the
_ exposed concrete gutter. If left unsupported the gutter may eventually
break off from the wall. Unless the deck drainage system is altered
the gutter should remain in its present location.
4. The end bearings of the steel bridge girders should be repaired to
prevent the bolts from shearing off.
5. The chandeliers should be tied back so they would not swing and be
_ damaged or cause damage in an earthquake.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
38
b. A toilet exhaust fan should be installed in each toilet room with ducts
extending up through the roof. Make-up-air should be provided through
door louvers.
7. An existing furnace provides heat to both the Main Entry and the
Offices. Since heating is not necessary in the Main Entry, those
registers can be removed and sealed off. A new furnace and air
conditioning unit could replace the old furnace and hook up to the
existing ductwork which will serve only the office spaces. Then the
wall air conditioning unit in the offices can be removed.
8. New exposed round ductwork can be added to each furnace and run in the
high ceiling spaces to provide adequate circulation of heated air out
into the middle of the large rooms.
9. The existing furnace system is not capable of bringing in and
circulating 100% outside air. It may be possible to modify some of the
furnaces for this capability. This feature in addition to the added
_ ductwork mentioned in item 7 will improve the air circulation.
10. With the addition of the exposed ductwork the inefficient electric wall
heaters should be removed and the openings sealed off.
11. Each furnace should have a time clock which would control the operation
of the system. This clock would turn the furnace on and off at pre-set
times to adequately warm the building in winter.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
39
12. The existing incandescent lighting fixtures are extremely inefficient.
It would be wise to replace them with more efficient fixtures with
higher foot candle levels. At a minimum the incandescent lamps should
be replaced.
13. The available spare capacity in the electrical service switchboard is
36 KVA. This would probably be sufficient to handle the proposed
additional air conditioning and toilet exhaust fans. With the
additional power needed for the proposed elevator, kitchen equipment
and other miscellaneous uses the available capacity will most likely be
exceeded. We recommend the installation of a new service conduit and
main switchboard.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
40
remove electric -xhausk -5ps em ; - r---
wall heaters for kitchen �I -- _.___--
---- -- i
Itehen
G.—n.'. r
❑ � I ❑ Re to'.3 fll
IL
I '
' change e
I
We3t Room I Social. Hall East Room
---?. .
-
I r
.Provide nkw expo.ed 9.
r(-'�~ j °� c-� cl� �� I• _ ��' I I d4C�WOr �ro1T1 cXi3'�In
r' I furnace unl�s
I I I
----------------
L— - =close off .._ exhaust fans '
L L
heat registers -
in Io66Y
Typical: New Air Condi{ionin9 Condenser
secure li9hf fixtures [rom Sway III to tic into existin furnace unit•
Provide lime clock and sumer. .. for off ice space?
3wilch for each furnace system !
Provide roof insulavion
Replace existing "vice ndescenF. ligqkt- fixtures �'-
with more efficient, 6ri 'Ht er f ixLdres—
r r
I I I i
I 7 i I
MAIN LEVEL
_T _ I
0 4 .8. 16 i t I ! i RECOMMENDED
-- -i -�
FUN C T I ON STRUCT./MECH./ELECT. 41
..._�.. .
- Cowry and !
•� I
�Ic%
i ? -_:.....
Pry �hool R oo m
- i
�71
LL-
Mcctino Room !! cxatrst fans
o n's
fi
i ,
Ncw dwctwork !`
Rcs�rocwu faciliFies
Z koile�s / Z lavatories a womens
! },oi6� / I urinal /.2 laval•oric s
LOWER LEVEL at mans
0 4 8 16 RECOMMENDED
U N C T I ® N STRUCTJMECHJELECT a
Maintenance
The following items are presently in need of repair or replacement. This
-- is not a complete list of all future maintenance items, but merely a list
of the major items that need attention.
1. Replace carpeting in the West Meeting Room.
2. Replace sheet vinyl and vinyl tile flooring throughout the building.
3. Cracks in the concrete slab on the lower level should be patched with
an epoxy injection as they appear. It is inadvisable that sheet
vinyls, vinyl tiles or similar floor finishes be placed in these areas
as any future cracks would be transferred through these materials. If
a floor finish other than concrete is desired, carpeting is
recommended.
4. The worn wood thresholds at the exterior doorways should be replaced.
New exterior wood thresholds would require continuous inspections and
maintenance due to constant exposure to weather. A metal threshold
requires less maintenance and is recommended.
5. Water spots on the wood ceiling indicate water has at some time
penetrated the roofing membrane beneath the roof tiles. It is
recommended that the leak be found and repaired. It is especially
important to water test roof areas which are to receive insulation even
if water spots are not evident to limit any damage to the new
insulation.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
A I
b. Maintenance of the wood decking system is a major problem. To avoid
the accumulation of water on the deck surface, larger gaps are needed
between each board. But this is a hazard to women with high heels.
The water and debris which flows through the gaps accumulate on the
roof membrane below. This area is inaccessible to cleaning. The
consequences of this are eventual decay of the wood decking and
deterioration of the roofing membrane.
Decay of wood decking is not always visibly apparent. The only way to
find out if decay is taking place is to remove selected areas of the
- deck and investigate the existing conditions. There are two
alternatives to deal with this problem. Minor repairs can be made to
the wood decking and at the same time the sloped roof membrane below
the decking should be cleaned out to insure proper drainage. If
extensive repairs to the wood decking or roof membrane are needed, or
positive drainage cannot be easily achieved replacement of the entire
wood decking system is in order. A monolithic surface which does not
trap water and debris will be eventually needed.
7. Holes have been drilled near the edges of the wood decking on the
bridge to alleviate the accumulation of water. These holes along with
the gaps between the wood boards must be periodically cleaned. If
additional drainage is required individual boards should be removed,
and replaced. It should be noted-that over time the wood boards will
be worn in their centers and cup. Periodic replacement of boards will
be required.
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
4•
1 '
I8. The ends of the roof girders should be cleaned and decay should be
repaired. A long term correction would be to cap the ends of the
1 girders with sheet metal, allowing an air space for ventilation. If
this work is not performed in the next few years, the rot could slowly
spread to the region of the support of the girders at the exterior
( walls.
l._
Iry� 9. The electrical receptacles, light switches and fixtures which are not
rfunctioning properly. or are dangerous to occupants should be replaced.
1 '
L
f=
L
L
L
Shannon Community Center
IHansen/Murakami/Eshima, Inc.
t_
45
I
Clean up and repair clay
--
of roof 9irdors. A plq i f
sheet meEal caps .A� ends.
Ell-
.,
' I I
j II it
� ,- ❑ "Refinish . ... ._ . ❑ ❑ ❑r-----ll
� I _ I
.'j Wes - Room '- ❑ Social Nall ❑ <•" .;=ash Room .. I
;-114'MIR 1'11
1 C ❑ ❑ j C ❑ i I
T -- -- ------- --- G G
IC
I
Re lava worn /dr rcthed �hrc holds. a vc ecte arc 4!, of
r mo ael d rc s
Rep it 7 re lace broken rccc tacle3, _ deck and invcshi5Ac conditions.
Pa P P Make minor repairs where
:li9hf..switches, Alfusers
^1es� --roo for Icaks prior Lo Clean" out drain holes ' .reyuired..__I�-major repairs arc
E f P required, removal of entire.
painting, insulating, etc. j and s aces between
replace floor finishes pp wood deck and application of
Individual boards. a monolithic Surface
__.• -�l j is recommended.
i
MAIN LEVEL.
0 4 S 16 I RECOMMENDED
MAIN-TENANCE
I - - 46
..................
Courtyard
Pre • .3c6ol l?oom
/*
L
j:
L
j : I
Pl:
• Pa ck cracks in comr-rc�c --,1a6 (w6crr- mfcJeJ)
• R.=p a-c worn / jt-9 r.t+cj tHres6lJs
• Replace crackeJ wool, Doors
/re-pair 6roke-m rcccp�jalcs,
LOWER LEVEL lijk� switc-Hcs, Jilfusers
-0 4 8 ' l6 11E RECOMMENDED'
7rM MAINTENANCE
is
IIV. Construction Cost Analysis
A cost summary for the various modifications considered is included below.
These are rough costs at this time as specific repair methods have not been
developed. These are construction costs only and .do not include costs for
design services, City time, temporary relocation of activities, financing,
furnishings, etc. Also these costs are based on mid 1986 costs of
construction.
1 Areas of Concern" Cost
Modification
L/S H.C. Func. Maint.
1 X X X 2,350 Single door hardware at all locations
(including lever handle, closer,
kickplate, threshold and
(_ weatherstripping etc. )
IX X X 5,000 Double door hardware at all locations
X X X 3,000 Replace 2 sets of double doors at East
Meeting Room with 1 pair of 3'-0" exit
doors (including hardware)
I_ X 3,000 Lower door heights from 10'-6" to 7'-0"
(2 locations)
X X 1,000
Exterior landing level with interior
floor level
�. X
500 Tempered glass in hazardous locations
X 1,500 Safety film on glazing above exitways
X X 6,500 Handrails (interior & exterior)
*Areas of concern relate to the four major categories of work referred to in
the report and listed below. L/S - Life Safety; H.C. - Handicapped Access;
_. Func. - Function; Maint. - Maintenance
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
48
Areas of Concern* Cost Modification
L/S H.C. Func. Maint.
X 2,000 Relocate doors to achieve 18" jambs
X X 7,500 Corridor system from North Entry
through East Meeting Room and storage
room
X 7,000 Acoustic wall panels in Social Hall
X 4,000 Acoustic wall panels in East Meeting
Room
X X 5,000 Remove platform at Social Hall,
relocate wall, provide movable platform
X X 20,000 Kitchen (Remove pantry, warmer.
Replace cabinets. New Wolf range,
oven, microwave, ventilation &
lighting. )
X 4,000 Three semi-private offices within
general office space
X 3,000 Lower counter heights in Pre-school
Room
X 5,000 Install carpeting in lower level
Meeting Room and Pre-school Room
X 5,000 Develop courtyard with planting,
trellises, etc.
X 1,500 Reslope concrete slab to drain at lower
level Meeting Room entry
X X 60,000 Elevator (including new North Entry,
courtyard access & corridor through
Pre-school Room)
X 1,500 Provide accessible drinking fountain
and telephone
X X 10,000 Existing Restrooms (Handicapped access,
increased lighting level, lighter
non-absorbent finishes)
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
49
Areas of Concern* Cost Modification
L/S H.C. Func. Maint.
X 2,000 Ventilation for existing restrooms
X X 20,000 New lower level restrooms
X X 1,000 Exterior access to lower level
restrooms (ramp with handrails)
X 1,000 Diverters at roof over entryways
X 18,000 Roof insulation at Social Hall, East &
' West Meeting Rooms and Offices.
X 2,500 Replace a 20 foot section of solid rail
at deck with spaced wood members.
X 6,000 Repair supports of twisted roof
girders.
X 1,000 Additional nailing of existing plywood
shear walls.
X 300 Repairs to the end bearings of the
steel bridge girders.
X 1,000 Brace wood chandeliers
X 8,000 Air conditioning system for offices
X 7,000 Exposed ductwork from furnace systems
($1,000 ea. system)
X 10,700 Capability for circulation of 100%
outside air. ($2,000 ea. furnace rm. +
$100 ea. furnace)
X 300 Remove electric wall heaters.
X 2,100 Time clock for each furnace system.
_ X 30,000 Replace incandescent lighting system.
Social Hall $10,200
Office 3,100
Lower Meeting Rm. 3,500
East Meeting Rm. 5,000
West Meeting Rm. 3,000
Toilets 800
Hall & Stairs 1,200
Pre-school 3,200
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
50
IAreas of Concern" Cost Modification
L/S H.C. Func. Maint.
fX 12,500 Electrical service conduit and
switchboard to replace existing.
1� X 18,000 Replace vinyl the and sheet vinyl
flooring
LX 3,500
Replace carpeting in West Meeting Room.
I , X unknown Verify and patch leaks in roof.
X 10,000 Remove portions of exterior wood deck
and bridge, investigate and make
repairs.
X 10,000 Repair and cap ends of exposed roof
I girders
, • X 2,100 Replace worn electrical receptacles.
X 900 Replace worn light switches.
TOTAL $326,250 If all corrective work is done.
Economies in construction may be achieved if certain modifications are
combined.
15,000 If entire deck is removed and replaced
with a monolithic surface.
r
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
51
i
V. Summary
1
This report has presented many recommendations which if applied would
enable the Shannon Community Center to operate more efficiently and comply
Iwith current code regulations. The extent to which an existing building
L must comply with current regulations is determined by various agencies.
( , Life and safety issues are in the jurisdiction of local building
. r officials. Handicapped accessibility requirements are governed by state
1 regulations. It is the owner's decision as to what functional or
maintenance items are done.
I_
The only regulations which are specific as to the amount of compliance are
the state requirements for handicapped accessibility. If the total
Iconstruction cost does not exceed $64,000 (current valuation threshold)
( . compliance is limited to the actual work of the project. The following
I. requirements apply regardless of the valuation of the work.
1. The area of remodel must comply.
2. A path of travel to the remodeled area must comply and
L3. bathrooms, telephones and drinking fountains serving the remodeled area
must comply.
ls„ The Shannon Community Center is the home for many community programs
including some geared strictly towards senior citizens and children. We
believe that for this reason the life safety and handicapped accessibility
r items are of the utmost importance.
L
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
IVI. Appendix
I�
I �
f-
f �
L
L
IShannon Community Center
Hansen/Murakami/Eshima, Inc.
53
Peter A®tdueer and AssD�intes, Inc. PPeter
rresidendveer, PE.
Geotechnical Consultants Richard Short, P.E.
Executive Vice President
Ronald Bajuniemi, P.E.
425 ROLAND WAY, OAKLAND, CALIFORNIA 94621, 415/568-4001 Vice President Engineering
Patrick Stevens, P.E.
Geotechnical Engineer
May 30, 1986 Michael McRae, P.E.
K215-26, 08477 Geotechnical Engineer
Dawn Rinaldi, P.E.
RECEIVED Geotechnical Engineer
Hansen/Murakami/Eshima, Incorporated JUN 3 1926
424 Second Street
Oakland, California 94607 HANStN MURAKAMI ESHIMA
Attention: nits. Lorna Dare
RE: GEOTECHNICAL DATA REVIEW
DUBLIN RECREATION CENTER
DUBLIN, CALIFORNIA
Ladies and Gentlemen:
In accordance with your request, we have reviewed the soils report and
other available soil and geological data for the Dublin Recreation Center
located west of San Ramon Road and north of Shannon Avenue in Dublin,
California.
Based on our review, the generally accepted location of the eastern trace
of the Calaveras fault zone in the vicinity of the site has not changed
since the preparation of the Earth Sciences Associates report dated August
1971; and this fault trace essentially follows San Ramon Road. In
addition, more recent geological maps of the area show that traces of the
_ Calaveras fault are located west of the site. These maps indicate that the
structure is not within 50 feet of the presently mapped traces. However,
subsequent to the submittal of August 1971 report, the site was included
within the Alquist Priolo Zone for the Calaveras fault. Under the
guidelines of the Alquist Priolo Act the soil and geological reports for all
structures within the Alquist Priolo Zone are to be reviewed by the
county geologist. We are unaware as to whether the report for the
recreation center was reviewed as required.
Based on our review of the structural drawings we understand that a
_ portion of the building has a structural- wood floor and another section has
a slab-on-grade. This composite floor section was recommended in the
original soils report to avoid the impact of the expansive surface soils
encountered at the site. We understand that the slab-on-grade has
cracked in some locations. These cracks are probably the result of
expansive soils which underlay the slab in some locations.
-._ The conclusions and recommendations presented in this letter have been
made in accordance with generally accepted soil and foundation engineers
principles and practices.
Hansen/Murakami/Eshima, Incorporated
May 30, 1986, 08477
Page 2
If you have any questions regarding this letter, please contact us.
Very truly yours,
PETER KALDVEER D ASSOC. , INC.
Ronald L. Bajuniemi
Soil Engineer CE #2 362
RLB:ms
Copies: Addressee (3)
L
L
L
I
I _ •
55
DAVID LOGAN MESSINGER AND ASSOCIATES, INC.
CONSULTING STRUCTURAL ENGINEERS
4009 WEBSTER STREET, OAKLAND CALIFORNIA 94609
r TELEPHONE (415) 655-9700
June 1 1 , 1986
DAVID L. MESSINGER, S.E.
�1:.;:'J I ! O^ ARTHUR W. ANDERSON, JR., S.E.
GERARD T. OUINN, S.E.
[_ Hansen, Murakami , Eshima, Inc .
Architects and Planners
( 424 - Second Street
Oakland, CA 94607
Attention: Ms . Lorna Dare
Subject : Structural Review
Dublin Recreational Center
(� Dublin, California
l Our Job No . 8640
fLadies and Gentlemen:
Pursuant to our request and authorization,y q we have reviewed the
structural aspects of the subject building .
The purpose of this review is to determine if there are any
serious seismic deficiencies in the structural system , and to
comment on the structural condition of the building.
We were given a half-size set of the architectural, structural,
mechanical , and electrical drawings ; a set of the original
[_ calculations; a soils report; and the structural portions of the
specifications .
LOur review process consisted of the following:
1 ) An initial site visit .
I2) Review of the construction documents supplied.
l.a 3 ) A - final site visit .
L The building is sited west of San Ramon Road and north of Shannon
Avenue in the City of Dublin. It is wood frame -construction,
with the easterly portion being two stories in height, and the
L westerly portion being one story in height. The westerly portion
has a wood framed floor supported by concrete grade beams and
drilled cast-in-place concrete piles. The upper floor of the
easterly portion is of wood framed construction supported by
steel beams , and the ground floor is of slab-on-grade
construction. There is a footbridge which spans the creek to the
south of the building which' is constructed of wood decking on
wood joists which are supported on steel beams. The steel beams
span 54 feet to concrete piers on either side of the creek.
l_
56
I
IMs . Lorna Dare
_ June 11 , 1986
( Page Two
The building was designed by the structural engineering firm of
Goplen and Yokoyama in 1971 to the provisions of the 1970 Uniform
Building Code (UBC). The structural calculations indicate that a
seismic force factor of 20% of the dead weight of the structure
was used for the design of the components of the seismic
resisting system, whereas the UBC would have only required 13.3%
of the dead weight. This more conservative seismic factor was
probably used due to the close proximity of the Calaveras fault,
the 'main trace of which is only about 50-60 feet from the east
end the building.
The structural calculations were well prepared, and our review
indicates that all of the items normally ..considered in the
seismic design of a building were considered. The structural
f drawings and specifications were also well done, and carried out
the intent of the design assumptions of the calculations.
I The soils report was also reviewed and its recommendations were
incorporated in the design of the building. A considerable
effort was made by the soils engineer to locate the fault zone ,
and they found it to be to the east of the building site. Since
the Calaveras fault is considered active , a phenomenon called
"fault creep" is associated with this type of fault. "Fault
creep" expresses itself in relative lateral movement of the
ground on either side of the fault zone. When "fault creep"
occurs through a building, it will distort it, and eventually
pull it apart to an extent that structural components and
(- connections are damaged or destroyed. The . building was examined
1 to see if there was any evidence of "fault creep" damage, and the
only thing which would- suggest damage from "fault creep" was
L slab-on-grade cracking in the lower floor at the east end of the
building; however, we believe that this cracking is due to
heaving of the expansive soils beneath the slab and is not due to
"fault creep".
The
physical condition of the structural elements of the building
were examined where they were accessible . to view, and the
Ifollowing items were observed:
Bridge_Decking: The decking boards on both the bridge and the
L deck at the south side of the building have little or no gap
between which would allow for breathing and drying out of the
wood, and drainage of water. The consequences of this are
L eventual decay. There are many knot holes in the wood decking
which have been patched with sheet metal. Drainage from the roof
spills onto certain areas of the deck, and could eventually lead
to decay. In certain areas of the deck, the boards are spaced
and allow trash and leaves to fall down onto concealed roofing.
The debris on this roof was wet and could eventually lead to
decay of the wood deck as well as deterioration of the roofing
f_
�-7
I
l }
I
Ms. Lorna Dare
June 11 , 1986
IPage Three
material. At the north bearing of the bridge, the steel girders
(- are supported on a neoprene bearing pad and bolted to the
I concrete piers . Slotted bolt holes were provided to allow for
thermal expansion and contraction of the bridge girders, but the
bolts are tight up against one side of the slotted hole. This
f condition could eventually shear off the bolts.
Roof Girder : The roof girders in many cases cantilever beyond
( p the eave of the building, and rain water pours freely off the end
of the eave and the ends of the cantilever girders. The ends of
many of the girders show evidence of decay, and there are lichens
on the ends of the girders . Many of the girders have "heart
centers" and have severely split and twisted. The girders have
twisted in some cases to an extent that the supporting
connections may be damaged.
1_
The following construction deficiencies were noted during our
final site visit :
�- Wood Columns: . The drawings clearly show groupings of four 8"x8 11
wood columns at the primary support for the transverse girders.
611x611 posts were installed.
Plywood Nailing: The back side of certain plywood 'shear walls in the
basement were accessible to view, and it was observed that a
I fairly significant portion of the plywood nailing did not engage
the stud . Also , the nailing of some plywood shear walls was less
than indicated on the drawings .
�- Settelment of Soil at Perimeter of Building:__ __ _ _ng_ We have been told
that there is concern that the settlement of soil around the
L perimeter of the building is caused by seismic activity. It is
our opinion that this settlement is caused by poor initial
compaction rather that seismic related activity.
Throughout the upper floor of the building, there are several
custom made suspended chandiliers which are made of wood and
glass and are suspended from a chain. These chandeliers should
be tied back so they would not swing and be damaged in an
earthquake .
Please let us know if we can be of future assistance .
Very truly yours ,
David L. Messinger
DLM:ff
DAVID LOGAN MESSINGER AND ASSOCIATES, INC.
CONSULTING STRUCTURAL ENGINEERS
4009 WEBSTER STREET, OAKLAND. CALIFORNIA 94609
TELEPHONE (415) 655-9700
DAVID L. MESSINGER. S.E.
July 21, 1986 ARTHUR W. ANDERSON, JR., S.E.
GERARo T OUINN, S.E.
Hansen, Murakmi, Eshima, Inc.
Architects and Planners
424 Second Street
Oakland, CA 94607
- Attention: Ms. Lorna Dare
Subject: Structural Review
Dublin Recreational Center
Dublin, California
Our Job No. 8640
HMEDUBI-8
L Ladies and Gentlemen:
You have asked us to review our letter to you dated June 11,
1986 , and to express our opinion on which of the items listed
therein should be repaired, and give an order of magnitude cost
associated with the repair.
Our comments will follow the order in which the items of concern
were listed in our June 11, 1986 letter.
l_ Bridge and Building Decking: Decay in wood is an isidious
process, and is not always visibly apparent. The bridge and
L building decking, although exposed to winter rain, still appear
to be sound, but we cannot guarantee that decay does not exist.
Certain measures, such as insuring that drainage from the roof is
taken off in some positive manner, and irrigation sprinklers
moved or adjusted so as to not water the deck, could be taken to
slow the decay process.
The only way to find out if decay is taking place is to remove
selected areas of the deck and investigate the existing
conditions. We suggest an allowance of $10,000 to remove
decking, investigate and make repairs.
Roof Girders : The decay and lichens on the overhanging ends of
the girders is more of a maintenance than a structural problem.
A suggested long-term correction would be to clean-up and repair
the decay, and cap the ends of the girders with sheet metal ,
allowing an air space for ventilation. We suggest an allowance
of $10 ,000 to carry out the suggested corrective work. The
twisting of the roof girders is impossible to repair without
removing the entire roof and replacing these twisted girders.
I
5
I
IMs . Lorna Dare
July 21, 1986
Page Two
(-
Wood Columns: 8x8 wood columns were specified, but 6x6 columns
f� were installed. Our calculations indicate that the 6x6 columns
are sufficient to carry the roof loads.
Plywood Nailing: We suggest an allowance of $1,000 to brace the
chandiliers .
During a recent phone conversation, you asked our opinion on
( whether there would be breakage of the large panes of glass
during a large earthquake. The architectural drawings indicate
that the glass is merely held by wood stops with no indicated
allowance for movement. It is difficult, if not impossible, to
calculate the movements during an earthquake of a plywood braced
building. We do know, however, that there will be movement which
will deform the frame in which the glass is held to a
parallelogram shape. The glass is very rigid, but brittle, and
there is a good probability that the glass would shatter in a
large earthquake.
f_. I hope this letter will satisfactorily answer your questions, but
we must re-iterate that the remedial cost suggested is merely our
I "best guess" at this time because we have not developed specific
repair details , and have -not consulted a cost estimator.
IVery truly yours,
CDAVID L. MESSINGER AND ASSOCIATES
LDavid L. Messinger
DLM:ff
c
i
i
I '
DAVID LOGAN MESSINGER AND ASSOCIATES, INC.
CONSULTING STRUCTURAL ENGINEERS
4009 WEBSTER STREET, OAKLAND, CALIFORNIA 94609
TELEPHONE (415) 655-9700
DAVID L. MESSINGER, S.E.
f ARTHUR W ANDERSON, JR., S.E.
October 16 -
IT , 19 8 6 -� GERARD T. OUINN, S.E.
I Hansen, Murakami, Eshima, Inc. \
Architects and Planners
424 Second Street
Oakland, CA 94607
Attention: Ms. Lorna Dare
Subject: Structural Review
Dublin Recreational Center
r Dublin, California
I Our Job No. 8640
. HMEDUB2-8
lLadies and Gentlemen:
Your office has requested that we make a more comprehensive list
l of structural repair costs for the subject building then were
1 outlined in our letters of June 11, 1986 and June 21, 1986. Our
costs are based only on our judgment after viewing the
I deficiencies in the field, and are not based on a professional
estimate made from schematic reconstruction drawings. We will
only comment where we feel the previous correspondence has not
fully explained the cost of repairing the deficiencies:
�-
Order-of-Magnitude Re air Costs - Structural Deficiencies
p
L1. ' Bridge and Building Decking $10,000
2. Repairs to the End Bearings of the Steel
Bridge Girders 300
3 . Metal Caps Over the Ends of the Cantilever
r Roof Girders 10,000
If this work is not performed in the next few
years , the rot could slowly spread to the region
of the support of the girders at the exterior
walls.
4 . Repairs to Twisted Roof Girders 6,000
1--
There is no way to repair twisted wood girders
other than the removal of the existing members
and replacing them with new members. The cost
figure that is quoted is the cost to repair
i .
61
Y
Ms. Lorna Dare
October 16 , 1986
Page Two
possible damage atthe supports of the girders
caused by the twising. Because of the lack of
time to prepare our report, and the lack of a
high ladder to inspect all of the connections,
the actual degree and extent of the damage is
unknown.
5 . Additional Plywood Nailing of Existing Wood Shear
Walls 1,000
6 . Bracing of Four Large Chandiliers 11000
f� Total $28,300
We must emphasize that the above cost figures are only our best
guess, and could vary considerably one way or the other.
The determination of the bracing costs of the typical lights and
the electrical and mechanical equipment is a function of the
electrical and mechanical engineers, and is not included in our
estimate.
Please let us know if we can be of further assistance.
Very truly yours,
DAVID-,Lr MESSINGER AND ASSOCIATES
y�
L ,Arthur W. A derson, Jr
AWA,Jr:ff
L
l
gemoto eins
July 22, 1986
l_ Ms. Lorna Dare
Hansen/Murakami/Eshima, Inc.
424 Second Street
Oakland, CA 94607
Subject: Shannon Park Community Center
Dear Lorna,
We have surveyed the building and noted the following mechanical items:
1. The building is heated by 8 gas fired furnaces located
in mechanical rooms on the upper and lower floors.
` 2. There is one window air conditioning unit located in
the office space.
3. The Men's Toilet and Women's Toilet ventilation louvers
have been removed and sealed off. Therefore, there is no
ventilation in the toilets.
4. There are 3 electric wall heaters with fans providing
heat in the Social Hall .
In reviewing the letter from Ms. Diane Lowart, Recreation Director,
dated April 24, 1986, we list the following comments.
L1. Entire Building , Item 3, "Inefficient heating and
cooling system".
I- Response:
The only cooling at present is located in the Office and provided
Lby a window unit. The gas fired furnaces do not have cooling.
The heating furnace #8 provides heat for the office spaces by duct
work below the floor and floor registers in every room.
618 Grand Avenue• Oakland,California 94610
Telephone(415)835-8438 63
Ms . Lorna Dare
Hansen/Murakami/Eshima, Inc.
Subject: Shannon Park Community Center
July 22, 1986
Page Two
One option is to remove the entire heating furnace and install
a new furnace with a DX cooling coil , remote air cooled conden-
sing unit, new branch ducts and new floor grilles. However, the
entry lobby would have to be heated by another system.
The air circulation from most of the furnaces is very poor due
to the fact that the supply air is very close to the return air
_ and there are no branch supply ducts. In general , the.air dis-
tribution could be improved by installing exposed supply duct-
_ work with wall grilles in the rooms.
2. Kitchen, Item 1 , "Lack of cooking facilities."
Response:
0
If more cooking facilites are added, that implies a range
hood and make up air system would be required.
3. Restrooms , Item 2, "Air Circulation."
Response:
_ Provided toilet exhaust fans with louvers in the door or
transfer grilles in the wall .
I , Best r gards,
Grri�
l_
Sam amoto, P.E.
l_ SY/cd
L
64
nen i o kECEIVED
L 3 _ 30
HANSEN MURAKAMI ESHIMA
July 30, 1986
Ms. Lorna Dare
Hansen/Murakami/Eshima
424 Second Street
- Oakland, CA 94607
Subject: Shannon Park Community Center
Dear Lorna,
Our recommendations for improving the mechanical system and its
related cost are as follows:
1. Add a distribution duct either concealed or exposed on
every furnace system with air outlets. Estimated cost
per furnace system is :
$1000 7 systems x $1000 = . . . . . . . . . $ 7000.00
2. Remove the existing furnace system serving the office
spaces and install a new furnace, dx cooling coil , re-
mote air cooled condensing, distribution ducts below
floor and floor registers.
Estimated cost. . . . . . . . . . . . . . . . . $ 8000.00
3. Add new toilet exhaust fans each of two bathrooms and
extend ducts up thru roof. Door louvers or transfer
grilles to provide makeupair.
Estimated cost. . . . . . . . . . . . . . . . . $ 2000.00
4. Provide time clock for each furnace system or control
multiple furnaces.
Estimated cost. . . . . . . . . . . . . . . . . $ 300.00 ea.
5. Provide summer switch for all existing furnaces.
Estimated cost. . . . . . . . . . . . . . . . $ 700.00
618 Grand Avenue•Oakland, California 94610
Telephone(415)835-8438 65
i
July 30, 1986
Ms. Lorna Dare
Hanse/Murakami/Eshima
Subject: Shannon Park Community Center
r
Page Two
r-
I 6. Provide 100% outside air capability for all furnaces.
In some cases it may be impossible because of exist-
ing conditions. However, the existing furnaces do
not have the capability to run at 100% outside air
(� capacity at present.
I . Estimated, cost. . . . . . . . . . . . . . . $ 2000.00 per
furnace- room.
7. Remove the existing electric wall heaters in the
Social Hall . - We understand that these are not
working well at present. Electric heating is
a high energy cost item and this heating could
be replaced by improved duct distribution.
IEstimated cost. . . . . . . . . . . . . . . .$ 300.00
8. We recommend consideration be given to provide
f roof, wall and floor insulation. To provide
additional insulation in cases where there is
existing insulation.
�— 9. If a full kitchen is installed a range hood exhaust
system and make up air system would have to be pro-
vided for the kitchen.
Estimated cost. . . . . . . . . . . . . . .$10,000.00
These are the major items that we can identify up to now. If there are
_ any questions please call . I will be out of town until August 18, 1986 how-
ever, you can leave any messages with Les King of our office.
With gards,
LSam Ya o
SY/cd
66
I
Electrical • Environmental/Process Consultants
iWI L K 1 N S®N E N G■N EG R I N D
618 Grand Avenue Oakland California 94610 • 415 834 4195
18 June 1986
RECEIVED
fJohn Nelson JUN 19 1981,
Hansen/Murakami/Eshima Inc. HANSEN MURAKAMI ESHIMA
424 Second Street
Oakland, CA 94607
Subject: City of Dublin Recreation Center Study
1 Dear John:
r On May 5 , 1986 we visited the site to review the present
I condition of the electrical installation.
Power
�- The existing electrical service is taken at 120/208
volts, three phase, four wire from a PG&E padmount
l transformer located just outside the kitchen door.
l The connected load for the facility, based on the con-
struction documents , is 94 KVA. The available capacity
in the main switchboard is approximately 130 KVA.
Available Capacity . . . . . . . . . . . . . . 130 KVA
l_ Connected Load . . . . . . . . . . . . . . . 94 KVA
Spare Capacity . . . . . . . . . . . . . . . . 36 KVA
L The main switchboard and various lighting panels appear
to be in good condition.
Duplex receptacles and lighting switches are, however,
showing signs of age.
Lighting
Room and exterior lamps are incandescent, with a row of
L very inefficient recessed fluorescent fixtures at the
perimeter of the long walls of each room.
L Most rooms have a ceiling of dark wood, which further
reduces the efficiency of the lighting system.
In the front office and kitchen a single row of suspended
fluorescent fixtures has been added, which provides the
major illumination in those spaces . Esthetically these
67
n
John Nelson
18 June 1986
- Page Two
fixtures are out-of-place.
Many of the fixtures are damaged, door frames are missing,
lenses are missing and lamps are exposed.
It appears that some of the recommendations in the PG&E
energy management checklist of April 25 , 1.984 have been
accomplished. Incandescent lamps have been reduced from
150 watts to 75 watts -- which saves energy, but substan-
tially reduces the lighting level.
The east and west meeting rooms are each illuminated by
two large wooden chandeliers. The chandeliers probably
- do not comply with current seismic code requirements.
I_ (Suspended fixtures must be able to swing to a 45° angle
without striking anything. )
Exterior pathway lights are vandalized and inoperative.
l In the parking area they have been replaced by 30 foot
electroliers .
Emergency lighting is provided by a central battery sys-
tem with remote heads .
Stage lighting consists of four spotlights installed on
a beam in front of the stage.
I Signals
l--
The fire alarm system consists of a flow switch at the
L sprinkler system riser, which is connected to a single
bell on each floor level. Fire alarm pollstations are
not provided, and smoke detectors are not apparent.
Each floor is protected by an infrared or sonic burglar
alarm system.
(� The stage is equipped with a sound system. Use of this
I system has apparently been a problem acoustically, but
whether the recommendations of the Lawrence Livermore
LLaboratory study were adopted is unknown.
Comments
1 . The general lighting system is most inefficient, and
in need of upgrading and repair.
I
John Nelson
18 June 1986
Page Three
2 . Present building finishes are not conducive to light-
ing efficiency.
3 . Based on connected load, there is only 36 KVA (100 amps)
of spare capacity at the main switchboard.
B s egards,
Peter W' on
I .
PW/mco
I.
L
70
7 July 1986
Dublin Recreation Center Study
Changes to consider:
1. Replace existing lighting system with more efficient system, higher
foot candle levels; hardware to be compatible with the existing
structure.
Estimated electrical cost $4.00/sf.
This does not include the cost of providing building
surfaces with higher reflectivity .
2. Replace receptacles and light switches to upgrade
worn devices . . . . . . .$20.00 each .
3. The available spare capacity in the service switchboard is 36 KVA.
This will probably be sufficient to handle the proposed
air conditioning for the front office (8 KVA) , and
various toilet exhaust fans. However, a full service
- kitchen could well overload the existing switchboard,
and would require a larger service.
Estimated cost for new service conduit and new 600 amp service
switchboard to replace existing $12,500.
4. Replace existing pathway lighting luminaires with vandalproof type.
Estimated cost per luminaire. . . . . . . . . $400 each
Wiring to the poles is assumed in good condition.
i_
I
f
I
71
rz
r
4
VII.Bibliography
1. Brooks, Walter Thomas, Shannon Park Community Center (Documents and
Specifications). 1972.
2. California State Building Standards Commission, California
Administrative Code, Title 24, Part 2 (Building, Energy and Handicapped
Regulations). Sacramento, 1984.
3. Earth Sciences Associates, Shannon Park Community Center (Documents and
Specifications). 1972.
4. International Conference of Building Officials, Uniform Building Code.
Whittier, California, 1982, 1985.
5. Peoples Housing Inc, Accessibility Checklist for Public Facilities and
fHousing. Peoples Center for Housing Change, Topanga, California, 1983.
L
L
L
L
Shannon Community Center
Hansen/Murakami/Eshima, Inc.
72
EXHIBIT B
M_ E_M_ 0 R_ A N D U M
TO : Rich Ambrose
FROM : Vic Taugher �,�---
SUBJECT : SHANNON COMMUNITY CENTER BUILDING IMPROVEMENT PLAN
DATE : December 10 , 1986
As requested I have reviewed the architects. recommendations
regarding improvements . Some of the recommendations are the
result of :
1 . Lack of maintenance .
2 . Failure to follow the approved plans or changes after
the completion of the building .
3 . Changes in Building Codes or State Law.
4 . Differing interpretation or application of the Building
Code .
The following are my comments :
Life Safety - I concur with the recommendation .
Handicapped Accessibility - I concur with the recommendation
except as follows :
2 . Widen all doors required for handicapped access .
7 . Title 24 does not require an elevator providing that
each floor level is accessible and that persons
participating in activities on one level are not
required to go to the other level . For example, if day
care occurs only on the lower level and there is no
need for a handicapped person to go to the upper level
to participate , an elevator would not be required.
However , if a handicapped person must go to the office
on the upper level in order to participate in the
program, an elevator would be required. In order to
eliminate the elevator , restrooms would be required on
the lower level .
Function - Architectural
While these are not code issues , the recommendations appear
to be appropriate .
Funcion - Structural /Mechanical /Electrical
I concur with items 1 through 6 , and 11 through 13 . Items
7 through 10 appear appropriate .
Maintenance - I concur with the recommendations . Item 6 is
extremely important .